Eaton 9PX 6K SP Installation And User Manual

Summary of 9PX 6K SP

  • Page 1

    English 9px 6k sp 9px ebm 240v sp installation and user manual copyright © 2013 eaton all rights reserved. Service and support: call your local service representative 9px6k-sp_en.

  • Page 2: Safety Instructions

    Page 2 9px-6k-sp_en save these instructions. This manual contains important instructions that should be followed during installation and maintenance of the ups and batteries. The 9px models that are covered in this manual are intended for installation in an environment within 32 to 104°f / 0 to 40°c...

  • Page 3: Safety Instructions

    Page 3 9px-6k-sp_en english safety instructions safety of persons • risk of voltage backfeed. The system has its own power source (the battery). Isolate the ups and check for hazardous voltage upstream and downstream during lockout-tagout operation. Terminal blocks may be energized even if the syste...

  • Page 4: Safety Instructions

    Page 4 9px-6k-sp_en safety instructions special precautions • the unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations. • all handling operations will require at least two people (unpacking, lifting, installation in rack system). • for ebm, straps are provide...

  • Page 5: Contents

    Page 5 9px-6k-sp_en english contents 1. Introduction ....................................................................................... 6 1.1 environmental protection ...............................................................................................6 2. Presentation ..................

  • Page 6: 1. Introduction

    Page 6 9px-6k-sp_en 1. Introduction thank you for selecting an eaton product to protect your electrical equipment. The 9px range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your ups (uninterruptible po...

  • Page 7: 1. Introduction

    Page 7 9px-6k-sp_en english 1. Introduction the eaton® 9px uninterruptible power system (ups) protects your sensitive electronic equipment from the most common power problems, including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations, switch...

  • Page 8: 2. Presentation

    Page 8 9px-6k-sp_en 2. Presentation 2.1 weights and dimensions 9px 6k sp tower installation rack installation d w h d h w description weights (lb/ kg ) dimensions h x w x d (inch/ mm ) 9px6ksp 119 / 54 6.8 x 17.4 x 25.6 / 173 x 440 x 650 9px ebm 240sp tower installation rack installation d w h d h w...

  • Page 9: 2. Presentation

    Page 9 9px-6k-sp_en english 2. Presentation 2.2 rear panel layout 9px 6k sp 1 3 12 13 14 2 7 9 10 8 6 5 4 11 1 rs232 communication port 2 usb communication port 3 dry (relay) contacts communication port 4 connector for roo (remote on/off) control 5 connectors for automatic recognition of an addition...

  • Page 10

    Page 10 9px-6k-sp_en 3. Installation for 9px 6k sp 3.1 inspecting the equipment if any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file ...

  • Page 11

    Page 11 9px-6k-sp_en english 3.3 checking the accessory kit • verify that the following additional items are included with the ups: 9 10 5 6 7 8 4 2 1 3 11 12 1 user manual 2 safety instructions 3 warranty sheet 4 software cd-rom 5 rs232 communication cable 6 usb communication cable 7 cable gland fo...

  • Page 12

    Page 12 9px-6k-sp_en 3. Installation for 9px 6k sp 3.4 tower installation if you ordered other ups accessories, refer to specific user manuals to check the tower installation with the ups. To install the cabinet: 1. Place the ups on a flat, stable surface in its final location. 2. Always keep 150 mm...

  • Page 13

    Page 13 9px-6k-sp_en english 3. Installation for 9px 6k sp 3.5 rack installation • rack mounting of ups and accessory modules. Follow steps 1 to 4 for module mounting on the rails. 4 3 1 4 3 2 1 2 the rails and necessary hardware are supplied by eaton. If you ordered other ups accessories, refer to ...

  • Page 14

    Page 14 9px-6k-sp_en 3. Installation for 9px 6k sp 3.6 connecting the internal battery do not make unauthorized changes to the ups; otherwise, damage may occur to your equipment and void your warranty. Do not connect the ups to utility until installation is completed. This step requires two people, ...

  • Page 15: 4. Installation For Ebm(S)

    Page 15 9px-6k-sp_en english 4. Installation for ebm(s) 4.1 inspecting the equipment if any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, ...

  • Page 16: 4. Installation For Ebm(S)

    Page 16 9px-6k-sp_en 4. Installation for ebm(s) 4.3 checking the accessory kit • if you ordered an optional extended battery module (ebm), verify that the following additional items are included with the ebm: 3 4 2 1 1 2 x battery power cable, attached with battery detection cable 2 stabilizer brack...

  • Page 17: 4. Installation For Ebm(S)

    Page 17 9px-6k-sp_en english 4. Installation for ebm(s) 4.4 prepare installation if you ordered other ups accessories, refer to specific user manuals to check the rack installation with the ups. • prepare ebm for rack mounting. This step requires two people. The extended battery module is very heavy...

