Eaton EDR 3000 Installation, Operation And Maintenance Manual

Summary of EDR 3000

  • Page 1

    Operation & maintenance manual general order mrm0007157 volume 3 of 6 equipment: medium voltage switchgear assembly pentagon - mcm7571 date: 2016-04-08 wesco midlothian va 7582 po# 7582-785492 york river electric ©2015 eaton corporation, all rights reserved.

  • Page 3: Main Table of Contents

    Main table of contents contact page 1.0 medium voltage switchgear assembly vol. 1 1.1 drawings 1.2 instruction data vol. 2 1.3 component data vol. 3-5 2.0 medium voltage switches vol. 6 2.1 drawings 2.2 instruction data 2.3 component data 3.0 panelboards vol. 6 3.1 drawings 3.2 instruction data 3.3 ...

  • Page 4

    Edr-3000 im02602003e device planning parameters of the device parameter description options default menu path hardware variant 1 optional hardware extension »a« 4 digital inputs

  • Page 5: For Warranty Support

    Visit our web site http://www.Eatonelectrical.Com to view the on-line catalog, pricing, document support, distribution directory, news and events. For warranty support 877-etncare for a general directory of eaton electrical products (800) 525-2000 for on-site field service, commissioning & maintenan...

  • Page 7

    Medium voltage switchgear assembly.

  • Page 9: Section Table of Contents

    Medium voltage switchgear assembly section table of contents 1.0 medium voltage switchgear assembly vol. 3 section table of contents 1.1 component data 1.1.1 im02602003e-edr-3000 revd manual.

  • Page 11

    Component data.

  • Page 13

    Edr-3000 - distribution relay installation, operation and maintenance software-version: 2.5. B im02602003e revision: d english.

  • Page 14

    Edr-3000 im02602003e edr-3000 functional overview www.Eaton.Com 2 50p standard 3 1 50x 51x cts 79 74 tc option fundamental and rms, max/min/avg currents thd current current phasors sequence currents metering sotf clpu trend recorder event recorder fault recorder waveform recorder zone interlocking i...

  • Page 15

    Edr-3000 im02602003e table of contents edr-3000 functional overview............................................................................................................................... 2 table of contents.........................................................................................

  • Page 16

    Edr-3000 im02602003e powerport-e keyboard commands........................................................................................................................... 170 measuring values.............................................................................................................

  • Page 17

    Edr-3000 im02602003e tcp/ip settings......................................................................................................................................................... 261 direct commands of the system module.........................................................................

  • Page 18

    Edr-3000 im02602003e breaker wear............................................................................................................................................................ 384 control - example: switching of a breaker....................................................................

  • Page 19

    Edr-3000 im02602003e digital inputs.............................................................................................................................................................. 648 relay outputs............................................................................................

  • Page 20

    Edr-3000 im02602003e comments on the manual this manual gives a general explanation of the tasks of device planning, parameter setting, installation, commissioning, operation, and maintenance of the eaton devices. The manual serves as reference document for: engineers in the protection field; commis...

  • Page 21

    Edr-3000 im02602003e warning indicates a hazardous situation which, if not avoided, could result in death or serious injury. Caution, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Caution, without the safety alert ...

  • Page 22

    Edr-3000 im02602003e typical applications for this product family/device line are for example: feeder protection; mains protection; transformer protection and machine protection. This device is not designed for any usage beyond these applications. This applies also to the use as a partly completed m...

  • Page 23

    Edr-3000 im02602003e out-of-date publication this publication may have been revised or updated since this copy was produced. To verify that you have the latest revision, be sure to check the eaton corporation website: http://www.Eaton.Com the latest versions of most publications are available at thi...

  • Page 24

    Edr-3000 im02602003e electrostatic discharge awareness all electronic equipment is sensitive to electrostatic discharge, some components more than others. To protect these components from electrostatic damage, the user must take special precautions to minimize or eliminate electrostatic discharges. ...

  • Page 25

    Edr-3000 im02602003e what is included with the device the device package includes all connection terminals, except communication connectors, but does not include the fastening material. Please check the package for completeness upon delivery. Device package contents: 1 – protective relay; 1 – mount ...

  • Page 26

    Edr-3000 im02602003e symbols www.Eaton.Com 14 in ac tiv e ac tiv e ig .D ir n po ss - >n on di r t rip 1 2 s et tin g v al ue : am e> . I d ev ic e p la nn in g: am e> s ig na l: ig m ea su re d v al ue s: am e> .*i nt a lm l 1 in te rn al m es sa ge f un ct io na l d es cr ip tio n: if th e se tti ...

  • Page 27

    Edr-3000 im02602003e www.Eaton.Com 15 a nd o r n eg at ed in pu t n eg at ed o ut pu t b an d- pa ss (f ilt er ) ih 1 b an d- pa ss (f ilt er ) ih 2 q uo tie nt o f a na lo g v al ue s t1 d el ay t im er 1 bkr .T- tr ip c m d t a na lo g v al ue s an d s q r 1 q a b c d r s fl ip -fl op a b c d 0 0 ...

  • Page 28

    Edr-3000 im02602003e www.Eaton.Com 16 2 2 in p u t s ig n al o u tp u t s ig n al 2 n am e. A ct iv e 3 n am e. B lo t rip c m d 4 n am e. A ct iv e 5 ih 2. B lo p ha se a 6 ih 2. B lo p ha se b 7 ih 2. B lo p ha se c 8 ih 2. B lo ig 9 n am e. F au lt in p ro je ct ed d ire ct io n 10 n am e. F au l...

  • Page 29

    Edr-3000 im02602003e www.Eaton.Com 17 34 bk r.P os c lo se 35 bk r.P os o p en 33 bk r.S ta te p le as e r ef er to d ia gr am : b kr .B kr m an ag er p le as e r ef er to d ia gr am : b kr .B kr m an ag er p le as e r ef er to d ia gr am : b kr .B kr m an ag er 36 bk r.P os in de te rm 37 b kr .P o...

  • Page 30

    Edr-3000 im02602003e www.Eaton.Com 18 41 bk r.P ro t c lo s e 42 bk r.C lo se c m d b kr .P ro t c lo s e b kr .C lo s e c m d 3 9 p le as e r ef er to d ia gr am : q -> &v d ec ou pl in g di st rib ut ed g en er at or q -> &v d ec ou pl in g di st rib ut ed g en er at or 4 0 p le as e r ef er to d ...

  • Page 31

    Edr-3000 im02602003e www.Eaton.Com 19 access level read only-lv0 prot-lv1 prot-lv2 supervisor-lv3 control-lv1 control-lv2 parameters can only be read within this level. This level enables to execute resets and acknowledgements this level enables to modify protection settings this level provides full...

  • Page 32

    Edr-3000 im02602003e general conventions www.Eaton.Com 20 » parameters are indicated by right and left double arrow heads and written in italic .« »signals are indicated by right and left double arrow heads and small caps .« [paths are indicated by brackets.] software and device names are written in...

  • Page 33

    Edr-3000 im02602003e load reference arrow system within the e-series the “load reference arrow system” is used in principal. Generator protection relays are working based on the “generator reference system”. Www.Eaton.Com 21.

  • Page 34

    Edr-3000 im02602003e device edr-3000 device planning pla nning of a device means to reduce the functional range to a degree that suits the protection task to be fulfilled ( i.E.: the device shows only those functions needed or desired). If the user, for example, deactivates the voltage protection fu...

  • Page 36

    Edr-3000 im02602003e installation and wiring three-side-view and panel cutout depending on the connection method of the communication system used, the needed space (depth) differs. If, for instance, a d-sub-plug is used, it has to be added to the depth dimension. Even when the auxiliary voltage is s...

  • Page 37

    Edr-3000 im02602003e the housing must be carefully grounded. Connect a ground cable (4 to 6 mm 2 [awg 12-10] / 1.7 nm [15 in-lb]) to the housing, using the screw that is marked with the ground symbol (at the rear side of the device). The power supply card needs a separate ground connection (2.5 mm 2...

  • Page 38

    Edr-3000 im02602003e outline standard mount - door cut-out the housing must be carefully grounded. Connect a ground cable (4 to 6 mm 2 [awg 12-10] / 1.7 nm [15 in-lb]) to the housing, using the screw that is marked with the ground symbol (at the rear side of the device). The power supply card needs ...

  • Page 39

    Edr-3000 im02602003e overview of slots - assembly groups in line with the customers' requirement, the devices are combined in a modular way (in compliance with the order code). In each of the slots, an assembly/group may be integrated. In the following diagram, the terminal assignment of the individ...

  • Page 40

    Edr-3000 im02602003e grounding the housing must be carefully grounded. Connect a ground cable (4 to 6 mm 2 [awg 12-10] / 1.7 nm [15 in-lb]) to the housing, using the screw that is marked with the ground symbol (at the rear side of the device). The power supply card needs a separate ground connection...

  • Page 41

    Edr-3000 im02602003e slot x1: power supply card with digital inputs rear side of the device (slots) the type of power supply card and the number of digital inputs on it used in this slot is dependent on the ordered device type. The different variants have a different scope of functions. Available as...

  • Page 42

    Edr-3000 im02602003e di-4 x - power supply and digital inputs make sure that the tightening torque is 5-7 in-lb [0.56-0.79 nm]. This assembly group comprises: a wide-range power supply unit; and four (4) digital inputs, grouped. Auxiliary voltage supply the auxiliary voltage inputs (wide-range power...

  • Page 43

    Edr-3000 im02602003e terminal marking pin assignment www.Eaton.Com 31 v+ v- di1 di2 di3 di4 com1 di-4p x com2 n.C. 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 power supply n.C. N.C. N.C. N.C. N.C. N.C. Do not use do not use 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 v+ power supply n.C. Com1 di1 ...

  • Page 44

    Edr-3000 im02602003e di-8 x - power supply and digital inputs make sure that the tightening torque is 5-7 in-lb [0.56-0.79 nm]. This assembly group comprises: a wide-range power supply unit; two non-grouped digital inputs; and six (6) digital inputs, grouped. Auxiliary voltage supply the auxiliary v...

