UPS OPERATING INSTRUCTIONS
EATON Eaton 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual
S 164201716 Rev 2 www.eaton.com/powerquality
7-48
4.
On the Charger Control Command screen, select
CHARGER ON
.
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
To turn the battery charger off:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
2.
On the System Status screen, select the
CHARGER
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Charger
Control Command screen is displayed.
4.
On the Charger Control Command screen, select
CHARGER OFF
.
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
7.4.27
Using the UPS LOAD OFF Pushbutton or Command
A UPS Load Off is initiated by the
LOAD OFF
pushbutton from the main menu bar, the
Load Off command on the UPS Control Command screen, or the Load Off command
on the Bypass Control Command screen. The UPS
LOAD OFF
controls the UPSs'
outputs by powering down the UPS and de‐energizing the critical load.
The UPSs (including Bypass) remain off until restarted.
NOTE The UPS Load Off controls each UPS independently and does not shut down the whole distributed
bypass system unless all UPSs have been transferred to bypass. To immediately shut down the whole
system, use the REPO switch (see paragraph 7.4.28).
To use the
LOAD OFF
pushbutton:
1.
Press the
LOAD OFF
pushbutton on the UPS to shut down.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
C
A
U
T
I
O
N
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use
this feature only when you want to de‐energize the critical load.
2.
To shut down the UPS, press
LOAD OFF
from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press
CANCEL
.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off on the UPS.
3.
If another UPS is to be shut down, proceed to that UPS and repeat
Steps 1 and 2.
C
A
U
T
I
O
N
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
4.
Restart the UPS after pressing the
LOAD OFF
pushbutton by following the
procedure in paragraph 7.4.1 on page 7-30 or 7.4.8 on page 7-34.
Summary of 9395 275
Page 1
Powerware series eaton 9395 550/275 ups 225–550 kva installation and operation manual ®.
Page 3
Powerware series eaton 9395 550/275 ups 225–550 kva installation and operation manual ®.
Page 4
Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...
Page 5
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality i table of contents 1 introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 6
Table of contents eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality ii 4.6 installing ups external and battery power wiring 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 7
Table of contents eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality iii 7.2.6 display menu operation 7-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 8
Table of contents eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality iv 7.4.22 single ups shutdown using load off 7-44 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 9
Table of contents eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality v list of figures figure 1‐1. Eaton9395 550/275 ups cabinet 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 10
Table of contents eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality vi figure 6‐1. Main elements of the ups system 6-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 11
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-1 chapter 1 introduction the eaton ® 9395 uninterruptible power supply (ups) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase system, p...
Page 12
Introduction eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-2 figure 1‐1. Eaton9395 550/275 ups cabinet.
Page 13
Introduction eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-3 figure 1‐2. Eaton9395 550/275 ups cabinet with the field installed upm.
Page 14
Introduction eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-4 1.1.2 control panel the control panel, located on the front of the ups, contains a liquid crystal display (lcd) and pushbutton switches to control the operation ...
Page 15
Introduction eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-5 1.2.3 maintenance bypass module the maintenance bypass module (mbm) enables power to completely bypass and isolate the ups so that the ups can be safely serviced or re...
Page 16
Introduction eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-6 1.2.8 inherent redundancy to deliver greater reliability, the eaton9395 ups can be configured by an authorized eaton customer service engineer for inherent redun...
Page 17
Introduction eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-7 1.2.11 monitoring and communication s remote monitor panel ii (rmp ii) – an optional rmp ii contains backlit status indicators and a local horn, allowing monitoring of...
Page 18
Introduction eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-8 1.4 basic system configurations the following basic ups system configurations are possible: s single ups with one upm and two to four battery cabinets for the up...
Page 19
Introduction eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-9 1.6 conventions used in this manual this manual uses these type conventions: s bold type highlights important concepts in discussions, key terms in procedures, and men...
Page 20
Introduction eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 1-10 1.8 for more information refer to the eaton 9395 integrated battery cabinet (model ibc-l) installation manual for the following additional information: s integr...
Page 21
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 2-1 chapter 2 safety warnings important safety instructions save these instructions this manual contains important instructions that should be followed during installation and maintena...
Page 22
Safety warnings eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 2-2 s the operating environment should be maintained within the parameters stated in this manual. S keep surroundings uncluttered, clean, and free from excess moi...
