SELF-TROUBLE DIAGNOSTIC FUNCTION
When machine fails, err lamp light up and following display appears :
display
remark
*** SYSTEM ERROR ***
INDOOR FILTER CLOG
suction hole filter is clogged
*** SYSTEM ERROR ***
AXP CONTACT OPEN
- air cooling type : cooling tower
fails or does not operate
- water cooling type : poor
external auxiliary signal
*** SYSTEM ERROR ***
INDOOR FAN OVER LOAD
indoor blower motor overload
(overload relay operates)
*** SYSTEM ERROR ***
OUTDOOR 1 OVER LOAD
- air cooling type : comp1 overload
- water cooling type :
outdoor unit 1 overload
high/low pressure switch
over currant relay, thermal protector
*** SYSTEM ERROR ***
OUTDOOR 2 OVER LOAD
- air cooling type : comp2 overload
- water cooling type :
outdoor unit 2 overload
high/low pressure switch
over currant relay, thermal protector
*** SYSTEM ERROR ***
OUTDOOR 3 OVER LOAD
- air cooling type : comp3 overload
- water cooling type :
outdoor unit 3 overload
high/low pressure switch
over currant relay, thermal protector
*** SYSTEM ERROR ***
OVER HEATING(BURN)
heater or humidifier overheating
over heating protector
*** SYSTEM ERROR ***
C/D WATER OVER FLOW
condensate overflow
*** SYSTEM ERROR ***
ROOM SENSOR TROUBLE
poor temperature and humidity
sensor open or short
*** SYSTEM ERROR ***
WATER EMPTY
insufficient humidifier water
*** SYSTEM ERROR ***
HUMIDIFIER FAULT
humidifier over currant
exceed the 140% setting regular
currant
*** SYSTEM ERROR ***
OUT FAN 1 OVER LOAD
outdoor unit fan1 overload(AHU)
over currant relay
thermal protector
*** SYSTEM ERROR ***
COMPRESSOR 1 OVER LOAD
comp1 overload(AHU)
high/low pressure switch
over currant relay, thermal protector
*** SYSTEM ERROR ***
OUT FAN 2 OVER LOAD
outdoor unit fan2 overload(AHU)
over currant relay
thermal protector
*** SYSTEM ERROR ***
COMPRESSOR 2 OVER LOAD
comp1 overload(AHU)
high/low pressure switch
over currant relay, thermal protector
☞
INDOOR FILTER CLOG, INDOOR FAN OVER LOAD, C/D WATER OVER FLOW, ROOM SENSOR TROUBLE,
HUMIDIFIER
FAULT ERROR happened, stop machine automatically. After error fixed, and then RUN switch pressed
error was reset, machine operated by one more run switch pressed.
☞ The following phenomena does not mean trouble:
(1) When room temperature is displayed LO℃ or HI℃ : This product displays room temperature between
0 40℃, and displays L℃ or HI℃ if room temperature exceeds this range.
(2) When room humidity is displayed LO%RH or HI%RH : This product displays room humidity between
30 80%RH, and displays LO%RH or HI%RH if room humidity exceeds this range.
(3) In principle the micro computer of this product is designed in the manner that two compressor
and humidifiers are installed, respectively(2 steps). For some models, however, it is designed
in the manner that one E.A of compressor and humidifier are installed, respectively(1 step).
In this case compressor and humidifier are displayed on LCD in 2 steps. For the models equipped
with each one E.A of compressor and humidifier, compressor or humidifier is operating in one
step if one of compressor 1 or 2, or one of humidifier 1 or 2 operates. If the machine used
three E.A of compressor, operation condition displayed on LCD in 3 steps. In case of used AHU
controller, displayer 4 step.