  • Page 45

    Edr-3000 im02602003e terminal marking pin assignment www.Eaton.Com 33 v+ v- com1 di1 com2 di2 di3 di4 di5 di6 di7 di8 com3 do not use di-8p x com3 n.C. Do not use 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 power supply 1 2 3 4 5 6 7 8 9 10 11 12 com1 13 14 15 16 17 18 v+ power supply di1 com2 di2 ...

  • Page 46

    Edr-3000 im02602003e slot x2: relay output card, irig-b, zone interlock, sc rear side of the device (slots) the type of card in this slot is dependent on the ordered device type. The different variants have a different scope of functions. Available assembly groups in this slot: (ro-3 x2): assembly g...

  • Page 47

    Edr-3000 im02602003e ro-3 x - relay outputs and supervision contact the relay outputs are potential-free contacts. In the assignment/relay outputs section, the assignment of the relay outputs is specified. The changeable signals are listed in the assignment list section . Make sure that the tighteni...

  • Page 48

    Edr-3000 im02602003e terminal marking pin assignment www.Eaton.Com 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 ro1 ro2 ro3 x?. Sc n.C. N.C. N.C. N.C. N.C. N.C. Ro1 cmn ro1 n.O. Ro1 n.C. Ro2 cmn ro2 n.O. Ro2 n.C. Ro3 cmn ro3 n.O. Ro3 n.C. 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 sc n.C. Sc n....

  • Page 49

    Edr-3000 im02602003e ro-5 x - relay outputs and system contact the relay outputs are potential-free contacts. In the assignment/relay outputs section, the assignment of the relay outputs is specified. The changeable signals are listed in the assignment list section . Make sure that the tightening to...

  • Page 50

    Edr-3000 im02602003e terminal marking pin assignment www.Eaton.Com 38 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 ro3 ro1 ro2 ro4 ro5 x?. Sc ro1 cmn ro1 n.O. Ro1 n.C. Ro2 cmn ro2 n.O. Ro2 n.C. Ro3 cmn ro3 n.O. Ro3 n.C. Ro4 cmn ro4 n.O. Ro4 n.C. Ro5 cmn ro5 n.O. Ro5 n.C. 1 3 2 4 5 6 7 8 9 10 11 12 1...

  • Page 51

    Edr-3000 im02602003e ro-3zi x - relay outputs, irig-b00x, zone interlock and sc the relay outputs are potential-free contacts. In the assignment/relay outputs section, the assignment of the relay outputs is specified. The changeable signals are listed in the assignment list section . Make sure that ...

  • Page 52

    Edr-3000 im02602003e terminal marking pin assignment www.Eaton.Com 40 ro3 cmn ro3 n.O. Ro3 n.C. 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 irig-b+ irig-b- ro1 n.O. Ro2 n.O. Sc n.C. Sc n.O. Sc cmn com out in com ro-3zi x 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 ro3 x?. Sc irig-b+ irig-b- com ou...

  • Page 53

    Edr-3000 im02602003e slot x3: current transformer measuring inputs rear side of the device (slots) available assembly groups in this slot: (ti-4 x3): standard ground current measuring card. (tis-4 x3): sensitive ground current measuring card. The technical data of the sensitive ground measuring inpu...

  • Page 54

    Edr-3000 im02602003e ti x- standard phase and ground current measuring input card a current measuring card is provided with four (4) current measuring inputs: three for measuring the phase currents and one for measuring of the ground current. Each of the current measuring inputs has a measuring inpu...

  • Page 55

    Edr-3000 im02602003e terminal markings pin assignment www.Eaton.Com 43 ia-1a ia-n ia-5a ib-1a ib-n ic-1a ic-n ic-5a ix-1a ix-n ix-5a ib-5a 1 2 3 4 5 6 7 8 10 11 9 12 1 2 3 4 5 6 7 8 9 10 11 12 ia 1a 5a n ib 1a 5a n ic 1a 5a n ix 1a 5a n x?..

  • Page 56

    Edr-3000 im02602003e tis x – phase and sensitive ground current measuring card the sensitive ground current measuring card is provided with four (4) current measuring inputs: three for measuring the phase currents and one for measuring of the sensitive ground current (the sensitive ground current in...

  • Page 57

    Edr-3000 im02602003e terminal markings pin assignment www.Eaton.Com 45 ia-1a ia-n ia-5a ib-1a ib-n ic-1a ic-n ic-5a ix-1a ix-n ix-5a ib-5a 1 2 3 4 5 6 7 8 10 11 9 12 1 2 3 4 5 6 7 8 9 10 11 12 ia 1a 5a n ib 1a 5a n ic 1a 5a n ix 1a 5a n x?..

  • Page 58

    Edr-3000 im02602003e common ct wiring configurations check the installation direction. It is imperative that the secondary sides of measuring transformers be grounded. The current measuring inputs may exclusively be connected to current measuring transformers (with galvanic separation). Ct secondary...

  • Page 59

    Edr-3000 im02602003e 3-phase, 3-wire ig calculated www.Eaton.Com 47 a b c ia ib ic 1 x?. 2 3 4 5 6 7 8 9 10 11 12 three-phase current measurement; inom secondary = 5 a. Ia 1a 5a n ib 1a 5a n ic 1a 5a n ix 1a 5a n ib' ic' ia' ir calc = ia + ib + ic = ig.

  • Page 60

    Edr-3000 im02602003e 3-phase, 3-wire ig measured www.Eaton.Com 48 a b c ib' ia ic' ib ic ia' 1 x?. 2 3 4 5 6 7 8 9 10 11 12 three-phase current measurement; inom secondary = 1 a. Ground current measuring via zero sequence ct ; ignom secondary = 1 a. Ix' ia 1a 5a n ib 1a 5a n ic 1a 5a n ix 1a 5a n wa...

  • Page 61

    Edr-3000 im02602003e 4-wire system, 4 th ct on neutral www.Eaton.Com 49 a b c ia ib ic 1 x?. 2 3 4 5 6 7 8 9 10 11 12 4-wire system, 4th ct on neutral; in secondary = 5 a. Ia 1a 5a n ib 1a 5a n ic 1a 5a n ix 1a 5a n ib' ic' ia' n in in' ix meas=in ir calc = ig = ia + ib + ic + in ir calc´.

  • Page 62

    Edr-3000 im02602003e 4-wire system ground current ct involving neutral www.Eaton.Com 50 a b c ia ib ic 1 x?. 2 3 4 5 6 7 8 9 10 11 12 4-wire system with ground current ct (toroidal) involving neutral; in secondary = 5 a. Ia 1a 5a n ib 1a 5a n ic 1a 5a n ix 1a 5a n ib' ic' ia' n in ix meas = ig ir ca...

  • Page 63

    Edr-3000 im02602003e slot x100: ethernet interface rear side of the device (slots) an ethernet interface may be available depending on the device type ordered. The available combinations can be gathered from the ordering code. Www.Eaton.Com 51 x1 x2 x3 slot1 slot2 slot3 x100 x 10 1 x103.

  • Page 64

    Edr-3000 im02602003e ethernet - rj45 terminal marking www.Eaton.Com 52 1 8 t xd + t xd – r xd + n .C . N .C . R xd – n .C . N .C ..

  • Page 65

    Edr-3000 im02602003e slot x101: irig-b00x rear side of the device (slots) if the device is equipped with an irig-b00x interface is dependent on the ordered device type. The available combinations can be gathered from the ordering code. Www.Eaton.Com 53 x1 x2 x3 slot1 slot2 slot3 x100 x 10 1 x103.

  • Page 66

    Edr-3000 im02602003e irig-b00x make sure that the tightening torque is 5-7 in-lb [0.56-0.79 nm]. Terminal markings pin assignment for device www.Eaton.Com 54 1 x101 2 irig-b+ irig-b- 1 2 irig-b+ irig-b-.

  • Page 67

    Edr-3000 im02602003e slot x103: data communication rear side of the device (slots) the data communication interface in the x103 slot is dependent on the ordered device type. The scope of functions is dependent on the type of data communication interface. Available assembly groups in this slot: rs485...

  • Page 68

    Edr-3000 im02602003e rs485 - modbus ® rtu make sure that the tightening torque is 2-4 in-lb [0.22-0.45 nm]. Terminal marking pin assignment the modbus ® connection cable must be shielded. The shielding has to be fixed at the screw that is marked with the ground symbol at the rear side of the device....

  • Page 69

    Edr-3000 im02602003e wiring example: device in the middle of the bus wiring example: device at the end of the bus (using the integrated terminal resistor) www.Eaton.Com 57 6 4 5 3 2 1 +5v gnd r1 = 560 Ω r2 = 120 Ω protective relay b(+) b(+)* a(-) a(-)* r1 r2 r1 h f s hi el d 6 4 5 3 2 1 +5v gnd r1 =...

  • Page 70

    Edr-3000 im02602003e shielding options (2-wire + shield) shielding options (3-wire + shield) www.Eaton.Com 58 shield at bus master side connected to earth termination resistors used shield at bus device side connected to earth termination resistors used shield at bus master side connected to earth t...

  • Page 71

    Edr-3000 im02602003e www.Eaton.Com 59 1 3 2 4 5 6 t r -p 1 3 2 4 5 6 t r -p 1 3 2 4 5 6 t r -p 1 3 2 4 5 6 t r -p shield at bus master side connected to earth termination resistors used shield at bus device side connected to earth termination resistors used shield at bus master side connected to ear...

  • Page 72

    Edr-3000 im02602003e slot x120 - pc interface the interface is a 9-pole d-sub at all device fronts. Pin assignment assignment of the null modem cable assignment of the fully wired, null modem cable. Dsub -9 (female) signal dsub -9 (female) signal 2 rxd 3 txd 3 txd 2 rxd 4 dtr 6,1 dsr, dcd 6,1 dsr, d...