Page 23
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 2-1 section i installation.
Page 24
Eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 2-2.
Page 25
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-1 chapter 3 ups installation plan and unpacking use the following basic sequence of steps to install the ups: 1. Create an installation plan for the ups system (chapter 3). 2. Prepar...
Page 26
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-2 for field installed upm (fi-upm) weights and dimensions, refer to the eaton 9395 field installed upm mechanical installation manual, liste...
Page 27
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-3 the ups ventilation requirements are shown in table 3‐3. Table 3‐3. Air conditioning or ventilation requirements during full load operation mode...
Page 28
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-4 871.7 [34.3] 830 [32.7] 40 [1.6] dimensions are in millimeters [inches]. Figure 3‐2. Ups cabinet dimensions (right side view) front 633 [2...
Page 29
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-5 front 613 [24.1] 40 [1.6] 36 [1.4] 356 [14] dimensions are in millimeters [inches]. Figure 3‐4. Ups cabinet dimensions (bottom view) front 38 [1...
Page 30
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-6 1873.9 [73.8] 1333.8 [52.5] 830 [32.7] cg 412 [16] 856 [33.7] 956 37.6 cg dimensions are in millimeters [inches]. Figure 3‐6. Ups cabinet ...
Page 31
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-7 3.2.2 ups system power wiring preparation read and understand the following notes while planning and performing the installation: s refer to nat...
Page 32
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-8 s in a common battery system, single and multiple upms are powered from one common battery source. In a separate battery system, multiple ...
Page 33
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-9 table 3‐4. Input/output ratings and external wiring requirements for the eaton 9395-550/275 – 480v, common battery basic unit rating units ratin...
Page 34
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-10 table 3‐5. Input/output ratings and external wiring requirements for the eaton 9395-550/275 – 400v, common battery basic unit rating unit...
Page 35
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-11 table 3‐6. Input/output ratings and external wiring requirements for the eaton 9395-550/275 – 480v, separate battery basic unit rating units ra...
Page 36
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-12 table 3‐7. Input/output ratings and external wiring requirements for the eaton 9395-550/275 – 400v, separate battery basic unit rating un...
Page 37
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-13 ac input to the ups with separate rectifier inputs is wired as if each upm is rated for 275 kva (see table 3‐8). The bypass input, battery inpu...
Page 38
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-14 for a ups with common rectifier input terminals, e1 through e12 are 2‐hole bus bar mountings for standard nema 2‐hole barrel lugs. The po...
Page 39
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-15 table 3‐10. Supplied terminal hardware kit part size quantity terminals used on eaton part number bolt, grade 5 m10 x 30 mm 23 ground and neutr...
Page 40
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-16 conduit sizes were chosen from nec table 4, electrical metallic tubing (emt). See table 3‐13 for conduit requirements. Per nec article 30...
Page 41
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-17 external overcurrent protection and disconnect are not provided by this product, but are required by codes. Refer to table 3‐4 through table 3‐...
Page 42
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-18 there is no manual dc disconnect device within the ups. A battery disconnect switch is recommended, and may be required by nec or local c...
Page 43
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-19 3.2.3 ups system interface wiring preparation control wiring for features and options should be connected at the customer interface terminal bl...
Page 44
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-20 3.2.4 distributed bypass power wiring preparation read and understand the following notes while planning and performing the installation:...
Page 45
Ups installation plan and unpacking eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-21 3.3 inspecting and unpacking the ups cabinet the ups cabinet is palleted separately for shipping. The cabinet is shipped bolted to a wooden pal...
Page 46
Ups installation plan and unpacking eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 3-22 4. Remove the protective covering from the cabinet. 5. Remove the packing material, and discard or recycle in a responsible manner. 6. In...
Page 47
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-1 chapter 4 ups system installation 4.1 preliminary installation information w a r n i n g installation should be performed only by qualified personnel. Refer to the following while ...
Page 48
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-2 note for the following steps, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see table 3‐1 on page 3-2 for cabi...
Page 49
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-3 shipping bracket bolts shipping bracket bolts pallet left side shipping bracket upm removable front panel figure 4‐1. Removing the left side shipping bracke...
Page 50
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-4 shipping bracket bolts shipping bracket bolts pallet right side shipping bracket removable left front panel front door figure 4‐2. Removing the right ...
Page 51
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-5 4.3 field installed upm installation if installing a fi-upm, install the fi-upm using the instructions in the eaton 9395 field installed upm mechanical inst...
