  • Page 1

    English 9sx 5000 9sx 6000 9px 5000 9px 6000 9sx ebm 180v 9px ebm 180v installation and user manual copyright © 2012 eaton all rights reserved. Service and support: call your local service representative 5-6kva eu_en.

  • Page 2

    Page 2 5-6kva eu_en.

  • Page 3: Safety Instructions

    Page 3 5-6kva eu_en english save these instructions. This manual contains important instructions that should be followed during installation and maintenance of the ups and batteries. The 9sx and 9px models that are covered in this manual are intended for installation in an environment within 0 to 40...

  • Page 4: Safety Instructions

    Page 4 5-6kva eu_en safety of persons the system has its own power source (the battery). Consequently, the power outlets may be energized p even if the systems is disconnected from the ac power source. Dangerous voltage levels are present within the system. It should be opened exclusively by qualifi...

  • Page 5: Contents

    Page 5 5-6kva eu_en english contents 1. Introduction ....................................................................................... 6 1.1 environmental protection ...............................................................................................6 2. Presentation ..................

  • Page 6: 1. Introduction

    Page 6 5-6kva eu_en 1. Introduction thank you for selecting an eaton product to protect your electrical equipment. The 9sx and 9px range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your ups (uninterrup...

  • Page 7: 1. Introduction

    Page 7 5-6kva eu_en english 1. Introduction the eaton® 9sx and 9px uninterruptible power system (ups) protects your sensitive electronic equipment from the most common power problems, including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations...

  • Page 8: 2. Presentation

    Page 8 5-6kva eu_en 2. Presentation 2.1 standard installations tower installation d w h rack installation d h w description weights (lb/kg) dimensions (inch/mm) d x w x h 9sx 5000 106 / 48 27.0 x 17.3 x 5.1 / 685 x 440 x 130 9sx 6000 106 / 48 27.0 x 17.3 x 5.1 / 685 x 440 x 130 9px 5000 106 / 48 27....

  • Page 9: 2. Presentation

    Page 9 5-6kva eu_en english 2. Presentation 2.2 rear panels 9sx 5000 / 6000 14 13 3 4 7 8 10 11 12 1 2 5 9 9px 5000 / 6000 3 4 6 7 8 10 11 12 1 2 5 9 14 13 1 rs232 communication port 2 usb communication port 3 dry (relay) contacts communication port 4 connector for roo (remote on/off) control 5 conn...

  • Page 10: 2. Presentation

    Page 10 5-6kva eu_en 2. Presentation 2.3 accessories part number description 9sxebm180rt, 9pxebm180 extended battery module 9rk rack kit 9px/9sx network-ms network card modbus-ms modbus and network card relay-ms relay card mbp6ki hotswap mbp 6000i tfmr11ki transformer 11000i bintsys battery integrat...

  • Page 11: 2. Presentation

    Page 11 5-6kva eu_en english 2. Presentation 2.4 control panel the ups has a five-button graphical lcd. It provides useful information about the ups itself, load status, events, measurements and settings. Online mode indicator (green) fault indicator (red) online mode 100% 30min 1ebm 50% 2.7kw 3.0kv...

  • Page 12: 2. Presentation

    Page 12 5-6kva eu_en 2. Presentation 2.5 lcd description after 5 minutes of inactivity, the lcd displays the screen saver. The lcd backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen. Operation status load/equipment status online mode 100% 30min 1ebm 5...

  • Page 13: 2. Presentation

    Page 13 5-6kva eu_en english 2.6 display functions press the enter ( ) button to activate the menu options. Use the two middle buttons ( and ) to scroll through the menu structure. Press the enter ( ) button to select an option. Press the button to cancel or return to the previous menu. Main menu su...

  • Page 14: 2. Presentation

    Page 14 5-6kva eu_en 2. Presentation submenu available settings default settings in/out settings interrupt time if bypass transfer is enabled, interrupt time: [10ms] [20ms] define break duration when transfer on bypass [10ms] overload prealarm [10%] … [102%] load % when overload alarm occurs [102%] ...

  • Page 15: 3. Installation

    Page 15 5-6kva eu_en english 3.1 inspecting the equipment if any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed ...