  • Page 73

    Edr-3000 im02602003e control wiring diagram below is the recommended control wiring schematic for the edr-3000. Www.Eaton.Com 61.

  • Page 74

    Edr-3000 im02602003e wiring diagrams please refer to the file “edr-3000_wiring_diagrams.Pdf” on your manual cd. Www.Eaton.Com 62.

  • Page 75

    Edr-3000 im02602003e input, output and led settings digital input configuration the state of the digital inputs can be checked within menu: [operations/status display/name of the assembly group (e.G. Di-8x)] the digital inputs can be configured within menu: [device para/digital inputs/name of the as...

  • Page 76

    Edr-3000 im02602003e di-8p x name of the assembly group: di-8p x1 device parameters of the digital inputs on di-8p x parameter description setting range default menu path nom voltage nominal voltage of the digital inputs 24 v dc, 48 v dc, 60 v dc, 110/120 v dc, 230/240 v dc, 110/120 v ac, 230/240 v ...

  • Page 77

    Edr-3000 im02602003e parameter description setting range default menu path debouncing time 2 a change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted. No debouncing time, 20 ms, 50 ms...

  • Page 78

    Edr-3000 im02602003e parameter description setting range default menu path debouncing time 5 a change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted. No debouncing time, 20 ms, 50 ms...

  • Page 79

    Edr-3000 im02602003e digital inputs output signals on di-8p x signal description di 1 signal: digital input di 2 signal: digital input di 3 signal: digital input di 4 signal: digital input di 5 signal: digital input di 6 signal: digital input di 7 signal: digital input di 8 signal: digital input www...

  • Page 80

    Edr-3000 im02602003e di-4p x settings name of the assembly group: di-4p x1 device parameters of the digital inputs on di-4p x parameter description setting range default menu path nom voltage nominal voltage of the digital inputs 24 v dc, 48 v dc, 60 v dc, 110/120 v dc, 230/240 v dc, 110/120 v ac, 2...

  • Page 81

    Edr-3000 im02602003e parameter description setting range default menu path debouncing time 3 a change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted. No debouncing time, 20 ms, 50 ms...

  • Page 82

    Edr-3000 im02602003e digital inputs output signals on di-4p x signal description di 1 signal: digital input di 2 signal: digital input di 3 signal: digital input di 4 signal: digital input www.Eaton.Com 70

  • Page 83

    Edr-3000 im02602003e wired inputs (aliases) available elements: wired inputs the module wiredinputs allows to alias digital inputs. By means of the menu [device para/wiredinputs] the user can assign specific functions on digital inputs. Alias example: the 52a contact will be assigned/connected to di...

  • Page 84

    Edr-3000 im02602003e global protection parameter of the wired inputs wired parameter description setting range default menu path bkr trouble breaker trouble 1..N, dig inputs -.- [device para /wired inputs] 52a m1 main 1 breaker closed 1..N, dig inputs -.- [device para /wired inputs] 52b m1 main 1 br...

  • Page 85

    Edr-3000 im02602003e parameter description setting range default menu path 52b t tie breaker open 1..N, dig inputs -.- [device para /wired inputs] toca t tie breaker connected 1..N, dig inputs -.- [device para /wired inputs] 43/10 t tie breaker selected to trip 1..N, dig inputs -.- [device para /wir...

  • Page 86

    Edr-3000 im02602003e states of the inputs of the wired inputs module name description assignment via bkr trouble-i breaker trouble [device para /wired inputs] 52a m1-i state of the module input: main 1 breaker closed [device para /wired inputs] 52b m1-i state of the module input: main 1 breaker open...

  • Page 87

    Edr-3000 im02602003e relay output configuration the state of the relay outputs can be checked within menu: [operations/status display/name of the assembly group (e.G. Ro-xx)] the relay outputs can be configured within menu: [device para/relay outputs/name of the assembly group (e.G. Ro-xx)] set the ...

  • Page 88

    Edr-3000 im02602003e www.Eaton.Com 76 a ss ig nm en t 1 in ve rt in g 1 a ss ig nm en t 2 in ve rt in g 2 a ss ig nm en t 3 in ve rt in g 3 a ss ig nm en t 4 in ve rt in g 4 a ss ig nm en t 5 in ve rt in g 5 o r in a ct iv e a ct iv e la tc h e d a ss ig nm en t 6 in ve rt in g 6 a ss ig nm en t 7 i...

  • Page 89

    Edr-3000 im02602003e if the relay output contacts are configured as » latched= active«, they will k eep their position even if there is a power outage within the power supply of the protective device. If the relay output contacts are configured as »latched=active«, they will also retain their positi...

  • Page 90

    Edr-3000 im02602003e ro-3 x settings ro-3 x2 direct commands of ro-3 x parameter description setting range default menu path disarmed this is the second step, after the "disarmed ctrl" has been activated, that is required to disarm the relay outputs. This will disarm those relay outputs that are cur...

  • Page 91

    Edr-3000 im02602003e device parameters of ro-3 x parameter description setting range default menu path operating mode operating mode norm de-energ, norm energ norm de-energ [device para /relay outputs /ro-3 x2 /ro 1] t-off delay switch off delay 0.00 - 300.00s 0.2s [device para /relay outputs /ro-3 ...

  • Page 92

    Edr-3000 im02602003e parameter description setting range default menu path assignment 3 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3 x2 /ro 1] inverting 3 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3 x2 /ro 1] as...

  • Page 93

    Edr-3000 im02602003e parameter description setting range default menu path inverting 7 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3 x2 /ro 1] operating mode operating mode norm de-energ, norm energ norm de-energ [device para /relay output...

  • Page 94

    Edr-3000 im02602003e parameter description setting range default menu path inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3 x2 /ro 2] assignment 3 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3 x2 /ro 2] in...

  • Page 95

    Edr-3000 im02602003e parameter description setting range default menu path assignment 7 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3 x2 /ro 2] inverting 7 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3 x2 /ro 2] op...

  • Page 96

    Edr-3000 im02602003e parameter description setting range default menu path assignment 2 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3 x2 /ro 3] inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3 x2 /ro 3] as...

  • Page 97

    Edr-3000 im02602003e parameter description setting range default menu path inverting 6 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3 x2 /ro 3] assignment 7 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3 x2 /ro 3] in...

  • Page 98

    Edr-3000 im02602003e parameter description setting range default menu path t-timeout force the output state will be set by force for the duration of this time. That means, for the duration of this time, the relay output does not show the state of the signals that are assigned on it. Only available i...

  • Page 99

    Edr-3000 im02602003e input states of ro-3 x name description assignment via ro1.1 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 1] ro1.2 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 1] ro1.3 module input state: assignment [device para /relay outpu...

  • Page 100

    Edr-3000 im02602003e name description assignment via ro2.1 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 2] ro2.2 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 2] ro2.3 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 2] ro2....

  • Page 101

    Edr-3000 im02602003e name description assignment via ro3.2 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 3] ro3.3 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 3] ro3.4 module input state: assignment [device para /relay outputs /ro-3 x2 /ro 3] ro3....

  • Page 102

    Edr-3000 im02602003e signals of ro-3 x signal description ro 1 signal: relay output ro 2 signal: relay output ro 3 signal: relay output disarmed! Signal: caution! Relays disarmed in order to safely perform maintenance while eliminating the risk of taking an entire process off-line. (note: zone inter...

  • Page 103

    Edr-3000 im02602003e ro-5 x settings ro-5 x2 direct commands of ro-5 x parameter description setting range default menu path disarmed this is the second step, after the "disarmed ctrl" has been activated, that is required to disarm the relay outputs. This will disarm those relay outputs that are cur...

  • Page 104

    Edr-3000 im02602003e parameter description setting range default menu path force ro4 by means of this function the normal relay output state can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energ...

  • Page 105

    Edr-3000 im02602003e device parameters of ro-5 x parameter description setting range default menu path operating mode operating mode norm de-energ, norm energ norm de-energ [device para /relay outputs /ro-5 x2 /ro 1] t-off delay switch off delay 0.00 - 300.00s 0.2s [device para /relay outputs /ro-5 ...

  • Page 106

    Edr-3000 im02602003e parameter description setting range default menu path assignment 3 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 1] inverting 3 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 1] as...

  • Page 107

    Edr-3000 im02602003e parameter description setting range default menu path inverting 7 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 1] operating mode operating mode norm de-energ, norm energ norm de-energ [device para /relay output...

  • Page 108

    Edr-3000 im02602003e parameter description setting range default menu path inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 2] assignment 3 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 2] in...

  • Page 109

    Edr-3000 im02602003e parameter description setting range default menu path assignment 7 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 2] inverting 7 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 2] op...

  • Page 110

    Edr-3000 im02602003e parameter description setting range default menu path assignment 2 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 3] inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 3] as...

  • Page 111

    Edr-3000 im02602003e parameter description setting range default menu path inverting 6 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 3] assignment 7 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 3] in...

  • Page 112

    Edr-3000 im02602003e parameter description setting range default menu path inverting 1 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 4] assignment 2 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 4] in...

  • Page 113

    Edr-3000 im02602003e parameter description setting range default menu path assignment 6 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 4] inverting 6 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 4] as...

  • Page 114

    Edr-3000 im02602003e parameter description setting range default menu path assignment 1 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 5] inverting 1 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 5] as...

  • Page 115

    Edr-3000 im02602003e parameter description setting range default menu path inverting 5 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-5 x2 /ro 5] assignment 6 assignment 1..N, assignment list -.- [device para /relay outputs /ro-5 x2 /ro 5] in...

  • Page 116

    Edr-3000 im02602003e parameter description setting range default menu path t-timeout disarm the relays will be armed again after expiring of this time. Only available if: mode = timeout disarm 0.00 - 300.00s 0.03s [service /test mode (prot inhibit) /warning! Cont? /disarmed /ro-5 x2] force mode by m...