Page 52
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-6 c a u t i o n delta sources (tn‐s) - the 9390 ups system can be operated only from a delta supply source that is fully floating and if the neutral‐for...
Page 53
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-7 4.6.2 external power wiring installation to install wiring to connections: 1. Remove one top screw and two bottom screws securing the ups left front panel (...
Page 54
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-8 top entry conduit landing for ac input and output, and dc input (remove panel to drill or punch conduit holes.) top view interface entry conduit landi...
Page 55
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-9 10. If wiring a distributed bypass system, proceed to step 11; otherwise, proceed to step 13. C a u t i o n distributed bypass system wiring length should b...
Page 56
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-10 note required parallel system wiring length must be equal to ensure approximately equal current sharing when in bypass mode. For proper operation the...
Page 57
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-11 (see figure 4‐7 for detail aa.) dc input from battery + (e4) – (e5) dc input from battery (e12) neutral ac input to ups rectifier (a, b, c) ac output to cr...
Page 58
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-12 ground terminals ac output to critical load phase c (e8) phase a (e6) phase b (e7) (e12) neutral ac input to ups rectifier phase a (e1) phase c (e3) ...
Page 59
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-13 (see figure 4‐9 for detail aa.) dc input from battery + (e4) – (e5) dc input from battery (e12) neutral ac input to upm rectifiers (a, b, c) ac output to c...
Page 60
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-14 ground terminals ac output to critical load phase c (e8) phase a (e6) phase b (e7) (e12) neutral upm rectifier input terminal block phase c (e11) pha...
Page 61
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-15 4.6.3 battery power wiring c a u t i o n when sizing the battery system, do not exceed the internal battery charger capabilities. See chapter 10, “product ...
Page 62
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-16 dc input from battery + (e4) – (e5) dc input from battery figure 4‐11. Ups power terminal detail bb – common battery.
Page 63
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-17 (upm 4 – fi-upm) dc input from battery + (e4) – (e5) dc input from battery dc input from battery + (e4) (upm 4 – fi-upm) (upm 1) – (e5) dc input from batte...
Page 64
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-18 3. Remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door off. Retain the hardware f...
Page 65
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-19 x-slot communication bays tb3 tb1 and tb2 (see figure 4‐14 for detail.) (see figure 4‐16 on page 4-22 for terminal assignments.) (see figure 4‐19 on page 4...
Page 66
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-20 table 4‐1. Tb1, tb2, and tb3 interface connections terminal tb1 name description 1 repo nc i nput: normally‐closed dry contact used to activate ups e...
Page 67
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-21 tb1 tb2 x-slot communication bays see figure 4‐16 for terminal assignments. Figure 4‐14. Interface terminal detail tb2 alarm relay 3 4 5 6 alarm relay nc a...
Page 68
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-22 ups building alarm 3 building alarm 3 return building alarm 4 building alarm 5 building alarm 4 return building alarm 5 return note all building alar...
Page 69
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-23 4.7.2 tb1 battery interface connections to install wiring to connections: 1. Verify the ups system is turned off and all power sources are removed. See cha...
Page 70
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-24 18. If wiring x-slot connections, proceed to paragraph 4.7.3; otherwise, proceed to step 19. 19. Reinstall the front door removed in step 3 and secur...
Page 71
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-25 4.7.3 x-slot connections note lan and telephone drops for use with x-slot cards must be provided by the customer. Note when installing external wiring to x...
Page 72
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-26 4.8 installing a repo switch a latching-type remote emergency power-off (repo) switch can be used in an emergency to shut down the ups and remove pow...
Page 73
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-27 6. If not already accomplished, remove one top screw and two bottom screws securing the ups left front panel (see figure 4‐2 on page 4-4). Lift the panel s...
Page 74
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-28 3 (no) ups tb1 repo switch (no) twisted wires 1 (nc) note repo switch rating is 24 vdc, 1a minimum. Note the repo switch must be a latching-type swit...
Page 75
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-29 3 (no) ups tb1 repo switch (nc) twisted wires 1 (nc) 2 (return) 4 (return) note repo switch rating is 24 vdc, 1a minimum. Note the repo switch must be a la...
Page 76
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-30 4.9 installing options, accessories, and distributed bypass control wiring to install options, accessories, and distributed bypass control wiring, se...