  • Page 16: 3. Installation

    Page 16 5-6kva eu_en 3. Installation 3.3 checking the accessory kit verify that the following additional items are included with the ups: z 1 6 2 11 10 9 7 4 5 3 8 1 (2) tower stands 2 rack kit for 19-inch enclosures (optional) 3 (2) cable glands for input/output connection 4 (2) cable lockers for 1...

  • Page 17: 3. Installation

    Page 17 5-6kva eu_en english 3. Installation 3.4 connecting the ebm(s) a small amount of arcing may occur when connecting an ebm to the ups. This is normal and will not harm personnel. Insert the ebm cable into the ups battery connector quickly and firmly. 1. Plug the ebm power cable(s) into the bat...

  • Page 18: 3. Installation

    Page 18 5-6kva eu_en 3. Installation 3.6 tower installation adjustment of the orientation of the lcd panel and of the logo. P adjustment of the angle of vision of the lcd panel. P if you ordered other ups accessories, refer to specific user manuals to check the tower installation with the ups. To in...

  • Page 19: 3. Installation

    Page 19 5-6kva eu_en english 3.7 rack installation if you ordered other ups accessories, refer to specific user manuals to check the rack installation with the ups. Prepare ups for rack mounting. P this step requires two people. The ups is heavy. To ease its rack mounting, you can remove the battery...

  • Page 20: 3. Installation

    Page 20 5-6kva eu_en rack mounting of ups, ebm, and accessory modules. P follow steps 1 to 4 for module mounting on the rails. 1 1 3 4 4 3 2 the rails and necessary hardware are supplied by eaton. 3. Installation.

  • Page 21: 3. Installation

    Page 21 5-6kva eu_en english 3.8 installation requirements recommended protective devices and cable cross-sections 1. Recommended upstream protection ups power rating upstream circuit breaker 5000va d curve – 32a 6000va d curve – 32a 2 poles circuit breaker g n(l2) l1 n(l2) l1 to ups normal ac sourc...

  • Page 22: 3. Installation

    Page 22 5-6kva eu_en 3.9 installation depending on the system earthing arrangement (sea) change in sea between upstream and downstream or galvanic isolation required 8 10 8 10 or normal ac load main low voltage switchboard (mlvs) isolation transformer normal ac load main low voltage switchboard (mlv...

  • Page 23: 4. Power Cables Connection

    Page 23 5-6kva eu_en english 4. Power cables connection 4.1 access to terminal blocks 1. Remove the terminal blocks cover (one screw) 2. Punch the knockouts and insert the cables/conduits inside high leakage current: z earth connection essential before connecting supply. 4.2 input/output connection ...

  • Page 24: 5. Operation

    Page 24 5-6kva eu_en 5. Operation 5.1 ups startup and shutdown if you ordered a hotswap mbp, refer to the specific user manual to check the startup sequence of the ups with the mbp. Starting the ups verify that the total equipment ratings do not exceed the ups capacity to prevent an overload alarm. ...

  • Page 25: 5. Operation

    Page 25 5-6kva eu_en english 5. Operation 5.2 operating modes the eaton 9sx and 9px front panel indicates the ups status through the ups indicators, see page 13. Online mode during online mode, the indicator illuminates solid and the ups is powered from the utility. The ups monitors and charges the ...

  • Page 26: 5. Operation

    Page 26 5-6kva eu_en 5. Operation 5.4 setting high efficiency mode on high efficiency mode, the ups operates normally on bypass, transfers to online (or battery) mode in less than 10 ms when utility fails, and transfers back to bypass in 5 minutes after utility returns. Eaton recommends to use the h...

  • Page 27: 5. Operation

    Page 27 5-6kva eu_en english 5. Operation 5.7 retrieving the event log to retrieve the event log through the display: 1. Press any button to activate the menu options, then select event log. 2. Scroll through the listed events. 5.8 retrieving the fault log to retrieve the fault log through the displ...

  • Page 28: 6. Communication

    Page 28 5-6kva eu_en 6. Communication 6.1 communication ports z rs232 or usb communication ports the rs232 and usb communication ports cannot operate simultaneously. Z relay output contacts the ups incorporates four programmable relay outputs; each information is available with a close or open conta...

  • Page 29: 6. Communication

    Page 29 5-6kva eu_en english 6. Communication z remote on/off remote on/off allows remote action of button to switch on/off the ups. Normally open when contact changes from open to closed, the ups is switched-on (or stays on). When contact changes from closed to open, the ups is switched-off (or sta...