  • Page 117

    Edr-3000 im02602003e input states of ro-5 x name description assignment via ro1.1 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 1] ro1.2 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 1] ro1.3 module input state: assignment [device para /relay outpu...

  • Page 118

    Edr-3000 im02602003e name description assignment via ro2.1 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 2] ro2.2 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 2] ro2.3 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 2] ro2....

  • Page 119

    Edr-3000 im02602003e name description assignment via ro3.2 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 3] ro3.3 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 3] ro3.4 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 3] ro3....

  • Page 120

    Edr-3000 im02602003e name description assignment via ro4.3 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 4] ro4.4 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 4] ro4.5 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 4] ro4....

  • Page 121

    Edr-3000 im02602003e name description assignment via ro5.4 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 5] ro5.5 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 5] ro5.6 module input state: assignment [device para /relay outputs /ro-5 x2 /ro 5] ro5....

  • Page 122

    Edr-3000 im02602003e signals of ro-5 x signal description ro 1 signal: relay output ro 2 signal: relay output ro 3 signal: relay output ro 4 signal: relay output ro 5 signal: relay output disarmed! Signal: caution! Relays disarmed in order to safely perform maintenance while eliminating the risk of ...

  • Page 123

    Edr-3000 im02602003e ro-3zi x - settings ro-3zi x2 direct commands of ro-3zi x parameter description setting range default menu path disarmed this is the second step, after the "disarmed ctrl" has been activated, that is required to disarm the relay outputs. This will disarm those relay outputs that...

  • Page 124

    Edr-3000 im02602003e parameter description setting range default menu path force ro2 by means of this function the normal relay output state can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energ...

  • Page 125

    Edr-3000 im02602003e global protection parameters of ro-3zi x parameter description setting range default menu path operating mode operating mode norm de-energ, norm energ norm de-energ [device para /relay outputs /ro-3zi x2 /ro 1] t-off delay switch off delay 0.00 - 300.00s 0.2s [device para /relay...

  • Page 126

    Edr-3000 im02602003e parameter description setting range default menu path assignment 3 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3zi x2 /ro 1] inverting 3 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3zi x2 /ro 1...

  • Page 127

    Edr-3000 im02602003e parameter description setting range default menu path inverting 7 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3zi x2 /ro 1] operating mode operating mode norm de-energ, norm energ norm de-energ [device para /relay outp...

  • Page 128

    Edr-3000 im02602003e parameter description setting range default menu path inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3zi x2 /ro 2] assignment 3 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3zi x2 /ro 2...

  • Page 129

    Edr-3000 im02602003e parameter description setting range default menu path assignment 7 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3zi x2 /ro 2] inverting 7 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3zi x2 /ro 2...

  • Page 130

    Edr-3000 im02602003e parameter description setting range default menu path assignment 2 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3zi x2 /ro 3] inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3zi x2 /ro 3...

  • Page 131

    Edr-3000 im02602003e parameter description setting range default menu path inverting 6 inverting of the state of the assigned signal. Inactive, active inactive [device para /relay outputs /ro-3zi x2 /ro 3] assignment 7 assignment 1..N, assignment list -.- [device para /relay outputs /ro-3zi x2 /ro 3...

  • Page 132

    Edr-3000 im02602003e parameter description setting range default menu path t-timeout force the output state will be set by force for the duration of this time. That means, for the duration of this time, the relay output does not show the state of the signals that are assigned on it. Only available i...

  • Page 133

    Edr-3000 im02602003e input states of ro-3zi x name description assignment via ro1.1 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 1] ro1.2 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 1] ro1.3 module input state: assignment [device para /relay...

  • Page 134

    Edr-3000 im02602003e name description assignment via ro2.1 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 2] ro2.2 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 2] ro2.3 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 2...

  • Page 135

    Edr-3000 im02602003e name description assignment via ro3.2 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 3] ro3.3 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 3] ro3.4 module input state: assignment [device para /relay outputs /ro-3zi x2 /ro 3...

  • Page 136

    Edr-3000 im02602003e signals of ro-3zi x signal description zi out signal: zone interlocking out ro 1 signal: relay output ro 2 signal: relay output ro 3 signal: relay output disarmed! Signal: caution! Relays disarmed in order to safely perform maintenance while eliminating the risk of taking an ent...

  • Page 137

    Edr-3000 im02602003e led configuration the leds can be configured within menu: [device para/leds/group x] attention must be paid to insure that there are no overlapping functions due to double or multiple led assignment of colors and flashing codes. If leds are configured as » latched= active«, they...

  • Page 138

    Edr-3000 im02602003e acknowledgment options leds can be acknowledged by: • the push-button »c« at the operating panel; • a signal from the »led reset list« (e.G. Digital inputs or communication signals) (if » latched = active« ); • the »ex acknowledge« module - all leds can be acknowledged at once, ...

  • Page 139

    Edr-3000 im02602003e www.Eaton.Com 127 in ac ti ve a ct iv e l a tc h e d a ss ig nm e nt 1 in ve rt in g 1 a ss ig nm e nt 2 in ve rt in g 2 a ss ig nm e nt 3 in ve rt in g 3 a ss ig nm e nt 4 in ve rt in g 4 a ss ig nm e nt 5 in ve rt in g 5 le d a ct iv e c ol o r le d in ac tiv e c ol o r o r o ...

  • Page 140

    Edr-3000 im02602003e the » system ok (operational) « led this led flashes green while the device is booting. After booting is complete, the led for system ok (operational) lights up in green signaling that the protection (function) is » activated« . If, however, in spite of successful booting, or af...

  • Page 141

    Edr-3000 im02602003e led settings leds group a device parameters of the leds parameter description setting range default menu path latched defines whether the led will be latched when it picks up. Inactive, active active [device para /leds /leds group a /led 1] ack signal acknowledgment signal for t...

  • Page 142

    Edr-3000 im02602003e parameter description setting range default menu path inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 1] assignment 3 assignment 1..N, assignment list -.- [device para /leds /leds group a /led 1] invertin...

  • Page 143

    Edr-3000 im02602003e parameter description setting range default menu path led active color the led lights up in this color if the state of the or- assignment of the signals is true. Green, red, red flash, green flash, - red [device para /leds /leds group a /led 2] led inactive color the led lights ...

  • Page 144

    Edr-3000 im02602003e parameter description setting range default menu path assignment 4 assignment 1..N, assignment list -.- [device para /leds /leds group a /led 2] inverting 4 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 2] assignme...

  • Page 145

    Edr-3000 im02602003e parameter description setting range default menu path assignment 1 assignment 1..N, assignment list 50p[1].Trip [device para /leds /leds group a /led 3] inverting 1 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 3] ...

  • Page 146

    Edr-3000 im02602003e parameter description setting range default menu path inverting 5 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 3] latched defines whether the led will be latched when it picks up. Inactive, active active [device p...

  • Page 147

    Edr-3000 im02602003e parameter description setting range default menu path inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 4] assignment 3 assignment 1..N, assignment list -.- [device para /leds /leds group a /led 4] invertin...

  • Page 148

    Edr-3000 im02602003e parameter description setting range default menu path led active color the led lights up in this color if the state of the or- assignment of the signals is true. Green, red, red flash, green flash, - red flash [device para /leds /leds group a /led 5] led inactive color the led l...

  • Page 149

    Edr-3000 im02602003e parameter description setting range default menu path assignment 4 assignment 1..N, assignment list -.- [device para /leds /leds group a /led 5] inverting 4 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 5] assignme...

  • Page 150

    Edr-3000 im02602003e parameter description setting range default menu path assignment 1 assignment 1..N, assignment list bf.Trip [device para /leds /leds group a /led 6] inverting 1 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 6] assi...

  • Page 151

    Edr-3000 im02602003e parameter description setting range default menu path inverting 5 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 6] latched defines whether the led will be latched when it picks up. Inactive, active inactive [device...

  • Page 152

    Edr-3000 im02602003e parameter description setting range default menu path inverting 2 inverting of the state of the assigned signal. Inactive, active inactive [device para /leds /leds group a /led 7] assignment 3 assignment 1..N, assignment list -.- [device para /leds /leds group a /led 7] invertin...

  • Page 153

    Edr-3000 im02602003e led input states name description assignment via led1.1 module input state: led [device para /leds /leds group a /led 1] led1.2 module input state: led [device para /leds /leds group a /led 1] led1.3 module input state: led [device para /leds /leds group a /led 1] led1.4 module ...

  • Page 154

    Edr-3000 im02602003e name description assignment via led2.3 module input state: led [device para /leds /leds group a /led 2] led2.4 module input state: led [device para /leds /leds group a /led 2] led2.5 module input state: led [device para /leds /leds group a /led 2] acknow sig 2 module input state...

  • Page 155

    Edr-3000 im02602003e name description assignment via acknow sig 3 module input state: acknowledgment signal (only for automatic acknowledgment). [device para /leds /leds group a /led 3] led4.1 module input state: led [device para /leds /leds group a /led 4] led4.2 module input state: led [device par...

  • Page 156

    Edr-3000 im02602003e name description assignment via led5.3 module input state: led [device para /leds /leds group a /led 5] led5.4 module input state: led [device para /leds /leds group a /led 5] led5.5 module input state: led [device para /leds /leds group a /led 5] acknow sig 5 module input state...

  • Page 157

    Edr-3000 im02602003e name description assignment via acknow sig 6 module input state: acknowledgment signal (only for automatic acknowledgment). [device para /leds /leds group a /led 6] led7.1 module input state: led [device para /leds /leds group a /led 7] led7.2 module input state: led [device par...

  • Page 158: Protective

    Edr-3000 im02602003e front panel www.Eaton.Com 146 1 2 3 5 7 6 9 10 rs232 interface ( powerport-e connection) ack/rst-key info key (signals/messages) control softkeys display led »system ok« programmable leds protective device 8 ok-key.

  • Page 159

    Edr-3000 im02602003e item graphic name description 1 (example for an insert) leds group a basically there are 7 programmable leds provided for user to configure, the choice for each programmable led can be any signal from the global assignment list, which includes all internal operation states of ea...