Page 77
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-31 installation checklist - all packing materials and restraints have been removed from each cabinet. - each cabinet in the ups system is placed in its instal...
Page 78
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-32 distributed bypass installation checklist - each cabinet in the distributed bypass system is placed in its installed location. - all conduits and cab...
Page 79
Ups system installation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-33 notes _________________________________________________________________________ _________________________________________________________________________ _...
Page 80
Ups system installation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 4-34 this page intentionally left blank..
Page 81
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-1 chapter 5 installing options and accessories 5.1 installing an optional powerware hot sync can bridge card as an option, a powerware hot sync controller area network (can) bridge c...
Page 82
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-2 7. Read and understand the following notes while planning and performing the wiring installation: s conduit must be installed between the u...
Page 83
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-3 connections for parallel system control connections for rmp ii, rim ii, or scm ii alarm j3 connections for bypass status figure 5‐2. Powerware ho...
Page 84
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-4 5.2 installing distributed bypass control wiring note when installing external wiring to the powerware hot sync can bridge card, conduit mu...
Page 85
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-5 ups 1 ups 2 ups 3 ups 4 can (if installed) (if installed) pull chain note this drawing is for distributed bypass wiring purposes and is not a flo...
Page 86
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-6 1 2 3 4 5 7 8 6 9 10 ups 1 twisted pair twisted pair twisted pair twisted pair twisted pair twisted pair 1 2 3 4 5 7 8 6 9 10 1 2 3 4 5 7 8...
Page 87
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-7 note nc and no designations on mob aux contacts are defined with breaker in off (open) position. Note if mob contacts have pigtail leads, use the...
Page 88
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-8 table 5‐4. Pull-chain wiring terminations with mobs from to function ups 1 can bridge card j3–1 (alarm) mob 1 aux 1 nc mob open alarm ups 1...
Page 89
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-9 5.3 installing an optional remote monitor panel ii to install rmp ii wiring: 1. Verify the ups system is turned off and all power sources are rem...
Page 90
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-10 terminal tb1 signal connections from the ups ground terminal terminal tb3 120 vac power figure 5‐7. Remote monitor panel ii and remote mon...
Page 91
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-11 note setup of the powerware hot sync can bridge card must be performed by an authorized eaton customer service engineer. Contact an eaton servic...
Page 92
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-12 10. If removed, reinstall the safety shield panel removed in paragraph 5.1, step 5. Secure with the retained hardware. 11. If removed, rei...
Page 93
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-13 5.5 installing an optional supervisory contact module ii to install scm ii wiring: 1. Verify the ups system is turned off and all power sources ...
Page 94
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-14 note setup of the powerware hot sync can bridge card must be performed by an authorized eaton customer service engineer. Contact an eaton ...
Page 95
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-15 system normal no redundancy on generator bypass not available on battery ups alarm on bypass shutdown imminent figure 5‐11. Supervisory contact ...
Page 96
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-16 5.6 accessory mounting dimensions figure 5‐12 through figure 5‐14 show the dimensions of the rmp ii, the rim ii, and the scm ii. Flush mou...
Page 97
Installing options and accessories eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-17 knockouts provided on five surfaces surface mount using #10 pan head screws for hanging. (mount with vent holes facing up.) flush mount using #1...
Page 98
Installing options and accessories eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-18 knockouts provided on five surfaces surface mount using #10 pan head screws for hanging. (mount with vent holes facing up.) flush mount us...
Page 99
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-19 section ii operation.
Page 100
Eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 5-20
Page 101
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-1 chapter 6 understanding ups operation 6.1 ups system overview the eaton9395 ups is a continuous-duty, solid‐state, transformerless (at 480 vac), three-phase, true online system tha...
Page 102
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-2 6.2 single ups a single ups operates independently to support an applied load from the inverter, providing conditioned and uninterruptible ac powe...
Page 103
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-3 static switch rectifier inverter k1 k3 battery converter battery battery breaker main power flow trickle current energized de-energized closed open brea...
Page 104
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-4 if commercial power voltage or frequency disturbances are detected, the system forward transfers to battery mode for minor disturbances and then t...
Page 105
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-5 static switch k5 rectifier inverter k1 k3 battery converter battery battery breaker main power flow trickle current energized de-energized closed open b...
Page 106
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-6 6.2.6 battery mode the ups automatically transfers to battery mode if a utility power outage occurs, or if the utility power does not conform to s...
