Eaton 5000 RT Installation And User Manual - 2. Installation

Manual is about: Pulsar Series

Summary of 5000 RT

  • Page 1

    W w w . E a t o n . C o m installation and user manual mx 5000 rt — ups exb rt — extended battery transformer 5000 pulsar series.

  • Page 3

    W w w . E a t o n . C o m installation and user manual mx 5000 rt — ups exb rt — extended battery transformer 5000 revision history mx installation and user manual, 86-87050-00 revision: a00 ecn#: 004747 04/2006 revision: a01 ecn#: 004773 05/2006 copyright © 2008 eaton all rights reserved. For techn...

  • Page 5: Contents

    Contents 86-87050-00 a02 - page 3 introduction ....................................................................................................................... 5 important safety instructions ............................................................................................ 6 symbol...

  • Page 6: Contents

    86-87050-00 a02 - page 4 6. Life cycle monitoring (lcm) 6.1 description ...................................................................................................................... 31 7. Maintenance 7.1 hot swapping the power sub-module. .......................................................

  • Page 7: Introduction

    Introduction thank you for selecting an eaton product to protect your electrical equipment. The mx range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your ups (uninterruptible power system). Warning : t...

  • Page 8

    Important safety instructions save these instructions. This manual contains important instructions that should be followed during installation and maintenance of the ups and batteries. The mx models that are covered in this manual are intended for installation in an environment within 0° to 40°c, fr...

  • Page 9

    Symbol usage important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audible signal. Led off. Led on. 86-87050-00 - page 7.

  • Page 10

    86-87050-00 a02 - page 8 (this page left blank intentionally).

  • Page 11: 1. Presentation

    1. Presentation 1.1 standard positions tower position rack position 86-87050-00 a02 - page 9 dimensions (h x w x d) in inches/mm mx 5000 rt 17.5 x 5.16 x 29.2/ 444.5 x 131 x 741.4 mx exb rt 17.5 x 5.16 x 25.6/ 444.5 x 131 x 650 transformer 5000 17.5 x 3.5 x 25.6/ 444.5 x 88.9 x 650 weights in lbs/kg...

  • Page 12: 1. Presentation

    1.2 rear panels mx 5000 rt mx exb rt transformer 5000 batt. No. 200-250v~,24 a rpo rs-232 caution : do not disconnect ba tt er y cabl e under load ba tt er y connect or 1 80 vd dc 1 5 8 9 10 4 6 7 2 3 13 11 12 12 load 4 / 120v~,16 a load 1 120v~,16a load 2 120v~,16a set th is sw itc h w hen unp ow e...

  • Page 13: 1. Presentation

    1. Presentation 86-87050-00 a02 - page 11 1.3 display and control panel (20) load protected led (21) downgraded operation led (22) load not protected led (23) alphanumeric display (24) escape (cancel) button (25) function buttons (scroll down) (26) function buttons (scroll up) (27) enter (confirm) b...

  • Page 14: 1. Presentation

    86-87050-00 a02 - page 12 1. Presentation 1.5 extended battery (exb) mx rt offers a standard backup time of 5 minutes at full load. To increase backup time, it is possible to connect mx exb rt modules to the upss for backup times up to 62 minutes (at full load). Battery extensions for mx rt mx 5000 ...

  • Page 15: 2. Installation

    86-87050-00 a02 - page 13 2. Installation 2.1 unpacking and contents check ups module contents (87050) 46 47 option (66102) optional transformer module contents (87102) 45 43 54 49 51 step down transformer is designed to provide isolated 120 volts ac outlets. Optional battery module contents (87103)...

  • Page 16: 2. Installation

    86-87050-00 a02 - page 14 2. Installation 2.2 internal battery connection (battery start-up) ba tt . N o . 200 -25 0v~ ,24a rp o rs- 23 2 cau tion : do no t d isc onn ect bat ter y c abl e un der loa d bat ter y co nn ect or 180 vdd c 59 60 input cable l6-30p 2.3 installation in tower position follo...

  • Page 17: 2. Installation

    86-87050-00 a02 - page 15 2. Installation 2.4 installation in rack position adjustment of the orientation of the logo and control panel 2 3 1 ups module rack mounting mx rt is very heavy. To ease its rack integration, we strongly recommend to remove the battery tray as shown below. See section 7.2 f...

  • Page 18: 2. Installation

    86-87050-00 a02 - page 16 2. Installation do not install the ups or battery module in hermetic closed environments without any exchange of air. Follow steps 1 to 4 for rack mounting the ups onto the rails. The rails and the necessary mounting hardware are supplied by eaton. Note for step 1: it is po...

  • Page 19: 2. Installation

    2. Installation 86-87050-00 a02 - page 17 2.5 communication ports mx rt provides 4 communication methods. 1. The rs232 port provides communications using eaton serial hid ups transfer (shut) protocol. The shut protocol is compatible with the power management applications available on the enclosed so...

  • Page 20: 2. Installation

    86-87050-00 a02 - page 18 remote power off communication port (9) installation of a remote power off function must be carried out in compliance with applicable regulations. In order to fully de-energize mx rt with the rpo port, it is necessary to use a two-position switch (normally open or closed co...