  • Page 160

    Edr-3000 im02602003e item graphic name description 5 softkeys the function of the »softkeys« are contextual. On the bottom line of the display, the present function is displayed/symbolized. Possible functions are: navigation; parameter decrement/increment; scrolling up/down a menu page; moving to a ...

  • Page 161

    Edr-3000 im02602003e item graphic name description 6 info key (signals/messages ) looking through the present led assignment. The direct select key can be activated at any time. If the info key is actuated again, the user will leave the led menu. Here only the first assignments of the leds will be s...

  • Page 162

    Edr-3000 im02602003e item graphic name description 7 »ack/rst- key« to abort changes and to ack- nowledge messages as well as resetting counters. In order to reset, press the soft- key »wrench « and enter the password. The user can exit the reset menu by pressing the softkey » arrow-left« 8 rs232 in...

  • Page 163

    Edr-3000 im02602003e basic menu control the graphic user interface is equivalent to a hierarchical structured menu tree. For access to the individual sub-menus, the »softkeys«/navigation keys are used. The function of the »softkeys« can be found as symbol in the footer of the display. Softkey descri...

  • Page 164

    Edr-3000 im02602003e powerport-e keyboard commands the user can control powerport-e alternatively by means of keyboard commands (instead of the mouse). Key description á move up within the navigation tree or parameter list. â move down within the navigation tree or parameter list. ß collapse the tre...

  • Page 165: Powerport-E

    Edr-3000 im02602003e powerport-e powerport-e is software that is used to configure a device and read data from a device. Powerport-e provides the following: menu controlled parameter setting including validity checks; off-line configuration of all relay types; reading and evaluation of statistical d...

  • Page 166

    Edr-3000 im02602003e installation of powerport-e port 52152 must not be blocked by a firewall. If it is, the connection will be blocked. If the windows user access control pops up while installing powerport-e , please “allow” all installation requirements concerning powerport-e . System requirements...

  • Page 167

    Edr-3000 im02602003e setting up the connection pc - device set up a connection via a serial interface after installation of the software, the »connection pc/notebook to the device« has to be initially configured so that the user is able to read device data or re-write them into the device by means o...

  • Page 168: Powerport-E

    Edr-3000 im02602003e www.Eaton.Com 156 rs232 parameter setting and evaluation via serial/rs232 powerport-e protective relay device example.

  • Page 169

    Edr-3000 im02602003e establishing the serial connection via a usb-/rs232-adapter if your pc/notebook does not have an rs-232 interface, an usb-/rs232-adapter+null modem cable can be used. Only an adapter approved by eaton corporation may be used. First install the adapter (with the related driver th...

  • Page 170

    Edr-3000 im02602003e set-up a connection via ethernet - tcp/ip warning: mixing up ip addresses (in case there is more than one protective device within the tcp/ip network or establishing an unintentional wrong connection to a protective device based on a wrong entered ip address. Transferring parame...

  • Page 171

    Edr-3000 im02602003e www.Eaton.Com 159 tcp/ip parameter setting and evaluation via tcp/ip powerport-e ip -a d d re ss device example.

  • Page 172: ...

    Edr-3000 im02602003e or: www.Eaton.Com 160 protective relay protective relay ... Tcp/ip tcp/ip tcp/ip parameter setting and evaluation via tcp/ip powerport-e ip -a d d re ss ip -a d d re ss ip -a d d re ss tcp/ip ethernet device example device example device example.

  • Page 173

    Edr-3000 im02602003e set-up a connection via modbus tunnel establishing a connection via a gateway (tcp/ip)/modbus rtu to the device is only possible if your device is equipped with an ethernet interface (rj45). Contact your it administrator in order to establish the network connection. Part 1: if y...

  • Page 174: ...

    Edr-3000 im02602003e www.Eaton.Com 162 protective relay protective relay ... Tcp/ip modbus rtu modbus rtu parameter setting and evaluation via modbus tunnel powerport-e power xpert gateway sl a v e id 2 sl a v e id 3 sl a v e id n ip-address modbus rtu device example device example device example.

  • Page 175

    Edr-3000 im02602003e connected to the device and calling up websites at the same time* *=applies to serial connections only (rs232) in principle, it is possible to call up websites while there is an active connection to the device. If your computer has no direct connection to the internet, that mean...

  • Page 176

    Edr-3000 im02602003e powerport-e troubleshooting during setting up the connection make sure that the windows service telephony is sta rted. In [start>system control >administration >services] the service »telephony« must be visible and must have been started. If not, the service has to be started. F...

  • Page 177

    Edr-3000 im02602003e powerport-e persistent connection problems in the case of persistent connection problems, the user should remove all connection settings and establish them again. In order to remove all connection settings, please proceed as follows. 1. Remove the settings for the dial-up networ...

  • Page 178

    Edr-3000 im02602003e loading of device data when using powerport-e start the powerport-e application . Make sure the connection has been established properly. Connect your pc with the device via a null modem cable . Select »receiving data from the device« in the »device« menu. Restoring device data ...

  • Page 179

    Edr-3000 im02602003e in order to (re-)transfer changed parameters into the device, select »transfer all parameters into the device« in the »device« menu. Confirm the safety inquiry »shall the parameters be overwritten into the device?«. Enter the password for setting parameters in the pop-up window....

  • Page 180

    Edr-3000 im02602003e printing of all opened working windows: the data shown on all windows are printed (i.E.: this applies only if more than one window is opened). Printing of the device parameter tree as from a shown position on: all data and parameters of the device parameter tree are printed as f...

  • Page 181

    Edr-3000 im02602003e off-line device planning via powerport-e in order to be able to transmit a parameter file (e.G.: created off-line) into the device, the following information must be located: type code (written on the top of the device/type label); and version of the device model (can be found i...

  • Page 182

    Edr-3000 im02602003e powerport-e keyboard commands you can control powerport-e alternatively by means of keyboard commands (instead of the mouse) key description á moving up within the navigation tree or parameter list. â moving down within the navigation tree or parameter list. ß collapse the tree ...

  • Page 183

    Edr-3000 im02602003e measuring values read out measured values in the »operation/measured values« menu, both measured and calculated values can be viewed. The measured values are ordered by »standard values« and »special values« (depending on the type of device). Read out of measured values via powe...

  • Page 184

    Edr-3000 im02602003e hmi and powerport-e : power auto scaling kw, kvar or kva mw, mvar or mva gw, gvar or gva www.Eaton.Com 172.

  • Page 185

    Edr-3000 im02602003e energy units (applies only for devices with energy measurement) by means of the parameter » energy units« the user can determine how measured values are to be displayed within the hmi and powerport-e : energy auto scaling kwh, kvarh or kvah mwh, mvarh or mvah gwh, gvarh or gvah ...

  • Page 186

    Edr-3000 im02602003e current - measured values ct if the device is not equipped with an voltage measuring card the first measuring input on the first current measuring card (slot with the lowest number) will be used as the reference angle (» ia«). Value description menu path ia fund. Measured value:...

  • Page 187

    Edr-3000 im02602003e value description menu path angle ic measured value (calculated): angle of phasor ic [operation /measured values /current fund.] angle ix meas measured value (calculated): angle of phasor ix meas [operation /measured values /current fund.] angle ir calc measured value (calculate...

  • Page 188

    Edr-3000 im02602003e value description menu path %ib thd measured value (calculated): ib total harmonic distortion [operation /measured values /current rms] %ic thd measured value (calculated): ic total harmonic distortion [operation /measured values /current rms] ia thd measured value (calculated):...

  • Page 189

    Edr-3000 im02602003e statistics statistics in menu »operation/statistics« the min., max. And mean values of the measured and calculated measured quantities can be found. Configuration of the minimum and maximum values the calculation of the minimum and maximum values will be started: when a reset si...

  • Page 190

    Edr-3000 im02602003e configuration of the average value calculation configuration of the current based average value calculation* *=availability depends on the ordered device code. Current based average values and peak values time period for the calculation of the average and peak values start optio...

  • Page 191

    Edr-3000 im02602003e configuration of the voltage based average value calculation* *=availability depends on the ordered device code. Voltage based average values time period for the calculation of the average values start options reset of the average and peak values configuration options where to c...

  • Page 192

    Edr-3000 im02602003e direct commands parameter description setting range default menu path resfc all resetting of all statistic values (current demand, power demand, min, max) inactive, active inactive [operation /reset] resfc i demand resetting of statistics - current demand (avg, peak avg) inactiv...

  • Page 193

    Edr-3000 im02602003e parameter description setting range default menu path resfc i demand resetting of statistics - current demand (avg, peak avg) 1..N, assignment list -.- [device para /statistics /demand /current demand] duration i demand recording time only available if: start i demand via: = dur...

  • Page 194

    Edr-3000 im02602003e states of the inputs of the statistics module name description assignment via startfc i demand-i state of the module input: start of statistics of the current demand (update the displayed demand ) [device para /statistics /demand /current demand] resfc i demand-i state of the mo...

  • Page 195

    Edr-3000 im02602003e signals of the statistics module signal description resfc all signal: resetting of all statistic values (current demand, power demand, min, max) resfc i demand signal: resetting of statistics - current demand (avg, peak avg) resfc max signal: resetting of all maximum values resf...

  • Page 196

    Edr-3000 im02602003e current - statistic values value description menu path i1 max fund. Maximum value positive phase sequence current (fundamental) [operation /statistics /max /ct] i1 min fund. Minimum value positive phase sequence current (fundamental) [operation /statistics /min /ct] i2 max fund....

  • Page 197

    Edr-3000 im02602003e value description menu path ib avg rms ib average value (rms) [operation /statistics /demand /current demand] ib min rms ib minimum value (rms) [operation /statistics /min /ct] ic max rms ic maximum value (rms) [operation /statistics /max /ct] ic avg rms ic average value (rms) [...