Page 107
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-7 6.3 single ups system oneline configurations the system oneline drawings in this section show the simplified internal structure of the ups, battery supp...
Page 108
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-8 input breaker (cb1) (optional) x-slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to ta...
Page 109
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-9 input breaker (cb1) (optional) x-slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to table 3‐...
Page 110
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-10 input breaker (cb1) (optional) x-slot interface e1, e2, e3 e6, e7, e8, e12 48v battery shunt trip note callout letters a , b , c , and d map to t...
Page 111
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-11 note callout letter a maps to table 3‐8 on page 3-13. Callout letters b , c , and d map to table 3‐6 on page 3-11 or table 3‐7 on page 3-12. Note if th...
Page 112
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-12 maintenance bypass panel output from ups mis to ups rectifier input rib: rectifier input breaker bib: bypass input breaker mis: maintenance isola...
Page 113
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-13 6.4 multiple ups distributed bypass system distributed bypass parallel operation extends the normal operation of eaton9395 upss by offering increased c...
Page 114
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-14 s in bypass mode, the critical load is directly supported by utility power through the bypass circuit in each ups. S in battery mode, the battery...
Page 115
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-15 main power flow ups 1 ups 2 ups 3 ups 4 output to critical load battery ups input tie cabinet ups 1 output bypass input ups 2 output ups 3 output ups 4...
Page 116
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-16 main power flow ups 1 ups 2 ups 3 ups 4 output to critical load battery ups input tie cabinet ups 1 output bypass input ups 2 output ups 3 output...
Page 117
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-17 6.4.4 battery mode – distributed bypass the upss transfer to battery mode automatically if a utility power outage occurs, or if the utility power does ...
Page 118
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-18 if at any time during the battery discharge the input power becomes available again, the rectifier begins to supply dc current to the inverter. A...
Page 119
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-19 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b ...
Page 120
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-20 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups ...
Page 121
Understanding ups operation eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-21 battery breaker battery converter inverter k3 fuse rectifier k1 k2 fuse fuse fuse e6 e7 e8 e12 k5 static switch fuse e1 e2 e3 cb1 (optional) ups 1 a b ...
Page 122
Understanding ups operation eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 6-22 this page intentionally left blank..
Page 123
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-1 chapter 7 ups operating instructions this section describes how to operate the ups. Note before starting the ups, ensure all installation tasks are complete and a preliminary start...
Page 124
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-2 7.1.1 control panel the control panel is used to set up and control the ups, and to monitor ups operation. For a description of the ups control pan...
Page 125
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-3 7.2.1 status indicators the four symbols on the right side of the control panel are status indicators. These colored light emitting diode (led) lamps wor...
Page 126
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-4 7.2.3 using the lcd and pushbuttons the lcd on the control panel provides an operator interface with the ups system. Figure 7‐3 identifies the disp...
Page 127
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-5 7.2.4 using the menu the ups menu bar allows you to display data in the information area to help you monitor and control ups operation. Table 7‐2 shows t...
Page 128
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-6 7.2.6 display menu operation table 7‐3 describes the menu functions and and how to use them. Table 7‐3. Display menu operation function subfunction...
Page 129
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-7 table 7‐3. Display menu operation (continued) operation subfunction function contrast adjust select contrast from the system setup level 0 menu to displa...
Page 130
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-8 table 7‐3. Display menu operation (continued) operation subfunction function high alert timer the high alert timer screen sets the length of time t...
Page 131
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-9 table 7‐3. Display menu operation (continued) operation subfunction function com port setup the com setup screen is used to change and save the settings ...
Page 132
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-10 7.2.8 system status screen and controls press the controls pushbutton on the main menu bar to display the system status screen. Online operation, ...
Page 133
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-11 table 7‐5. Command menu operation function subfunction operation ups control commands use the up or down arrow pushbutton to highlight the command funct...
Page 134
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-12 7.3 single ups operation the paragraphs in this section provide operating instructions for a ups system containing only one ups. Note a field inst...
Page 135
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-13 16. Verify the following messages display sequentially on the upm status line: dc starting, charger off inverter starting inverter syncing online, charg...
Page 136
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-14 7.3.3 disable energy saver system mode from the ups command menu to disable energy saver system mode: note the energy saver system mode commands a...
Page 137
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-15 7.3.5 enable variable module management system mode from the ups command menu to enable variable module management system mode: note the variable module...
