C.P. Electronics SPIR-PRM Product Manual - Part Numbers
LOAD
16 Amp resistive load
10 Amp incandescent lighting
6 Amp fluorescent lighting
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary of transformer)
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
Quartz halogen heaters: 2600W max, recommended timing 30 minutes, for lower timing switch
via contactor
SUPPLY VOLTAGE
220-240 Volts AC 50 Hz
TIME OUT PERIOD
Adjustable 10 seconds to 60 minutes in two ranges
LIGHT LEVEL
Optional adjustment by thumbwheel light to dark.
TERMINAL CAPACITY 2.5mm
2
MATERIAL
Flame retardant ABS
TYPE
Class 2
TEMPERATURE
-10°C to 35°C
CONFORMITY
EN60669-2-1
EN55015
LOAD DOES NOT COME ON
Check to see if the live supply to the circuit is
good. Strap across the L and LIVE OUT termi-
nal to turn the load on.
If the supply and wiring are good, check the
LUX level setting. Increase the LUX level set-
ting to allow the controller to turn on at higher
ambient natural light level.
LIGHTS DO NOT GO OFF
Ensure that the area is left unoccupied for a
greater time period than the time out period set
using the switch.
Make sure that the sensor is not adjacent to
circulating air, heaters or lamps.
Part Numbers
Fault Finding
Specification
SPIR-PRM
Wall mounted PIR presence detector
Setup
Switch settings
Time setting
Lux setting
1.
Set the LUX level thumbwheel fully clockwise.
2.
Set the time to minimum (fully anticlockwise) and set both switches to ON (0-1/2 hour range, no power up delay) according to the diagram.
3.
Apply power—the load should come on immediately.
4.
Vacate the room or remain very still and wait for the load to switch off (should take no more than 2 minutes).
5.
Check that the load switches on when movement is detected.
6.
To set the final LUX level wait until the level of natural daylight is just enough that lighting is required. Starting with the LUX thumbwheel fully
anti-clockwise. Very slowly turn the thumbwheel clockwise until the lights come on. Note that when the LUX thumbwheel is fully clockwise then
the lights will always come on with occupancy.
7.
Select the time out range using switch 1 according to the diagram. Set the time out period using the thumbwheel, fully clockwise is the maxi-
mum (either 1/2 hour or 1 hour depending on the range).
8.
If required, select the power up delay using switch 2 (to prevent the load coming on immediately on power up).
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
FM 45789
EMS 534520
C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel:
+ 44 (0) 333 900 0671
Fax:
+ 44 (0) 333 900 0674
www.green-iswitches.co.uk
enquiry@green-iswitches.co.uk
Ref: #WD283 Issue 3
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE Wiring
Regulations and any applicable Building Regulations.