  • Page 18: 4. Installation For Ebm(S)

    Page 18 9px-6k-sp_en 4. Installation for ebm(s) 4.5 tower installation if you ordered other ups accessories, refer to specific user manuals to check the tower installation with the ups. To install the cabinet: 1. Place the ups on a flat, stable surface in its final location. 2. Always keep 150 mm of...

  • Page 19: 4. Installation For Ebm(S)

    Page 19 9px-6k-sp_en english 4. Installation for ebm(s) 4.6 rack installation • rack mounting of ups and accessory modules. Follow steps 1 to 4 for module mounting on the rails. 1 4 3 4 3 1 2 2 the rails and necessary hardware are supplied by eaton. If you ordered other ups accessories, refer to spe...

  • Page 20: 4. Installation For Ebm(S)

    Page 20 9px-6k-sp_en 4. Installation for ebm(s) 4.7 connecting the ebm(s) a small amount of arcing may occur when connecting an ebm to the ups. This is normal and will not harm personnel. Insert the ebm cable into the ups battery connector quickly and firmly. 1. Plug the ebm power cable(s) into the ...

  • Page 21: 5. Power Cable Connection

    Page 21 9px-6k-sp_en english 5. Power cable connection 5.1 installation requirements recommended protective devices and cable cross-sections 1. Recommended upstream protection ups power rating upstream circuit breaker 9px 6k sp 6000va 30a 3 pole circuit breaker utility n l1 g l2 l1 n l2 to ups input...

  • Page 22: 5. Power Cables Connection

    Page 22 9px-6k-sp_en 5. Power cables connection 5.2 access to terminal blocks 1 2 3 4 4 • untightened the cable gland. • remove the terminal blocks cover (two screws). • punch the knockouts and insert the cables/conduits inside. Note: the l14-30p input power cable is attached by eaton. High leakage ...

  • Page 23: 6. Hmi and Settings

    Page 23 9px-6k-sp_en english 6.1 control panel the ups has a five-button graphical lcd. It provides useful information about the ups itself, load status, events, measurements and settings. Online mode indicator (green) fault indicator (red) online mode 100% 40min 1ebm 50% 2.7kw 3.0kva efficiency: 93...

  • Page 24: 6. Hmi and Settings

    Page 24 9px-6k-sp_en 6.2 lcd description after 5 minutes of inactivity, the lcd displays the screen saver. The lcd backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen. Operation status load/equipment status online mode 100% 40min 1ebm 50% 2.7kw 3.0kva ...

  • Page 25: 6. Hmi and Settings

    Page 25 9px-6k-sp_en english 6.3 display functions press the enter ( ) button to activate the menu options. Use the two middle buttons ( and ) to scroll through the menu structure. Press the enter ( ) button to select an option. Press the button to cancel or return to the previous menu. Main menu su...

  • Page 26: 6. Hmi and Settings

    Page 26 9px-6k-sp_en submenu available settings default settings in/out settings overload prealarm [10%] … [102%] load % when overload alarm occurs [102%] on/off settings cold start [enabled] [disabled] authorize the product to start on battery power. [enabled] forced reboot [enabled] [disabled] if ...

  • Page 27: 7. Operation

    Page 27 9px-6k-sp_en english 7. Operation 7.1 ups startup and shutdown starting the ups verify that the total equipment ratings do not exceed the ups capacity to prevent an overload alarm. To start the ups: 1. Verify that the internal batteries are connected. See "connecting the internal battery" on...

  • Page 28: 7. Operation

    Page 28 9px-6k-sp_en 7. Operation 7.2 operating modes the eaton 9px front panel indicates the ups status through the ups indicators, see page 25. Online mode during online mode, the indicator illuminates solid and the ups is powered from the utility. The ups monitors and charges the batteries as nee...

  • Page 29: 7. Operation

    Page 29 9px-6k-sp_en english 7. Operation 7.3 transferring the ups between modes from online (or battery) to bypass mode. Press any button to activate the menu options, then select control and go to bypass. From bypass to online (or battery) mode. Press any button to activate the menu options, then ...

  • Page 30: 7. Operation

    Page 30 9px-6k-sp_en 7. Operation 7.6 retrieving the event log to retrieve the event log through the display: 1. Press any button to activate the menu options, then select event log. 2. Scroll through the listed events. 7.7 retrieving the fault log to retrieve the fault log through the display: 1. P...

  • Page 31: 8. Communication

    Page 31 9px-6k-sp_en english 8. Communication 8.1 communication ports • rs232 or usb communication ports the rs232 and usb communication ports cannot operate simultaneously. 5 6 2 1 • relay output contacts the ups incorporates four relay outputs; each information is available with a close or open co...