  • Page 198

    Edr-3000 im02602003e value description menu path %(i2/i1) max measured value (calculated): i2/i1 maximum value, phase sequence will be taken into account automatically [operation /statistics /max /ct] %(i2/i1) min measured value (calculated): i2/i1 minimum value, phase sequence will be taken into ac...

  • Page 199

    Edr-3000 im02602003e system alarms available elements: sysa within the system alarms menu [sysa] the user can configure: general settings (activate/inactivate the demand management, optional assign a signal, that will block the demand management); demand management (current); and thd protection. Ple...

  • Page 200

    Edr-3000 im02602003e example for a sliding window: i f the sliding window is selected and the interval is set to 15 minutes, the protective device calculates and updates the average current or power continuously, for the past 15 minutes (the newest measuring value replaces the oldest measuring value...

  • Page 201

    Edr-3000 im02602003e www.Eaton.Com 189 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 window configuration = sliding window configuration = fixed sliding sliding t-del...

  • Page 202

    Edr-3000 im02602003e step 2. In addition, the demand specific settings have to be configured in the [system para/system alarms/demand] menu: determine if the demand should generate an alarm or if it should run in the silent mode (alarm active/inactive); set the threshold; and where applicable, set a...

  • Page 203

    Edr-3000 im02602003e device planning parameters of the demand management parameter description options default menu path mode mode do not use, use use [device planning] signals of the demand management (states of the outputs) signal description active signal: active exblo signal: external blocking a...

  • Page 204

    Edr-3000 im02602003e parameter description setting range default menu path t-delay tripping delay 0 - 60min 0min [sysa /demand /current demand] alarm alarm inactive, active inactive [sysa /thd /i thd] threshold threshold (to be entered as primary value) 1 - 500000a 500a [sysa /thd /i thd] t-delay tr...

  • Page 205

    Edr-3000 im02602003e states of the inputs of the demand management name description assignment via exblo-i module input state: external blocking [sysa /general settings] www.Eaton.Com 193.

  • Page 206

    Edr-3000 im02602003e resets collective acknowledgments for latched signals: collective acknowledgments leds relay outputs scada pending trip command leds+ relay outputs+ scada+ pending trip command via powerport-e or at the panel all... Can be acknowledged. At the panel, the [operation\ acknowledge]...

  • Page 207

    Edr-3000 im02602003e options for individual acknowledgments for latched signals: individual acknowledgment leds relay output pending trip command via a signal from the assignment list (e.G.: a digital input), a single ... Can be acknowledged. Single led: where? Within the configuration menu of this ...

  • Page 208

    Edr-3000 im02602003e manual acknowledgment • press the »ack/rst« button on the panel. • select the item to be acknowledged via the softkeys: • relay outputs; • leds; • scada; • a trip command; or • all the above mentioned items at once. • press the softkey with the »wrench-symbol«. • enter the passw...

  • Page 209

    Edr-3000 im02602003e external acknowledgments within the [ex acknowledge] menu, the user can assign a signal (e.G.: the state of a digital input) from the assignment list that: • acknowledges all (acknowledgeable) leds at once; • acknowledges all (acknowledgeable) output relays at once; or • acknowl...

  • Page 210

    Edr-3000 im02602003e external led - acknowledgment signals the following signals can be used for external acknowledgment of latched leds. Name description -.- no assignment di-4p x1.Di 1 signal: digital input di-4p x1.Di 2 signal: digital input di-4p x1.Di 3 signal: digital input di-4p x1.Di 4 signa...

  • Page 211

    Edr-3000 im02602003e name description logic.Le2.Gate out signal: output of the logic gate logic.Le2.Timer out signal: timer output logic.Le2.Out signal: latched output (q) logic.Le2.Out inverted signal: negated latched output (q not) logic.Le3.Gate out signal: output of the logic gate logic.Le3.Time...

  • Page 212

    Edr-3000 im02602003e name description logic.Le11.Timer out signal: timer output logic.Le11.Out signal: latched output (q) logic.Le11.Out inverted signal: negated latched output (q not) logic.Le12.Gate out signal: output of the logic gate logic.Le12.Timer out signal: timer output logic.Le12.Out signa...

  • Page 213

    Edr-3000 im02602003e name description logic.Le20.Out signal: latched output (q) logic.Le20.Out inverted signal: negated latched output (q not) logic.Le21.Gate out signal: output of the logic gate logic.Le21.Timer out signal: timer output logic.Le21.Out signal: latched output (q) logic.Le21.Out inver...

  • Page 214

    Edr-3000 im02602003e name description logic.Le29.Out inverted signal: negated latched output (q not) logic.Le30.Gate out signal: output of the logic gate logic.Le30.Timer out signal: timer output logic.Le30.Out signal: latched output (q) logic.Le30.Out inverted signal: negated latched output (q not)...

  • Page 215

    Edr-3000 im02602003e name description logic.Le39.Gate out signal: output of the logic gate logic.Le39.Timer out signal: timer output logic.Le39.Out signal: latched output (q) logic.Le39.Out inverted signal: negated latched output (q not) logic.Le40.Gate out signal: output of the logic gate logic.Le4...

  • Page 216

    Edr-3000 im02602003e name description logic.Le48.Timer out signal: timer output logic.Le48.Out signal: latched output (q) logic.Le48.Out inverted signal: negated latched output (q not) logic.Le49.Gate out signal: output of the logic gate logic.Le49.Timer out signal: timer output logic.Le49.Out signa...

  • Page 217

    Edr-3000 im02602003e name description logic.Le57.Out signal: latched output (q) logic.Le57.Out inverted signal: negated latched output (q not) logic.Le58.Gate out signal: output of the logic gate logic.Le58.Timer out signal: timer output logic.Le58.Out signal: latched output (q) logic.Le58.Out inver...

  • Page 218

    Edr-3000 im02602003e name description logic.Le66.Out inverted signal: negated latched output (q not) logic.Le67.Gate out signal: output of the logic gate logic.Le67.Timer out signal: timer output logic.Le67.Out signal: latched output (q) logic.Le67.Out inverted signal: negated latched output (q not)...

  • Page 219

    Edr-3000 im02602003e name description logic.Le76.Gate out signal: output of the logic gate logic.Le76.Timer out signal: timer output logic.Le76.Out signal: latched output (q) logic.Le76.Out inverted signal: negated latched output (q not) logic.Le77.Gate out signal: output of the logic gate logic.Le7...

  • Page 220

    Edr-3000 im02602003e manual resets in the »operation/reset« menu, the user can: • reset counters; • delete records (e.G.: waveform records); and • reset special things (like statistics, thermal replica, etc.). The description of the reset commands can be found within the corresponding modules. Manua...

  • Page 221

    Edr-3000 im02602003e status display in the status display within the »operation« menu, the present state of all signals can be viewed. This means the user is able to see if the individual signals are active or inactive at that moment. The user can see all signals sorted by protective elements/module...

  • Page 222

    Edr-3000 im02602003e operating panel (hmi) hmi special parameters of the panel the »device parameter/hmi« menu is used to define the contrast of the display, the maximum admissible edit time, and the menu language (after expiration, all unsaved parameter changes will be rejected). Direct commands of...

  • Page 223

    Edr-3000 im02602003e recorders waveform recorder waveform rec the waveform recorder works with 32 samples per cycle. It can be started by one of eight start events (selection from the »assignment list«/or-logic). The waveform record contains the measuring values including the pre-trigger time. By me...

  • Page 224

    Edr-3000 im02602003e www.Eaton.Com 212 start: 1 trigger start: 2 trigger start: 3 trigger start: 4 trigger start: 5 trigger start: 6 trigger start: 7 trigger start: 8 trigger man. Trigger recording or or.

  • Page 225

    Edr-3000 im02602003e www.Eaton.Com 213 start 1 t t 0 1 0 1 300 ms 1200 ms pre-trigger time t 0 1 500 ms post-trigger time t 0 1 2000 ms t-rec t 0 1 2000 ms max file size start 1 = prot.Pickup start 2 = -.- start 3 = -.- start 4 = -.- start 5 = -.- start 6 = -.- start 7 = -.- start 8 = -.- post-trigg...

  • Page 226

    Edr-3000 im02602003e www.Eaton.Com 214 start 1 t t 0 1 0 1 300 ms 200 ms pre-trigger time t 0 1 500 ms post-trigger time t 0 1 1000 ms t-rec t-rec t 0 1 2000 ms max file size start 1 = prot.Trip start 2 = -.- start 3 = -.- start 4 = -.- start 5 = -.- start 6 = -.- start 7 = -.- start 8 = -.- post-tr...

  • Page 227

    Edr-3000 im02602003e read out of w aveform records within the » operation/waveform rec« menu, the user can: • detect the accumulated waveform records. Within the »operation/recorders/man trigger« menu, the user can trigger the waveform recorder manually. To read out the w aveform recorder with power...

  • Page 228

    Edr-3000 im02602003e deleting waveform records within the »operation/waveform rec« menu, the user can: delete waveform records; choose the waveform record that is to be deleted via »softkey« »up« and »softkey« »down«; call up the detailed view of the waveform record via »softkey« »right«; confirm by...

  • Page 229

    Edr-3000 im02602003e direct commands of the waveform recorder module parameter description setting range default menu path man. Trigger manual trigger false, true false [operation /recorders /man. Trigger] res all rec reset all records inactive, active inactive [operation /reset] global protection p...

  • Page 230

    Edr-3000 im02602003e parameter description setting range default menu path start: 7 start recording if the assigned signal is true. 1..N, assignment list -.- [device para /recorders /waveform rec] start: 8 start recording if the assigned signal is true. 1..N, assignment list -.- [device para /record...

  • Page 231

    Edr-3000 im02602003e waveform recorder module input states name description assignment via start1-i state of the module input:: trigger event / start recording if: [device para /recorders /waveform rec] start2-i state of the module input:: trigger event / start recording if: [device para /recorders ...

