Camille Bauer SIRAX MM1200 Operating Instructions Manual - page 43
PM 1000268 000 00
Device handbook SIRAX MM1200
43/48
Explanation for 4X register:
Adress
Parameter
Description
40001
Demand Reset
Demand Reset is used to reset the Demand parameter. A value of zero must be Written to this regis-
ter to reset the Demand period. Writing any other value will return an error.
40003
Demand Period
Demand period represents demand time in minutes. The applicable values are 8,15,20 or 30. Wri-
ting any other value will return an error.
40005
Energy display on
Modbus
This address is used to set energy display on MODBUS in Wh, KWh & Mwh.
Write one of the following value to this address.
1 = Energy in Wh. 2 = Energy in KWh.
3 = Energy in MWh.
40007
System Voltage
This address is read only and displays System Voltage
40009
System Current
This address is read only and displays System Current
40011
System Type
This address is used to set the System type.
Write one of the following value to this address.
1: 3 Phase 3 Wire
2: 3 Phase 4 Wire.
Writing any other value will return error.
40013
Pulse Width
of Relay
This address is used to set pulse width of the Pulse output.
Write one of the following values to this address:
60: 60 ms
100: 100 ms
200: 200 ms
Writing any other value will return error.
40015
Reset Energy Counter
This address is used to reset the Energy Counter. Write zero value to this register to reset the energy
counter. Writing any other value will return an error.
40017
Run/On Hour & Inter-
ruption reset
This address is used to reset the Run/On hour & number of Interruption. Write zero value to this
register to reset the Run/On hour & number of Interruption.
Writing any other value will return an error.
40019
Rs485 Set-up Code
This address is used to set the baud rate, Parity, Number of stop bits. Refer to TABLE 3 for details.
40021
Node Address
This register address is used to set Device address between 1 to 247.
40023
Pulse Divisor
This address is used to set pulse divisor of the Pulse output.
Write one of the following values to this address for Wh:
1: Divisor 1
10: Divisor 10
100: Divisor 100
1000: Divisor 1000 & in KWh & MWh Divisior will be 1 default. Writing any other value will return an
error. Pulse rate divisor is set to 1, when Energy on Rs485 is set to kWh or MWh.
40025
Min - Reset
This address is used to reset the Min parameters value. Write Zero value to this register to reset the
Min parameters. Writing any other value will return an error.
40027
Max - Reset
This address is used to reset the Max parameters value. Write Zero value to this register to reset the
Max parameters. Writing any other value will return an error.
40029
Analog Out 1-
Para Set
This address is used to set the parameter for Analog Output 1. Write one of the parameter no. As
per the options given in Table 2 for Analog & Limit Output Parameters.
Writing any other value will return an error.
40031
Analog Out 2-
Para Set
This address is used to set the parameter for Analog Output 2. Write one of the parameter no. As
per the options given in Table 2 for Analog & Limit Output Parameters.
Writing any other value will return an error.
40033
PT Primary
This address allows the user to set PT Primary value. The maximum settable value is 692.8kV L-L
depends on the per phase 666.6MVA Restriction of power combined with CT primary.
40035
CT Pimary
This address allows the user to set CT Primary value. The maximum settable value is 9999 & also
depends on the per phase 666.6MVA Restriction of power combined with PT primary.
40037
Sys Power
System Power (Read Only) is the Nominal system power based on the values of Nominal system volts
and Nominal system current.
40039
Energy digit Reset
Count
This address is used to set the rollover count for energy. If Energy on Rs485 is in Wh rollover count
can be from 7 to 14. If it is in KWh then rollover count can be from 7 to 12 & for MWh rollover count
can be from 7 to 9.