Dacor DR30E Installation Instructions Manual - Warning
3
Product Specifications
wARNINg
IMPORTANT: Observe all governing codes and ordinances
during planning and installation. Contact your local building
department for further information.
Electrical Requirements (U.S.A.
and Canadian Slide-in Units)
It is the owner’s responsibility to ensure that a licensed electrician
performs the installation of the electrical supply for this appliance.
The electrical installation, including minimum supply wire size,
must comply with the National Electric Code ANSI/NFPA 70 (latest
revision) and local codes and ordinances.
A copy of this standard
may be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, Massachusetts 02269-9101
The correct voltage, frequency and amperage must be supplied
to the appliance from a dedicated, grounded, single phase circuit
that is protected by a properly sized circuit breaker or time-delay
fuse. If a time-delay fuse is utilized, fuse both sides of the line (L1
and L2).
Electrical Specifications
Circuit Requirements
Total Connected Load
240 Vac 60 Hz, 4-wire*, 50 Amp.
11.94 kW (49.75 Amp.)
* Two 120 Vac hot (L1 and L2), one neutral (N1) and one ground.
The above electrical specifications are for reference only. See
the range data label for exact specifications. See inside cover for
location.
•
The wiring needs to be long enough to allow the range to be
pulled out for service, while remaining connected.
•
The wiring connected to the range must:
◊ Meet NEMA standards and have a minimum rating of
250 Volts @ 50 Amp.
◊ Include a strain relief
◊ Be terminated by tinned leads, closed loop terminals or
open ended spade lugs with upturned ends
◊ Connect to a junction box or receptacle installed by a
licensed electrician
The appliance may be connected one of the following ways:
•
Using conduit:
◊ A 4-wire conduit connected to a 4-wire junction box, or
◊ A 3-wire conduit (where local code permits) connected to
a 3-wire junction box.
Suggested conduit wiring color code: black, white, red
and green.
•
Using an appliance cord:
◊ A 4-wire appliance cord equipped with a NEMA 14-50P
plug connected to a NEMA 14-50R receptacle, or
◊ A 3-wire appliance cord (where local code permits)
equipped with a NEMA 10-50P plug connected to a
NEMA 10-50R receptacle
Appliance cord plug must be UL listed type SRD or SRDT.
Electrical Requirements
(Canadian Freestanding Units)
•
It is the owner’s responsibility to ensure that the required
4-wire electrical outlet is installed by a licensed electrician
as specified below prior to range installation. The electrical
outlet installation, including minimum supply wire size and
grounding, must be in accordance with all governing codes
and ordinances.
•
The correct voltage, frequency and amperage must be
supplied to the appliance from a separate, grounded, circuit
that is protected by a properly sized circuit breaker or time
delay fuse. If a fuse is utilized, fuse both sides of the line (L1
and L2). Refer to the ratings on the range rating label.
Electrical Specifications
Circuit Requirements
Total Connected Load
240 Vac 60 Hz, 4-wire*, 50 Amp.
11.94 kW (49.75 Amp.)
The ratings above are for reference only - refer to the range rating
label (see inside cover).
•
Freestanding ranges equipped for use in Canada come pre-
wired with a 4-wire appliance cord and NEMA 14-50P plug.
•
Do not modify the factory wiring. The plug is designed to plug
directly into a NEMA 14-50R electrical receptacle installed by
a licensed electrician according to the above specifications.
NEMA 14-50P Plug
NEMA 10-50P Plug
NEMA 14-50R Receptacle
NEMA 10-50R Receptacle