  • Page 232

    Edr-3000 im02602003e waveform recorder module signals signal description recording signal: recording memory full signal: memory full clear fail signal: clear failure in memory res all rec signal: all records deleted res record signal: delete record man. Trigger signal: manual trigger www.Eaton.Com 2...

  • Page 233

    Edr-3000 im02602003e special parameters of the waveform recorder value description default size menu path rec state recording state ready ready, recording, writing file, trigger blo [operation /status display /recorders /waveform rec] error code error code ok ok, write err, clear fail, calculation e...

  • Page 234

    Edr-3000 im02602003e fault recorder fault rec purpose of the fault recorder the fault recorder provides compressed information about faults (e.G. Trip causes). The compressed information can be read out also at the hmi. This might be helpful for fast fault analysis already at the hmi. After a fault,...

  • Page 235

    Edr-3000 im02602003e definitions time to trip: time between first alarm (prot.Pickup) and first trip (prot.Trip) decision fault duration: time period from the rising edge of the general pickup ( »p rot .P ickup « ) signal up to the falling edge of the general pickup signal. Please note that general ...

  • Page 236

    Edr-3000 im02602003e behaviour of the fault recorder who triggers the fault recorder? The fault recorder will be triggered by the rising edge of the »p rot .P ickup « (general pickup) signal. Please note that » p rot .P ickup « (general pickup) is an or-connection of all pickup signals. The first pi...

  • Page 237

    Edr-3000 im02602003e how to close the overlay/popup? By using softkey »ok«. How to find out fast, if a fault has lead to a trip or not? Faults that lead to a trip will be indicated by a flash icon (right side) within the overview menu of the fault recorder. Which fault record pops up? The newest fau...

  • Page 238

    Edr-3000 im02602003e content of a fault record a fault record comprises information about: date/time date and time of the fault faultnr the number of the fault will be incremented with each fault (general alarm or »p rot .P ickup «) grid fault no. This counter will be incremented by each general pic...

  • Page 239

    Edr-3000 im02602003e how to set up the fault recorder the » record-mode« will determine if trips only cause a fault record or if also alarms without a consecutively trip should cause a fault record. This parameter is to be set within menu [device para\recorders\fault rec] how to navigate within the ...

  • Page 240

    Edr-3000 im02602003e how to read out the fault recorder via powerport-e if powerport-e is not running, please start the application. If the device data have not been loaded, click »receive data from the device« in the »device« menu. Double click the »operation« icon in the navigation tree. Double cl...

  • Page 241

    Edr-3000 im02602003e direct commands of the fault recorder module parameter description setting range default menu path res all rec reset all records inactive, active inactive [operation /reset] global protection parameters of the fault recorder module parameter description setting range default men...

  • Page 242

    Edr-3000 im02602003e event recorder event rec the event recorder can register up to 300 events and the last 50 (minimum) saved events are stored in non-volatile memory, and therefore retained when power is lost to the unit. The following information is provided for any of the events. Events are logg...

  • Page 243

    Edr-3000 im02602003e read out the event recorder call up the » main menu«. Call up the sub-menu »operation/recorders/event rec« . Select an event. To read out the event recorder via powerport-e if powerport-e is not running, please start the application. If the device data have not been loaded, clic...

  • Page 244

    Edr-3000 im02602003e via the print menu, the user can export the data into a file. Please proceed as follows. •call up the data as described above. •call up the »file/print« menu. •choose »print actual working window« within the pop-up. •press the »print« button. •press the »export to file« button. ...

  • Page 245

    Edr-3000 im02602003e direct commands of the event recorder module parameter description setting range default menu path res all rec reset all records inactive, active inactive [operation /reset] event recorder module signals signal description res all rec signal: all records deleted www.Eaton.Com 23...

  • Page 246

    Edr-3000 im02602003e trend recorder available elements: trend rec functional description the trend data are data points stored by the trend recorder on the relay device over fixed intervals of time, and can be downloaded from the device using powerport-e. A trend record is viewable using the quality...

  • Page 247

    Edr-3000 im02602003e selection list for trending name description -.- no assignment ct.Ia rms measured value: phase current (rms) ct.Ib rms measured value: phase current (rms) ct.Ic rms measured value: phase current (rms) ct.Ix meas rms measured value (measured): ix (rms) ct.Ir calc rms measured val...

  • Page 248

    Edr-3000 im02602003e global protection parameters of the trend recorder parameter description setting range default menu path resolution resolution (recording frequency) 60 min, 30 min, 15 min, 10 min, 5 min 15 min [device para /recorders /trend rec] observed value1 observed value1 1..N, trendreclis...

  • Page 249

    Edr-3000 im02602003e parameter description setting range default menu path observed value10 observed value10 1..N, trendreclist -.- [device para /recorders /trend rec] www.Eaton.Com 237.

  • Page 250

    Edr-3000 im02602003e trend recorder module signals (output states) signal description hand reset hand reset direct commands of the trend recorder parameter description setting range default menu path reset delete all entries inactive, active inactive [operation /reset] counter values of the trend re...

  • Page 251

    Edr-3000 im02602003e time synchronization timezones the device gives the user the ability to synchronize the device with a central time generator. This provides the following advantages: the time does not drift from the reference time. A continuously accumulating deviation of the reference time ther...

  • Page 252

    Edr-3000 im02602003e accuracy of time synchronization the accuracy of the device's synchronized system time depends on different factors: accuracy of the connected time generator; synchronization protocol that is used; and at modbus tcp and sntp: network load and data package transmission times plea...

  • Page 253

    Edr-3000 im02602003e selection of timezone and synchronisation protocol the protection relay masters both utc and local time. This means that the device can be synchronised with utc time while using local time for user display. Time synchronisation with utc time (recommended): time synchronisation i...

  • Page 254

    Edr-3000 im02602003e global protection parameters of the time synchronization parameter description setting range default menu path dst offset difference to wintertime -180 - 180min 60min [device para /time /timezone] dst manual manual setting of the daylight saving time inactive, active active [dev...

  • Page 255

    Edr-3000 im02602003e parameter description setting range default menu path summertime w place of selected day in month (for clock change summertime) only available if: dst manual = active first, second, third, fourth, last last [device para /time /timezone] summertime h hour of clock change summerti...

  • Page 256

    Edr-3000 im02602003e parameter description setting range default menu path wintertime h hour of clock change wintertime only available if: dst manual = active 0 - 23h 3h [device para /time /timezone] wintertime min minute of clock change wintertime only available if: dst manual = active 0 - 59min 0m...

  • Page 257

    Edr-3000 im02602003e parameter description setting range default menu path time zones time zones utc+14 kiritimati, utc+13 rawaki, utc+12.75 chatham island, utc+12 wellington, utc+11.5 kingston, utc+11 port vila, utc+10.5 lord howe island, utc+10 sydney, utc+9.5 adelaide, utc+9 tokyo, utc+8 hong kon...

  • Page 258

    Edr-3000 im02602003e parameter description setting range default menu path timesync time synchronization -, irig-b, sntp, modbus - [device para /time /timesync /timesync] www.Eaton.Com 246.

  • Page 259

    Edr-3000 im02602003e sntp sntp important pre-condition: the device needs to have access to an sntp server via the connected network. This server preferably should be installed locally. Principle – general use sntp is a standard protocol for time synchronization via a network. At minimum, one sntp se...

  • Page 260

    Edr-3000 im02602003e accuracy the accuracy of the sntp server used and the accuracy of its reference clock influences the accuracy of the protection relay's clock. With each transmitted time information, the sntp server sends information about its accuracy: stratum: the stratum gives information on ...

  • Page 261

    Edr-3000 im02602003e fault analysis if there is no sntp signal for more than 120 seconds., the sntp status changes from “active” to “inactive” and an entry in the event recorder will be set. The sntp functionality can be checked in the [operation/status display/time sync./sntp] menu. If the sntp sta...

  • Page 262

    Edr-3000 im02602003e device planning parameters of the sntp parameter description options default menu path mode mode do not use, use use [device planning] direct commands of the sntp parameter description setting range default menu path res counter reset all counters. Inactive, active inactive [ope...

  • Page 263

    Edr-3000 im02602003e parameter description setting range default menu path ip byte4 ip1.Ip2.Ip3.Ip4 0 - 255 0 [device para /time /timesync /sntp] server2 server 2 inactive, active inactive [device para /time /timesync /sntp] ip byte1 ip1.Ip2.Ip3.Ip4 0 - 255 0 [device para /time /timesync /sntp] ip b...

  • Page 264

    Edr-3000 im02602003e signals of the sntp signal description sntp active signal: if there is no valid sntp signal for 120 sec, sntp is regarded as inactive. Sntp counters value description default size menu path noofsyncs total number of synchronizations. 0 0 - 9999999999 [operation /count and revdat...

  • Page 265

    Edr-3000 im02602003e value description default size menu path noofhighoffs service counter: total number of high offsets. 0 0 - 9999999999 [operation /count and revdata /timesync /sntp] noofinttimeouts service counter: total number of internal timeouts. 0 0 - 9999999999 [operation /count and revdata...

  • Page 266

    Edr-3000 im02602003e value description default size menu path netconn quality of network connection (good, sufficient, bad). - good, sufficent, bad, - [operation /status display /timesync /sntp] www.Eaton.Com 254.

  • Page 267

    Edr-3000 im02602003e irig-b00x irig-b requirement: an irig-b00x time code generator is needed. Irig-b004 and higher will support/transmit the “year information”. If you are using an irig time code that does not support the “year information” (irig-b000, irig-b001, irig-b002, irig-b003), you have to ...

  • Page 268

    Edr-3000 im02602003e irig-b commissioning activate the irig-b synchronization within menu [device para/ time/ timesync]: select » irig-b« in the time synchronisation menu. Set the time synchronization in the irig-b menu to » active« . Select the irig-b type (choose b000 through b007). Fault analysis...

  • Page 269

    Edr-3000 im02602003e device planning parameters of the irig-b00x parameter description options default menu path mode mode do not use, use use [device planning] direct commands of the irig-b00x parameter description setting range default menu path res irig-b cr resetting of the diagnosis counters: i...

