Dimplex R7 Installation Instructions Manual

Summary of R7

  • Page 1

    Installation instructions important please read this leaflet carefully and retain for further use. Note also the information given on the heater • the installation must be carried out by trained personnel. • a means for disconnection must be incorporated in the fi xed wiring in accordance with the w...

  • Page 2: Installation  Instructions

    Installation instructions preparation the heater will arrive separately from its storage bricks, the following bricks will be required. R 7 / 8 / 10 - 40 bricks r12 - 48 bricks r15 - 64 bricks electrical supply two supplies are required for the operation of this heater - for ‘on-peak’ and ‘off-peak’...

  • Page 3: Ventilation & Ducting

    Ventilation & ducting cupboard ventilation - when the heater is installed in a cupboard, two return grilles should be provided in the cupboard door or wall. The top of the high level grille should be approximately 50mm below the top of the cupboard and the bottom of the low level grille approximatel...

  • Page 4: Fig. M

    Main element supply - single phase connect the live (coloured red or brown) of the main supply cable (i.E. That cable supplying the heating elements) to the d.I.N. Connector block marked ‘l1’ and the neutral lead (coloured blue or black) to the neutral terminal marked ‘n’. Connect all earth leads (b...

  • Page 5: Fig. N

    6. Core assembly - see fig. T note: it is essential that the thermal insulation, especially the moulded air passages, are not damaged during assembly. Follow these instructions carefully. Care must be taken to ensure that the bricks, when fi tted, do not intrude into the space allowed for air passag...

  • Page 6: Fig.  R

    9. Commissioning the unit when the heater has been completely assembled it will be necessary to commission the unit. This entails checking that the unit is functioning properly, that the airfl ow delivered is correct for the installation and that the outlet air temperatures are acceptable. Fan speed...

  • Page 7

    Special instructions for conversion from r10 to r7 / r8 heater follow these instructions carefully to ensure the electricaire units operate safely and reliably. The build of the storage core for models r7, r8 and r10 is identical (see diagram model no. R7/8/10). Elements must only be fi tted as indi...

  • Page 8: Recycling

    Electricaire 71186 issue 8 : 02.09 installer note : please ensure that the user instructions are handed to the user when you have completed the installation if applicable, or left with the heater if the building is unoccupied when the installation is carried out. Dimplex uk ltd, millbrook house, gra...