Campbell CS105 Instruction Manual - Vaisala
CS105/CS105MD Barometric Pressure Sensor
VAISALA
EXT. TRIG
AGND
GND
SUPPLY
VOUT
PRESSURE TRANSMITTER
MODEL
SERIAL NO
RANGE
OUTPUT
SUPPLY
PTB101B
P4450003
600-1060 hPa
0-2.5 VDC
10-30 VDC
MADE IN FINLAND
6H Green - Pressure (VOUT)
6L White - Signal Ground (AGND)
12 V Switch Red - 12 VDC (SUPPLY)
GND Black - Power Ground (GND)
FIGURE 4. CS105MD Wiring Diagram
5
Summary of CS105
Page 1
Cs105/cs105md barometric pressure sensor revision: 3/07 c o p y r i g h t © 1 9 9 5 - 2 0 0 7 c a m p b e l l s c i e n t i f i c , i n c ..
Page 2: Warranty and Assistance
Warranty and assistance the cs105/cs105md barometric pressure sensor is warranted by campbell scientific, inc. To be free from defects in materials and workmanship under normal use and service for twelve (12) months from date of shipment unless specified otherwise. Batteries have no warranty. Campbe...
Page 3
Cs105/cs105md table of contents pdf viewers note: these page numbers refer to the printed version of this document. Use the adobe acrobat® bookmarks tab for links to specific sections. 1. General .........................................................................1 2. Specifications ..............
Page 4
This is a blank page..
Page 5: Sensor
Cs105/cs105md barometric pressure sensor 1. General the cs105 analog barometer uses vaisala’s barocap ® silicon capacitive pressure sensor. The barocap sensor has been designed for accurate and stable measurement of barometric pressure. The cs105 outputs a linear 0 to 2.5 vdc signal that corresponds...
Page 6: 3. Installation and Wiring
Cs105/cs105md barometric pressure sensor supply voltage: 10 to 30 vdc supply voltage control: when enabled with an internal jumper, the cs105 is on continually. When disabled, the cs105 can be turned on/off with 5 vdc/0 vdc. Supply voltage sensitivity: less than 0.1 mb current consumption: µa (quies...
Page 7
Cs105/cs105md barometric pressure sensor figure 1. Cs105 mounted on the backplate of an enc12/14 enclosure, and connected to a cr1000 datalogger internal battery temparary batter made in usa bpalk 12v alkaline battery pack logan, utah vaisala ext. Trig agnd gnd supply vout pressure transmitter model...
Page 8: Vaisala
Cs105/cs105md barometric pressure sensor vaisala ext. Trig agnd gnd supply vout pressure transmitter model serial no range output supply ptb101b p4450003 600-1060 hpa 0-2.5 vdc 10-30 vdc made in finland see table 1 blue - pressure (vout) see table 1 yellow - signal ground (agnd) continuous 12 vdc re...
Page 9: Vaisala
Cs105/cs105md barometric pressure sensor vaisala ext. Trig agnd gnd supply vout pressure transmitter model serial no range output supply ptb101b p4450003 600-1060 hpa 0-2.5 vdc 10-30 vdc made in finland 6h green - pressure (vout) 6l white - signal ground (agnd) 12 v switch red - 12 vdc (supply) gnd ...
Page 10: 4. Programming
Cs105/cs105md barometric pressure sensor 4. Programming 4.1 cs105md programming the metdata1 station for the cs105md is done through campbell scientific’s short cut program. Short cut includes code in the .Dld file to correct for elevation. 4.2 cs105 atmospheric pressure changes little with time. In...
Page 11
Cs105/cs105md barometric pressure sensor example 1. Cr1000 program for measuring the cs105 once every hour 'main program beginprog scan(5,sec,1,0) 'cs105 barometric pressure sensor measurement bp_mmhg: if iftime(59,60,min) then portset(1,1) if iftime(0,60,min) then voltse(bp_mmhg,1,mv2500,1,1,0,_50h...
Page 12
Cs105/cs105md barometric pressure sensor 07: real time (p77) 1: 0110 day,hour/minute 08: sample (p70) 1: 1 reps 2: 1* loc [ p_mb ] -input locations- 1 p_mb * proper entries will vary with program and datalogger channel, and input location assignments. ** on the 21x use the 5000 mv slow range. Exampl...
Page 13: 5. Long Lead Lengths
Cs105/cs105md barometric pressure sensor -input locations- 1 p_mb * proper entries will vary with program and datalogger channel, and input location assignments. ** on the 21x use the 5000 mv slow range. Example 4. 21x program for measuring the cs105 every execution interval using an excitation chan...
Page 14
Cs105/cs105md barometric pressure sensor example 5. Cr10(x) program for measuring the cs105 once every hour with instruction 2 (differential measurement) ;{cr10x} ; *table 1 program 01: 10 execution interval (seconds) 01: if time is (p92) 1: 59 minutes (seconds --) into a 2: 60 interval (same units ...
Page 15: 7. Maintenance
Cs105/cs105md barometric pressure sensor 6. Correcting pressure to sea level the weather service, most airports, radio stations, and television stations reduce the atmospheric pressure to a common reference (sea level). Equation 1 can be used to find the difference in pressure between the sea level ...
Page 16
Cs105/cs105md barometric pressure sensor this is a blank page. 12.
Page 17: Appendix A. Daily Average
Appendix a. Daily average if the cs105 will be measured every minute or faster, and a daily average is required, follow example 5. In example 5 the daily average, maximum, and minimum pressure is recorded at midnight. A constant is subtracted from the pressure before the average instruction is execu...
Page 18
Appendix a. Daily average 08: average (p71) 1: 1 reps 2: 2* loc [ p_const ] 09: if flag/port (p91) 1: 10 do if output flag is high (flag 0) 2: 30 then do 10: z=x+f (p34) 1: 3* x loc [ p_mb_avg ] 2: 800 f 3: 3* z loc [ p_mb_avg ] 11: end (p95) 12: if time is (p92) 1: 0 minutes (seconds --) into a 2: ...
Page 19
This is a blank page..
Page 20
Campbell scientific companies campbell scientific, inc. (csi) 815 west 1800 north logan, utah 84321 united states www.Campbellsci.Com info@campbellsci.Com campbell scientific africa pty. Ltd. (csaf) po box 2450 somerset west 7129 south africa www.Csafrica.Co.Za cleroux@csafrica.Co.Za campbell scient...