  • Page 21: 2. Installation

    86-87050-00 a02 - page 19 2. Installation 2.7 hardwire connection of output power cable to ups w this type of connection must be carried out by qualified electrical personnel. W before carrying out any connection, check that the battery circuit breaker and the upstream protection device (normal ac s...

  • Page 22: 2. Installation

    86-87050-00 a02 - page 20 2. Installation 2.8 connection to output receptacles ba tt . N o . 200 -250 v~, 24a rp o rs- 23 2 cau tio n: do no t d isc on nec t bat ter y c abl e un der loa d bat ter y co nn ect or 180 vdd c 1. Connect the equipment to the ups 4 nema l6-30r. If more than one load is co...

  • Page 23: 3. Operation

    3. Operation 3.1 initial start-up to ensure that your system is configured in complete accordance with safety regulations and to benefit from the manufacturer’s warranty, please contact technical support at www.Eaton.Com or call (800) 279-7776. 1. Check that the battery disconnect switch (60) on top...

  • Page 24: 3. Operation

    86-87050-00 a02 - page 22 3. Operation 3.3 operating modes normal mode this is the standard operating mode, set by default in the factory. Under normal condition (normal ac source available): led (20) is on. Leds (30), (32), (34) are green. The equipment is protected by the ups. Eco mode the main ad...

  • Page 25: 3. Operation

    86-87050-00 a02 - page 23 3. Operation 3.4 operation on battery power when the normal ac source is not available, the load continues to be protected by the ups. Power is supplied by the battery. Transfer to battery power leds (20), (21) are on. Leds (31), (32), (34) are green. The audible alarm beep...

  • Page 26: 3. Operation

    86-87050-00 a02 - page 24 3.5 return to normal ac source after an outage, the ups restarts automatically when normal ac source is restored (unless this function has been disabled via ups personalization) and the load is supplied again. 3.6 ups shutdown when ac present before shutdown, please read al...

  • Page 27

    86-87050-00 a02 - page 25 4. Access to maintenance and personalization data 4.1 display organization local settings output settings on/off settings battery settings model ups set-up maintenance measurements alarm history manual battery test led and buzzer test lcm statistics operation limits ups inp...

  • Page 28

    86-87050-00 a02 - page 26 4.4 ups set-up local settings output settings on/off settings function factory setting options language english french, german, italian, portuguese, spanish date/time format international format (dd-mm-yyyy/hh :mm) us (mm-dd-yyyy/hh:mm am/pm) date/time change gmt+ 1(contine...

  • Page 29

    Battery personalization 4.5 maintenance 4.6 ups set-up using external software w insert the solution-pac cd-rom in the drive. W on the first navigation screen, select «point to point solution» and follow the instructions on how to install the personal solution-pac software. W then select «settings»,...

  • Page 30

    86-87050-00 a02 - page 28 (this page left blank intentionally).

  • Page 31: 5. Troubleshooting

    86-87050-00 a02 - page 29 5. Troubleshooting displayed details signification correction no battery the battery is incorrectly connected check battery connections (see section 2.9) i/o bad connection ac source is not connected to the correct terminals check ac wiring no power module the power sub-mod...

  • Page 32: 5. Troubleshooting

    86-87050-00 a02 - page 30 5.3 troubleshooting requiring eaton after-sales support 27 environment fault note: in case of multiple fault, press the “enter” button (27) and the scroll button (25) to get access to further details. 5. Troubleshooting displayed signification correction power module fault ...

  • Page 33

    86-87050-00 a02 - page 31 6. Life cycle monitoring (lcm) 6.1 description this function, embedded in the ups, displays messages on screen, and communication channels, at every important stage of the ups’s life, allowing you to: press the “enter” button (27) to display lcm warning details. Secure your...

  • Page 34

    86-87050-00 a02 - page 32 (this page left blank intentionally).

  • Page 35: 7. Maintenance

    86-87050-00 a02 - page 33 7. Maintenance 7.1 hot swapping the power sub-module this operation must be carried out by qualified electrical personnel only. This operation can be performed without interrupting the equipment. Disconnecting the power sub-module (87100): 1. Remove the 6 mounting screws to...

  • Page 36

    86-87050-00 a02 - page 34.

  • Page 37: 8. Appendices

    86-87050-00 a02 - page 35 8.1 technical specifications (1) if the output voltage is 200v — 250v, the output power is 5000va / 4500w. (2) with one exb module or more, the standard output power is 5000va / 4000w. (3) values for 70% / 100% of ups output. (4) programmable: 200v / 208v / 220v / 230v / 24...

  • Page 38

    86-87050-00 a02 - page 36.

  • Page 39: 8. Appendices

    86-87050-00 a02 - page 37 8. Appendices eaton customer care center technical support and product services technical questions? If you encounter a problem while following the instructions in this manual, or have questions about the operation, repair, or servicing of your equipment, please visit our w...

  • Page 40

    86-87050-00 a02 - page 38.

  • Page 41: 8. Appendices

    86-87050-00 a02 - page 39 8. Appendices 8.2 glossary backup time time that the connected equipment can operate on battery power. Bypass ac source source supplying the bypass line. The equipment can be transferred to the bypass line if an overload occurs on the ups output, for maintenance or in the e...

  • Page 42: Notes

    Notes 86-87050-00 a02 - page 40

  • Page 43

    86-87050-00 a02.

  • Page 44

    Www.Eaton.Com 86-87050-00 a02.