BASIC DC Solareg II Operating Manual - Controller Functions

Manual is about: Microcontroller-controlled temperature difference controller for solar thermal systems

Summary of Solareg II

  • Page 1

    Microcontroller-controlled temperature difference controller for solar thermal systems operating manual solareg ii basic dc.

  • Page 2

    2 inhalt 1 application area / device features 3 1.1 application area 3 1.2 device features 3 2 safety instructions 3 3 mounting the device 4 3.1 opening the device 4 3.2 wall mounting 4 3.3 connections 5 3.4 temperature sensor connection 5 4 short descriptions and device operation 5 4.1 display layo...

  • Page 3: 2  Safety Instructions

    3 1 application area / device features 1.1 application area the solareg ii basic dc controllers are high-performance microprocessor-con- trolled units for controlling the functions of solar thermal systems. They are suitable for most types of south facing solar thermal systems. The controller is onl...

  • Page 4: 3  Mounting The Device

    4 3 mounting the device 3.1 opening the device the upper part of the housing is locked to the lower part using two latches. Pull the side pieces (cover plates) of the upper part of the housing outwards (see picture) to unlatch it and upwards until the cover plate is opened. 3.2 wall mounting the dev...

  • Page 5

    5 3.3 connections the following points must be followed for the 12v connections: ◼ we strongly recommend using a 12v lead gel rechargeable battery for this device. Other rechargeable battery types can also be used, but only after taking into account the end-of-charge voltage. A fuse that corresponds...

  • Page 6: 5  Menu Structure

    6 4.2 operating the device the solareg ii controller is convenient and easy to operate using four operating buttons. Using the operating buttons, you can: access display values ◼ perform device settings ◼ the graphic display symbols allow you to easily navigate through the operating structure. The o...

  • Page 7

    7 display e.G. Meaning can be reset 13,2 measured voltage u=solar module ua=battery (only if connected) no 5.2 "programming" menu the operating parameters are displayed and can be changed, if necessary, in the programming menu. The preset values generally ensure fault-free system operation. Display ...

  • Page 8: 6  System Diagrams

    8 6 system diagrams 1 collector, 1 storage tank s1 a1 s3 s2 fuse a4 + m a1 m0 b s1 s2 s3 12v connections b battery + mo module + m earth a1 solar circuit pump (switching output 1) a4 potential-free sensor connections s1 collector sensor s2 lower storage tank s3 general temperature point the ground o...

  • Page 9: Controller Functions

    9 controller functions 7.1 general controller functions the controller compares the temperatures of the various measuring points and op- timally charges the storage tank. If the collector temperature exceeds the storage tank temperature, the solar circuit pump is switched on. Monitoring and protecti...

  • Page 10

    10 7.2.3 system protection if the collector temperature exceeds the collector protection temperature (see 7.2.2) by 10k, the solar circuit pump is switched off to protect the system compo- nents. If the collector temperature drops below the collector protection temperature, the solar circuit pump is...

  • Page 11

    11 settings table for the switch-off threshold values for rechargeable battery operation values without rechargeable bat- tery position switch-off voltage in volts position switch-off voltage in volts 0 10,0 0 8,0 1 10,2 1 8,2 2 10,4 2 8,4 3 10,6 3 8,6 4 10,8 4 8,8 5 11,0 5 9,0 6 11,2 6 9,2 7 11,4 7...

  • Page 12: 8  System Monitoring

    12 8 system monitoring if an error occurs, the flashing symbol is generally displayed. 8.1 sensor monitoring the connected sensors and sensor cables are monitored for interruptions and short-circuits. Errors are indicated by the symbol. You can find the error source by scrolling up or down the info ...

  • Page 13: 9  Troubleshooting

    13 9 troubleshooting system faults are distinguished into two general categories: faults that are automatically detected by the controller and therefore can be ◼ displayed using error messages faults that the controller cannot detect ◼ 9.1 faults with error messages error indication in the display p...

  • Page 14

    14 9.2 faults without error messages faults and malfunctions that cannot be displayed as well as possible causes and their error source can be identified using the following table. If you cannot remedy the fault using the description below, contact the supplier or installer. Problem possible causes ...

  • Page 15

    15 10 solareg ii specifications housing material 100% recyclable abs housing for wall mount- ing dimensions l x w x d in mm, weight 175 x 134 x 56; approx. 360 g protection class ip20 according to din 40050 electrical specifications operating voltage dc 12 volts max. Module voltage. Dc 23 volts max....

  • Page 16: 12  Warranty Conditions

    16 12 warranty conditions the solareg ii controllers are carefully produced and tested on an automatic testing station. If any failures occur, first check if there are any operation / setting or system errors. Furthermore, check the pump and temperature sensor connections. Prozeda gmbh provides a 2-...