Page 138
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-16 7.3.7 start variable module management system high alert mode from the ups command menu to start high alert mode: note the high alert mode command...
Page 139
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-17 10. On the system status screen, select the bypass command. 11. Press the controls pushbutton on the system status menu bar. The bypass control command ...
Page 140
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-18 7.3.10 disable energy saver system mode from the bypass command menu to disable energy saver system mode: note the energy saver system mode comman...
Page 141
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-19 7.3.12 enable variable module management system mode from the bypass command menu to enable variable module management system mode: note the variable mo...
Page 142
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-20 5. Press the select pushbutton on the bypass command menu bar. If the ups is online, the ups transfers to battery mode and then to online mode in ...
Page 143
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-21 9. On the system status screen, the ups status should indicate shutdown and the upm status should indicate offline. 10. Verify no alarms are active. 11....
Page 144
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-22 7.3.16 starting a single upm to start a single upm: 1. Unfasten the front door latch and swing the door open (see figure 4‐2 on page 4-4). 2. If t...
Page 145
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-23 23. Press the select pushbutton on the upm command menu bar. The upm transfers to online mode. The upm status indicates online. 7.3.17 transfer from onl...
Page 146
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-24 7.3.19 transfer from online to bypass mode and shut down upms to transfer the critical load to bypass mode and shut down the upms: 1. Transfer the...
Page 147
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-25 3. On the system status screen, select the upm command. The ups control command screen is displayed. 4. On the ups control command screen, select the up...
Page 148
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-26 11. Verify the following messages display sequentially on the upm status line: dc starting, charger off inverter starting inverter syncing ready t...
Page 149
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-27 3. Press the controls pushbutton on the system status menu bar. The charger control command screen is displayed. 4. On the charger control command scree...
Page 150
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-28 the load off screen is displayed, providing a choice to proceed or abort the shutdown. C a u t i o n all power to the critical load is lost when t...
Page 151
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-29 7.3.25 using the remote emergency power-off switch a ups emergency power-off is initiated by the repo pushbutton switch. In an emergency, you can use th...
Page 152
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-30 7.4 multiple ups distributed bypass operation the paragraphs in this section provide operating instructions for a ups system containing multiple u...
Page 153
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-31 17. Verify the following messages display sequentially on the ups status line: dc starting, charger off inverter starting inverter syncing online, charg...
Page 154
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-32 7.4.3 disable energy saver system mode from the ups command menu to disable energy saver system mode: note the energy saver system mode commands a...
Page 155
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-33 7.4.5 enable variable module management system mode from the ups command menu to enable variable module management system mode: note the variable module...
Page 156
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-34 7.4.7 start variable module management system high alert mode from the ups command menu to start high alert mode: note the high alert mode command...
Page 157
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-35 10. On the system status screen, verify the ups status is shutdown and the upm status is shutdown. 11. On the system status screen, select the bypass co...
Page 158
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-36 7.4.10 disable energy saver system mode from the bypass command menu to disable energy saver system mode: note the energy saver system mode comman...
Page 159
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-37 7.4.12 enable variable module management system mode from the bypass command menu to enable variable module management system mode: note the variable mo...
Page 160
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-38 5. Press the select pushbutton on the bypass command menu bar. If the ups is online, the ups transfers to battery mode and then to online mode in ...
Page 161
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-39 9. On the system status screen, verify the ups status is shutdown and the upm status is offline. 10. Verify no alarms are active. 11. If upm 4 (fi-upm) ...
Page 162
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-40 7.4.16 starting a single upm to start a single upm: 1. Unfasten the front door latch and swing the door open (see figure 4‐2 on page 4-4). 2. If t...
Page 163
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-41 22. On the upm control command screen, select upm go to online . 23. Press the select pushbutton on the upm command menu bar. The upm transfers to onlin...
Page 164
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-42 7.4.19 transfer from online to bypass mode and shut down upms to transfer the critical load to bypass mode and shut down all upms: 1. Transfer the...
Page 165
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-43 3. On the system status screen, select the upm command. The ups control command screen is displayed. 4. On the ups control command screen, select the up...
Page 166
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-44 11. Verify the following messages display sequentially on the upm status line: dc starting, charger off inverter starting inverter syncing ready t...