  • Page 30: 6. Communication

    Page 30 5-6kva eu_en 6. Communication remote control connection and test 1 - check the ups is shut down and the electrical supply network disconnected. 2 - remove rpo connector from the ups by unfitting the screws. 3 - connect a normally closed volt-free contact between the two pins of connector. 1 ...

  • Page 31: 6. Communication

    Page 31 5-6kva eu_en english installation of the communication cards z parallel communication port. This slot is used for parallel operation (only on 9px models). It is not necessary to shutdown the ups before installing a communication card. 1. Remove the slot cover 4 secured by screws. 2. Insert t...

  • Page 32: 7. Ups Maintenance

    Page 32 5-6kva eu_en 7. Ups maintenance 7.1 equipment care for the best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the equipment at an ambient temp...

  • Page 33: 7. Ups Maintenance

    Page 33 5-6kva eu_en english 7. Ups maintenance 7.4 replacing batteries do not disconnect the batteries while the ups is in battery mode. Batteries can be replaced easily without turning off the ups or disconnecting the load. If you prefer to remove input power to change the batteries, see "ups shut...

  • Page 34: 7. Ups Maintenance

    Page 34 5-6kva eu_en 7. Ups maintenance replacing the internal battery z the internal battery is heavy. Use caution when handling the heavy batteries. To replace the battery pack: 1. Remove the center cover of the front panel 2. Remove the two screws to open the left side of the front panel 3. Remov...

  • Page 35: 7. Ups Maintenance

    Page 35 5-6kva eu_en english 7. Ups maintenance replacing the ebm(s) z the ebm is heavy. Lifting the cabinet into a rack requires a minimum of two people. To replace the ebm(s): 1. Unplug the ebm power cable and battery detection cable from the ups. If additional ebm(s) are installed, unplug the ebm...

  • Page 36: 7. Ups Maintenance

    Page 36 5-6kva eu_en 7. Ups maintenance 7.5 replacing the ups equipped with a hotswap mbp the hotswap mbp allows to service or replace the ups without interrupting the connected loads. Refer to the specific user manual for more information about hotswap mbp. To remove the ups: 1. Press any button to...

  • Page 37: 8. Troubleshooting

    Page 37 5-6kva eu_en english 8. Troubleshooting the eaton 9px and 9sx are designed for durable, automatic operation and also alert you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preve...

  • Page 38: 8. Troubleshooting

    Page 38 5-6kva eu_en 8. Troubleshooting power overload power requirements exceed the ups capacity (greater than 100% of nominal; see in table 6 on page 41 for specific output overload ranges). Remove some of the equipment from the ups. The ups continues to operate, but may switch to bypass mode or s...

  • Page 39: 8. Troubleshooting

    Page 39 5-6kva eu_en english 8.2 silencing the alarm press the esc (escape) button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again, overriding the previous alarm ...

  • Page 40: 9. Specifications

    Page 40 5-6kva eu_en 9. Specifications 9.1 model specifications table 1. Power module model list model power ratings 9sx5kirt 5000va / 4500w 9px5ki 5000va / 4500w 9sx6kirt 6000va / 5400w 9px6ki 6000va / 5400w table 2. Extended battery module model list model configuration battery voltage for power r...

  • Page 41: 9. Specifications

    Page 41 5-6kva eu_en english 9. Specifications table 6. Electrical output all models normal mode battery mode voltage regulation ±1% ±1% efficiency > 98% (high efficiency mode) > 93% > 91% frequency regulation sync with line ±5% of nominal line frequency (outside this range: ±0.5% of auto-selected n...

  • Page 42: 9. Specifications

    Page 42 5-6kva eu_en 9. Specifications agency markings ce / c-tick / culus operating temperature 0 to 40°c (32 to 104°f) in online mode, with linear derating for altitude note: thermal protection switches load to bypass in case of overheating. Storage temperature 0 to 40°c (32 to 104°f) with batteri...

  • Page 43: 10. Glossary

    Page 43 5-6kva eu_en english 10. Glossary bypass ac source source supplying the bypass line. The equipment can be transferred to the by- pass line if an overload occurs on the ups output, for maintenance or in the event of a malfunction. Frequency converter operating mode used to convert the ac-powe...