Eaton Digitrip OPTIM 550 KEP3125T52 Installation Instructions Manual

Manual is about: Digitrip OPTIM 550 series 3-Pole Trip Unit Installation and Operation with K-Frame Series C Circuit Breakers

Summary of Digitrip OPTIM 550 KEP3125T52

  • Page 1

    I.L. 29c507 effective may 2000 cutler-hammer installation instructions for the digitrip optim 550 3-pole trip unit installation and operation with k-frame series c circuit breakers table of contents description page 1.0 general information . . . . . . . . . . . . . . . . . . . . . .1 2.0 ul listed d...

  • Page 2

    Make sure that the trip unit is suitable for the intended installation by comparing nameplate data with any exist- ing equipment and system requirements. Inspect the trip unit for completeness, and check for damage before installing it in the circuit breaker frame. Remove and save the jumper plug as...

  • Page 3

    Ground fault trip units are supplied from the factory with a wire harness with pigtail lead connections for a neutral current sensor (white and gray wires). A neutral current sensor is provided with each trip unit. Install the jumper plug assembly into the trip unit (see figure 3-2) with the keying ...

  • Page 4

    I.L. 29c507 page 4 effective 5/00 figure 3-3 neutral current sensor placement 1.50 table 3.1 digitrip k-frame optim rating plugs make sure interphase barriers are properly seated in the base and sliding handle barrier is properly seated in the cover. .03 .281 diam. 2 holes .36r .12 1.00 ref. 2.75 2....

  • Page 5

    4.0 principle of operation in open air at 40°c, a k-frame circuit breaker with a digitrip optim 550 trip unit installed will carry continu- ously up to 400 amperes without exceeding a 50°c rise at the terminals. The calibration of the trip unit is insen- sitive to ambient temperatures over a range o...

  • Page 6

    I.L. 29c507 page 6 effective 5/00 a "thermal memory" effect prevents the breaker from being re-energized immediately after an overload. A "cooling off" period of up to 5 minutes is required, which allows time for cabling to cool off. For details on the operation and protective functions of the optim...

  • Page 7

    Connections exactly as shown in figure 5-3. The break- er should not trip and the ground fault alarm light should not light. Repeat the test using the other two combina- tions of breaker phases. Field testing should be used for function- al testing and not field calibration of the digitrip optim 550...

  • Page 8

    I.L. 29c507 page 8 effective 5/00 7.0 references 7.1 series c k-frame molded case circuit breakers 29c104 frame instruction leaflet ad 29-167k typical time-current characteristic curves for k-frame breakers 7.2 internal accessories the following types of internal accessories, which mount on the trip...

  • Page 9

    I.L. 29c507 page 9 effective 5/00 ground fault test record form ground fault test record should be retained by those in charge of the building’s electrical installation in order to be available to the authority having jurisdiction test date circuit breaker number results tested by: figure 5-4 typica...

  • Page 10: Cutler-Hammer

    Cutler-hammer pittsburgh, pennsylvania u.S.A. Effective 5/00 (isi) style 6602c55h01 printed in u.S.A. Page 10 i.L. 29c507.