Page 167
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-45 w a r n i n g power is present inside the ups cabinet until the upstream input feeder circuit breaker is opened. Note if the ups contains an input break...
Page 168
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-46 15. Press the select pushbutton on the upm 1 command menu bar. The upm status indicates shutdown . The input, output, and battery contactors open,...
Page 169
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-47 13. Press the controls pushbutton on the system status menu bar. The ups control command screen is displayed. 14. On the ups control command screen, sel...
Page 170
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-48 4. On the charger control command screen, select charger on . 5. Press the select pushbutton on the charger command menu bar. To turn the battery ...
Page 171
Ups operating instructions eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-49 w a r n i n g power is present inside the ups cabinet until the upstream input feeder circuit breaker is opened. To use the load off command: 1. Press t...
Page 172
Ups operating instructions eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 7-50 7.4.28 using the remote emergency power-off switch a ups emergency power-off is initiated by the repo pushbutton switch. In an emergency, you can ...
Page 173
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-1 chapter 8 communication this chapter describes the communication features of the eaton9395 ups and provides information about connecting hardware and using terminal mode. For termi...
Page 174
Communication eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-2 lan and telephone drops for use with x-slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an x-slot ca...
Page 175
Communication eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-3 the enotify service relies on a connectups-x web/snmp card (or power xpert card) installed with the ups sending one-way status and event e-mails to eaton remote monit...
Page 176
Communication eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-4 remote notification differs from the basic terminal mode with the addition the following functions: s call answer the call answer function allows the user to ca...
Page 177
Communication eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-5 8.5.2 event history log this key sequence prints the entire event history log of the ups at the time the data is requested. The printout begins with the oldest alarm ...
Page 178
Communication eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-6 model: eaton 9395 cto: tf12710000000 serial: mcu dsp: 70.81.14 mcu bootloader: 80.40 mcu pld: 1.00 pmf 1 dsp: 80.81.14 pmf 1 bootloader: 80.40 pmf 1 pld: 1.00 x...
Page 179
Communication eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-7 8.6 building alarm monitoring this standard feature lets you connect the ups to your building alarms, such as smoke detectors or overtemperature alarms. The customer ...
Page 180
Communication eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-8 the rmp ii contains a local horn and the backlit status indicators listed in table 8‐1. Table 8‐1. Rmp ii status indicators system normal the ups is energized (...
Page 181
Communication eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-9 8.9 relay interface module ii an optional rim ii uses relay contact closures to indicate the operating status and alarm condition of the ups system. The module uses a...
Page 182
Communication eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 8-10 8.10 supervisory contact module ii an optional scm ii establishes an interface between the ups system and the customer's monitor. This interface allows the cus...
Page 183
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 9-1 chapter 9 ups maintenance the components inside the ups cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very lit...
Page 184
Ups maintenance eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 9-2 s proper disposal of batteries is required. Refer to your local codes for disposal requirements. S do not dispose of batteries in a fire. Batteries may explod...
Page 185
Ups maintenance eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 9-3 upm air filter location isbm air filter locations figure 9‐1. Ups filter locations c a u t i o n verify washed filters are thoroughly dry before reinstalling. E. Pu...
Page 186
Ups maintenance eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 9-4 c a u t i o n verify washed filter is thoroughly dry before reinstalling. C. Push the washed or new foam filter over the screw heads on the cabinet mounted st...
Page 187
Ups maintenance eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 9-5 9.2.5 battery maintenance contact an eaton service representative for battery maintenance. Battery replacement and maintenance should be performed only by authorize...
Page 188
Ups maintenance eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 9-6 this page intentionally left blank..
Page 189
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 10-1 chapter 10 product specifications 10.1 model numbers the ups is housed in a free‐standing cabinet with safety shields behind the door and front panels. The ups is available in 50 ...
Page 190
Product specifications eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality 10-2 10.2.2 ups output ups output capacity 100% rated current output voltage regulation "1% (10% to 100% load) output voltage adjustment (nominal +/–3%) 40...
Page 191
Eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality w-1 warranty limited factory warranty for three‐phase eaton ® ups products warrantor: the warrantor for the limited warranties set forth herein is eaton corporation, a delaware corpora...
Page 192
Warranty eaton eaton 9395 550/275 ups (225–550 kva) installation and operation manual s 164201716 rev 2 www.Eaton.Com/powerquality w-2 this page intentionally left blank..
Page 194
*1642017162* 164201716 2.