Eaton 5SC 1000i Rack2U Installation And User Manual

Summary of 5SC 1000i Rack2U

  • Page 1

    English copyright © 2016 eaton all rights reserved. 5sc 1 - 3 kva us_en 5sc 1000i rack2u 5sc 1500i rack2u 5sc 2200i rt2u 5sc 3000i rt2u installation and user manual.

  • Page 2

    Page 2 5sc 1 - 3 kva us_en.

  • Page 3

    Page 3 5sc 1 - 3 kva us_en english certification standards uninterruptible power systems (ups) directives: • iec 62040-1: general and safety requirements for ups • iec 62040-2: electromagnetic compatibility (emc) requirements • iec 62040-3: method of specifying the performance and test requirements ...

  • Page 4

    Page 4 5sc 1 - 3 kva us_en safety of persons • the system has its own power source (the battery). Consequently, the power outlets may be energized even if the systems is disconnected from the ac power source. • dangerous voltage levels are present within the system. It should be opened exclusively b...

  • Page 5: Contents

    Page 5 5sc 1 - 3 kva us_en english contents 1. Introduction ....................................................................................... 6 1.1 environmental protection ...................................................................................................6 2. Presentation .......

  • Page 6: 1. Introduction

    Page 6 5sc 1 - 3 kva us_en 1. Introduction thank you for selecting an eaton product to protect your electrical equipment. The 5sc range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your ups (uninterrupt...

  • Page 7: 2. Presentation

    Page 7 5sc 1 - 3 kva us_en english 2. Presentation 2.1 standard installations rack installation d h w tower installation (only for 5sc 2200i rt2u and 5sc 3000i rt2u models) d h w description weights (kg/ lb ) dimensions (mm/ inch ) d x w x h 5sc 1000i rack2u 15.0 / 33.0 405*440*86.2 / 15.9*17.3*3.4 ...

  • Page 8: 2. Presentation

    Page 8 5sc 1 - 3 kva us_en 2.2 rear panels 5sc 1000i rack2u and 5sc 1500i rack2u 4 5 6 1 2 3 5sc 2200i rt2u 2 6 3 1 5 4 5sc 3000i rt2u 2 6 3 1 5 4 (1) socket for connection to ac power source (2) slot for optional communication card (3) outlets for connection of equipment (4) rs232 communication por...

  • Page 9: 2. Presentation

    Page 9 5sc 1 - 3 kva us_en english 2. Presentation 2.3 control panel the ups has a three-button lcd. It provides useful information about the ups itself, load status, events, measurements and settings. Avr % min hz kva kw 7 8 9 7 on/off button 8 scroll down 9 mute alarm 2.4 lcd description 12 11 13 ...

  • Page 10: 3. Installation

    Page 10 5sc 1 - 3 kva us_en 3. Installation 3.1 unpacking and contents check 19 21 22 24 23 25 27 26 20 (19) 5sc ups (20) rail and wall mounting kits (21) quick start, safety instructions and environmental document (22) rs232 communication cable (23) usb communication cable (24) 2 connection cables ...

  • Page 11: 3. Installation

    Page 11 5sc 1 - 3 kva us_en english 3. Installation 3.2 installation of tower models only for 5sc 2200i rt2u and 5sc 3000i rt2u models 3.3 installation of rack models 5sc 1000i rack2u and 5sc 1500i rack2u models follow steps 28 to 30 for model mounting on the rails. Use provided screws on step 28 of...

  • Page 12: 3. Installation

    Page 12 5sc 1 - 3 kva us_en 3. Installation 5sc 2200i rt2u and 5sc 3000i rt2u models follow steps 31 to 33 for model mounting on the rails. Use provided screws on step 33 of installation. Using a longer screw could present a safety risk. 33 33 31 32 31 34 34 the rails and necessary hardware are supp...

  • Page 13: 3. Installation

    Page 13 5sc 1 - 3 kva us_en english 3. Installation 3.4 wall mounting of rack models only for 5sc 1000i rack2u and 5sc 1500i rack2u use provided screws on step 35 of installation. Using a longer screw could present a safety risk. 35 35 36 36.

  • Page 14: 3. Installation

    Page 14 5sc 1 - 3 kva us_en 3. Installation 3.5 communication ports connection of rs232 or usb communication port the rs232 and usb communication ports cannot operate simultaneously. 4 23 22 5 installation of the communication cards (optional) 2 characteristics of the contact rs232 communication por...

  • Page 15: 3. Installation

    Page 15 5sc 1 - 3 kva us_en english 3.6 ups remote control functions the 5sc offers a choice between two remote control functions. • rpo : r emote p ower o ff allow a remote contact to be used to disconnect all the equipment connected to the ups. Restarting the ups requires manual intervention. • ro...

  • Page 16: 4. Operation

    Page 16 5sc 1 - 3 kva us_en 4. Operation 4.1 start-up and normal operation to start the ups: 1. Verify that the ups power cord is plugged in. 2. Press the button on the ups front panel for at least 2 seconds. 3. Check the ups front panel display for active alarms. If the indicator is on, do not proc...

  • Page 17: 5. Maintenance

    Page 17 5sc 1 - 3 kva us_en english 5. Maintenance 5.1 troubleshooting operation status possible cause action overload power requirement exceeds the ups capacity (greater than 105 % of nominal). Remove some of the equipment from the ups. The ups continues to operate, but may shutdown if the load inc...

  • Page 18: 5. Maintenance

    Page 18 5sc 1 - 3 kva us_en 5. Maintenance 5.2 battery-module replacement safety recommendations the battery can cause electrocution and high short-circuit currents. The following safety precautions are required before servicing the battery components: • remove watches, rings, bracelets and all othe...

  • Page 19: 6. Appendices

    Page 19 5sc 1 - 3 kva us_en english 6. Appendices 6.1 technical specifications 5sc 1000i rack2u 5sc 1500i rack2u 5sc 2200i rt2u 5sc 3000i rt2u output power @ 230 v 1000 va 700 w 1500 va 1050 w 2200 va 1980 w 3000 va 2700 w ac input power rated input voltage single phase 220-240 v input voltage range...

  • Page 20: 6. Appendices

    Page 20 5sc 1 - 3 kva us_en 6. Appendices backup time time during which the load can be supplied by the ups operating on battery power. Battery test internal ups test to check battery status. Cold start the devices connected to the ups can be started even if ac input power is not available. The ups ...