  • Page 32: 8. Communication

    Page 32 9px-6k-sp_en 8. Communication • remote on/off remote on/off allows remote action of button to switch on/off the ups. + - normally open when contact changes from open to closed, the ups is switched-on (or stays on). When contact changes from closed to open, the ups is switched-off (or stays o...

  • Page 33: 8. Communication

    Page 33 9px-6k-sp_en english 8. Communication remote control connection and test 1. Check the ups is shut down and the electrical supply network disconnected. 2. Remove rpo connector from the ups by unfitting the screws. 3. Connect a normally closed volt-free contact between the two pins of connecto...

  • Page 34: 8. Communication

    Page 34 9px-6k-sp_en installation of the communication cards 7 it is not necessary to shutdown the ups before installing a communication card. 1. Remove the slot cover 7 secured by screws. 2. Insert the communication card in the slot. 3. Secure the card cover with the 2 screws. 8.2 eaton intelligent...

  • Page 35: 9. Ups Maintenance

    Page 35 9px-6k-sp_en english 9. Ups maintenance 9.1 equipment care for the best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the equipment at an ambi...

  • Page 36: 9. Ups Maintenance

    Page 36 9px-6k-sp_en 9. Ups maintenance 9.4 replacing batteries do not disconnect the batteries while the ups is in battery mode. Batteries can be replaced easily without turning off the ups or disconnecting the load. If you prefer to remove input power to change the batteries, see "ups shutdown" on...

  • Page 37: 9. Ups Maintenance

    Page 37 9px-6k-sp_en english 9. Ups maintenance • replacing the ups internal battery the internal battery is heavy. Use caution when handling the heavy batteries. Description weights (lb/ kg ) 9px 6k sp internal battery 23 / 10.5 1 2 3 5 6 7 8 4 to replace the battery pack: • remove the center cover...

  • Page 38: 9. Ups Maintenance

    Page 38 9px-6k-sp_en • replacing the ebm(s) the ebm is heavy. Lifting the cabinet requires a minimum of two people. Description weights (lb/ kg ) 9px ebm 240sp 93 / 42 9px ebm 240sp without internal battery 47 / 21 9px ebm 240sp internal battery 23 / 10.5 to replace the ebm(s): 1. Unplug the ebm pow...

  • Page 39: 9. Ups Maintenance

    Page 39 9px-6k-sp_en english 9. Ups maintenance 9.5 recycling the used equipment contact your local recycling or hazardous waste center for information on proper disposal of the used equipment. • do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batterie...

  • Page 40: 10. Troubleshooting

    Page 40 9px-6k-sp_en 10. Troubleshooting the eaton 9px is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms in...

  • Page 41: 10. Troubleshooting

    Page 41 9px-6k-sp_en english 10. Troubleshooting ups overtemperature the ups internal temperature is too high or a fan has failed. At the warning level, the ups generates the alarm but remains in the current operating state. If the temperature rises another 10°c, the ups transfers to bypass mode or ...

  • Page 42: 10. Troubleshooting

    Page 42 9px-6k-sp_en 10.2 silencing the alarm press the esc (escape) button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again, overriding the previous alarm silenci...

  • Page 43: 11. Specifications

    Page 43 9px-6k-sp_en english 11. Specifications 11.1 model specifications table 1. Ups model list model power ratings 9px6ksp 4680va / 4212w at 100/200v output 5160va / 4644w at 110/220v output 5340va / 4806w at 115/230v output 5520va / 4968w at 120/208v, 120/240v output 6000va / 5400w at 127/220v o...

  • Page 44: 11. Specifications

    Page 44 9px-6k-sp_en 11. Specifications table 6. Electrical output all models normal mode battery mode voltage regulation ±2% (lx-n); ±5% (l1-l2) ±10% efficiency > 97% (high efficiency mode) > 93% for 9px6ksp frequency regulation sync with line ±5% of nominal line frequency (outside this range: ±0.5...

  • Page 45: 11. Specifications

    Page 45 9px-6k-sp_en english 11. Specifications agency markings ce / culus / nom operating temperature 32 to 104°f (0 to 40°c) in online mode, with linear derating for altitude note: thermal protection switches load to bypass in case of overheating. Storage temperature 32 to 104°f (0 to 40°c) with b...

  • Page 46

    Page 46 9px-6k-sp_en eaton customer care center technical support and product services ? Technical questions? If you encounter a problem while following the instructions in this manual, or have questions about the operation, repair, or servicing of your equipment, please visit our web site powerqual...

  • Page 47: 12. Glossary

    Page 47 9px-6k-sp_en english 12. Glossary bypass ac source source supplying the bypass line. The equipment can be transferred to the bypass line if an overload occurs on the ups output, for maintenance or in the event of a malfunction. Frequency converter operating mode used to convert the ac-power ...

  • Page 48

    Page 48 9px-6k-sp_en.