Eaton 93E User and installation manual - Eaton  93P/e  Small And

Manual is about: 15-80 kVA 380/400/415 V

Summary of 93E

  • Page 1

    Eaton 93p/e small and large external battery cabinet p-164000427 user's and installation guide.

  • Page 3: Eaton  93P/e  Small And

    Eaton 93p/e small and large external battery cabinet user's and installation guide.

  • Page 4

    Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the battery cabinet. Please read all instructions before operating the equipment and save this manual for future reference. This is a produc...

  • Page 5: Contents

    Contents 1 safety instructions ........................................................................................................................ 1 1.1 symbols on the ups and accessories ................................................................................................... 1 1.2 c...

  • Page 6: 1 Safety Instructions

    P-164000427 small and large battery cabinet 1 revision 2 user's and installation guide 1 safety instructions 1.1 symbols on the ups and accessories the following are examples of symbols used on the ups or accessories to alert you to important information: danger risk of electric shock - indicates th...

  • Page 7: 1.3 General

    P-164000427 small and large battery cabinet 2 revision 2 user's and installation guide 1.2 conventions used in this manual this manual uses these type conventions: • bold type highlights important concepts in discussions, key terms in procedures, and menu options, or represents a command or option t...

  • Page 8

    P-164000427 small and large battery cabinet 3 revision 2 user's and installation guide warning • to reduce the risk of fire or electric shock, install this battery cabinet in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exce...

  • Page 9: 1.4  Audience

    P-164000427 small and large battery cabinet 4 revision 2 user's and installation guide • the operating environment should be maintained within the parameters stated in this manual. • keep surroundings uncluttered, clean, and free from excess moisture. • observe all danger, caution, and warning notic...

  • Page 10: 1.7  Environment

    P-164000427 small and large battery cabinet 5 revision 2 user's and installation guide 1.7 environment the battery cabinet must be installed and operated according to the recommendations in this manual. Environmental specifications are in chapter 4.3. Ensure proper ventilation. Ensure there are no f...

  • Page 11: 2  Installation

    P-164000427 small and large battery cabinet 6 revision 2 user's and installation guide 2 installation the battery system provides emergency short-term backup power to safeguard operation during brownouts, blackouts, and other power interruptions. By default, 93pm and 93e upss are configured to use v...

  • Page 12

    P-164000427 small and large battery cabinet 7 revision 2 user's and installation guide cable entry to the 93pm ups is always on the rear or the bottom of the cabinet. In 30-150 kw ups models the entry is also located on the bottom of the right side panel. Cable entry to the 93e ups is on the rear or...

  • Page 13

    P-164000427 small and large battery cabinet 8 revision 2 user's and installation guide figure 2 -2: 93p/e battery cabinet (large battery cabinet) a dc-rated circuit breaker within each cabinet provides protection and service isolation. The battery cabinets use convection cooling to regulate internal...

  • Page 14

    P-164000427 small and large battery cabinet 9 revision 2 user's and installation guide 3. Carefully slide the battery cabinet off the pallet. Now the battery cabinet is ready to be placed aside the ups. Notes of installation location with 93pm ups: both sides can be used for battery cabinet placemen...

  • Page 15

    P-164000427 small and large battery cabinet 10 revision 2 user's and installation guide 2.2 preparing the large battery cabinet installation note the battery cabinet is heavy. If unpacking instructions are not closely followed, the cabinet may tip and cause serious injury. 1. If not already accompli...

  • Page 16

    P-164000427 small and large battery cabinet 11 revision 2 user's and installation guide 5. Select the cable routing out of different options and route the cables to the dedicated connectors inside ups cabinet. Terminals are located under the circuit breaker and are marked with +, - and a protecting ...

  • Page 17

    P-164000427 small and large battery cabinet 12 revision 2 user's and installation guide cable connection to battery poles is to be done as follows: figure 2 -5: cable connection on b attery poles 9. If multiple cabinets are to be used, repeat the steps for the rest of the cabinets and in 93pm system...

  • Page 18

    P-164000427 small and large battery cabinet 13 revision 2 user's and installation guide 2.3 installation with other than 93pm or 93e ups other upss may not be fully compatible with 93p/e external battery cabinet. Check ups manual for the requirements for the external battery supply..

  • Page 19: 3 Maintenance

    P-164000427 small and large battery cabinet 14 revision 2 user's and installation guide 3 maintenance the components inside the cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. This design allows authorized s...

  • Page 20

    P-164000427 small and large battery cabinet 15 revision 2 user's and installation guide when replacing batteries, use the same number of sealed, lead -acid batteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. 3.2 performing preventive maintenance ...

  • Page 21

    P-164000427 small and large battery cabinet 16 revision 2 user's and installation guide these symbols indicate on a product figure 3 -1: weee symbol use proper local collecting centers meeting local legislation when handling waste of electrical and electronic equipment. Danger hazardous materials. B...

  • Page 22: 4 Technical Data

    P-164000427 small and large battery cabinet 17 revision 2 user's and installation guide 4 technical data for complete technical specification, contact your eaton representative. Due to continuous product improvement programs, specifications are subject to change without notice. 4.1 standards and reg...

  • Page 23

    P-164000427 small and large battery cabinet 18 revision 2 user's and installation guide 4.2 battery specification battery type vrla, 12 vdc battery quantity 93pm 30-50 kw units: 1) 36 blocks, 216 cells per battery string, 2v per cell. 93pm 80-200 kw units: 1) 36 blocks, 216 cells per battery string,...

  • Page 24: 5 Warranty

    P-164000427 small and large battery cabinet 19 revision 2 user's and installation guide 5 warranty the product is warranted against defects in materials and workmanship for a period of twelve (12) months from its original date of purchase. The local office or distributor may grant a warranty period ...

  • Page 25: 6  Installation Checklist

    P-164000427 small and large battery cabinet 20 revision 2 user's and installation guide 6 installation checklist all packing materials and restraints have been removed from each cabinet. Each cabinet in the ups system is placed in its installation location. A cabinet grounding/mounting kit is instal...

  • Page 26

    P-164000427 small and large battery cabinet 21 revision 2 user's and installation guide.