  • Page 270

    Edr-3000 im02602003e signals of the irig-b00x (output states) signal description active signal: active inverted signal: irig-b inverted control signal1 signal: irig-b control signal control signal2 signal: irig-b control signal control signal4 signal: irig-b control signal control signal5 signal: ir...

  • Page 271

    Edr-3000 im02602003e value description default size menu path edges edges 0 0 - 65535 [operation /count and revdata /timesync /irig-b] www.Eaton.Com 259.

  • Page 272

    Edr-3000 im02602003e device parameters sys date and time in the »device parameters/date/time« menu, the user can set the date and time. The user cannot set time and date manually (manual changes will be ignored), if the clock of the protective device is synchronized automatically (e.G. Via irig- b o...

  • Page 273

    Edr-3000 im02602003e tcp/ip settings warning: mixing up ip addresses (in case there is more than one protective device within the tcp/ip network or establishing an unintentional wrong connection to a protective device based on a wrong entered ip address. Transferring parameters into the wrong protec...

  • Page 274

    Edr-3000 im02602003e direct commands of the system module parameter description setting range default menu path ack ro led comm tcmd reset the relay outputs, leds, communication, and the trip command. Inactive, active inactive [operation /reset] ack led all acknowledgeable leds will be acknowledged....

  • Page 275

    Edr-3000 im02602003e global protection parameters of the system parameter description setting range default menu path pset-switch switching parameter set ps1, ps2, ps3, ps4, pss via inp fct, pss via comm pss via inp fct [protection para /pset-switch] ps1: activated by this setting group will be the ...

  • Page 276

    Edr-3000 im02602003e parameter description setting range default menu path remote reset enables or disables the option to acknowledge from external/remote via signals (assignments) and communication. Inactive, active active [device para /ex acknowledge] ack led all acknowledgeable leds will be ackno...

  • Page 277

    Edr-3000 im02602003e system module input states name description assignment via ack led-i module input state: leds acknowledgment by digital input. [device para /ex acknowledge] ack ro-i module input state: acknowledgment of the relay outputs. [device para /ex acknowledge] ack comm-i module input st...

  • Page 278

    Edr-3000 im02602003e signal description maint mode active signal: arc flash reduction maintenance active maint mode inactive signal: arc flash reduction maintenance inactive maintmode manually signal: arc flash reduction maintenance manual mode maint mode comm signal: arc flash reduction maintenance...

  • Page 279

    Edr-3000 im02602003e special values of the system module value description menu path build build [device para /version] version version [device para /version] operating hours cr operating hours counter of the protective device [operation /count and revdata /sys] www.Eaton.Com 267.

  • Page 280

    Edr-3000 im02602003e communication protocols modbus ® modbus modbus ® protocol configuration the time-controlled modbus ® protocol is based on the master-slave working principle. This means that the substation control and protection system sends an inquiry or instruction to a certain device (slave a...

  • Page 281

    Edr-3000 im02602003e modbus rtu part 1: configuration of the devices call up »device parameter/modbus« and set the following communication parameters: slave address, to allow clear identification of the device; and baud rate. Also, select the rs485 interface-related parameters such as: number of dat...

  • Page 282

    Edr-3000 im02602003e modbus tcp establishing a connection via tcp/ip to the device is only possible if the device is equipped with an ethernet interface (rj45). Contact your it administrator in order to establish the network connection. Part 1: setting the tcp/ip parameters call up »device parameter...

  • Page 283

    Edr-3000 im02602003e direct commands of the modbus ® parameter description setting range default menu path res diagn cr all modbus diagnosis counters will be reset. Inactive, active inactive [operation /reset] global protection parameters of the modbus ® parameter description setting range default m...

  • Page 284

    Edr-3000 im02602003e parameter description setting range default menu path physical settings digit 1: number of bits. Digit 2: e=even parity, o=odd parity, n=no parity. Digit 3: number of stop bits. More information on the parity: it is possible that the last data bit is followed by a parity bit whi...

  • Page 285

    Edr-3000 im02602003e modbus ® module signals (output states) some signals (that are active for a short time only) have to be acknowledged separately (e.G.: trip signals) by the communication system. Signal description transmission signal: communication active comm cmd 1 communication command comm cm...

  • Page 286

    Edr-3000 im02602003e modbus ® module values value description default size menu path noofrequeststotal total number of requests. Includes requests for other slaves. 0 0 - 9999999999 [operation /count and revdata /modbus] noofrequestsforme total number of requests for this slave. 0 0 - 9999999999 [op...

  • Page 287

    Edr-3000 im02602003e iec 61850 iec61850 introduction to understand the functioning and mode of operation of a substation in an iec 61850 automation environment, it is useful to compare the commissioning steps with those of a conventional substation in a modbus tcp environment. In a conventional subs...

  • Page 288

    Edr-3000 im02602003e commissioning steps for a conventional substation with modbus tcp environment: • parameter setting of the ieds; • ethernet installation; • tcp/ip settings for the ieds; and • wiring according to wiring scheme. Commissioning steps for a substation with iec 61850 environment: 1. P...

  • Page 289

    Edr-3000 im02602003e generation/export of a device specific icd file each eaton iec 61850 capable device includes a description of its own functionality and communications skills in the form of an ied capability description (*.Icd) file. This file can be exported as follows and be used for the confi...

  • Page 290

    Edr-3000 im02602003e import of the *.Scd file into the device when the substation configuration is completed, the *.Scd file has to be transmitted to all connected devices. This has to be done as follows: 1. Connect the device with your pc/notebook. 2. Start powerport e. 3. Click on » receive data f...

  • Page 291

    Edr-3000 im02602003e device planning parameters of the iec 61850 parameter description options default menu path mode mode do not use, use use [device planning] www.Eaton.Com 279.

  • Page 292

    Edr-3000 im02602003e direct commands of the iec 61850 parameter description setting range default menu path resetstatistic reset of all iec61850 diagnostic counters inactive, active inactive [operation /reset] global protection parameters of the iec 61850 parameter description setting range default ...

  • Page 293

    Edr-3000 im02602003e parameter description setting range default menu path virtualoutput7 virtual output. This signal can be assigned or visualized via the scd file to other devices within the iec61850 substation. 1..N, assignment list -.- [device para /iec61850] virtualoutput8 virtual output. This ...

  • Page 294

    Edr-3000 im02602003e parameter description setting range default menu path virtualoutput17 virtual output. This signal can be assigned or visualized via the scd file to other devices within the iec61850 substation. 1..N, assignment list -.- [device para /iec61850] virtualoutput18 virtual output. Thi...

  • Page 295

    Edr-3000 im02602003e parameter description setting range default menu path virtualoutput27 virtual output. This signal can be assigned or visualized via the scd file to other devices within the iec61850 substation. 1..N, assignment list -.- [device para /iec61850] virtualoutput28 virtual output. Thi...

  • Page 296

    Edr-3000 im02602003e states of the inputs of the iec 61850 name description assignment via virtout1-i module input state: binary state of the virtual output (ggio) [device para /iec61850] virtout2-i module input state: binary state of the virtual output (ggio) [device para /iec61850] virtout3-i modu...

  • Page 297

    Edr-3000 im02602003e name description assignment via virtout18-i module input state: binary state of the virtual output (ggio) [device para /iec61850] virtout19-i module input state: binary state of the virtual output (ggio) [device para /iec61850] virtout20-i module input state: binary state of the...

  • Page 298

    Edr-3000 im02602003e iec 61850 module signals (output states) signal description virtinp1 signal: virtual input (iec61850 ggio ind) virtinp2 signal: virtual input (iec61850 ggio ind) virtinp3 signal: virtual input (iec61850 ggio ind) virtinp4 signal: virtual input (iec61850 ggio ind) virtinp5 signal...

  • Page 299

    Edr-3000 im02602003e iec 61850 module values value description default size menu path noofgooserxall total number of received goose messages including messages for other devices (subscribed and not subscribed messages). 0 0 - 9999999999 [operation /count and revdata /iec61850] noofgooserxsubscr ibed...

  • Page 300

    Edr-3000 im02602003e value description default size menu path noofdatawrittencorr ect total number of correctly written values by this device. 0 0 - 9999999999 [operation /count and revdata /iec61850] noofdatachangenot ification number of detected changes within the datasets that are published with ...

  • Page 301

    Edr-3000 im02602003e values of the iec 61850 value description default size menu path goosepublisherstate state of the goose publisher (on or off) off off, on, error [operation /status display /iec61850] goosesubscriberstat e state of the goose subscriber (on or off) off off, on, error [operation /s...

  • Page 302

    Edr-3000 im02602003e parameters parameter setting and planning can be done: directly at the device; or by way of the powerport-e software application. Parameter definitions device parameters device parameters are part of the “device parameter tree”. By modifying the device parameters, the user may (...

  • Page 303

    Edr-3000 im02602003e system parameters system parameters are part of the “device parameter tree”. System parameters comprise the essential, basic settings of your switchboard such as rated frequency and transformer ratios. Protection parameters please note that by deactivating, for example protectiv...

  • Page 304

    Edr-3000 im02602003e device planning parameters device planning parameters are part of the “device parameter tree”. Improving the usability (clarity): all protection modules that are currently unused can be hidden (switched to invisible) through device planning. In the device planning menu, the user...

  • Page 305

    Edr-3000 im02602003e adaptive parameter sets www.Eaton.Com 293 ps et-s witc h ad ap ts et p ro te ct io n p ar a p ar am e te r s et 4 a ct iv e/ in ac tiv e a ct iv e / in a ct iv e a ct iv e/ in a ct iv e a ct iv e/ in a ct iv e a ct iv e /in a ct iv e p ar am e te r s et 3 a ct iv e/ in ac tiv e ...

  • Page 306

    Edr-3000 im02602003e adaptive parameter sets are part of the “device parameter tree”. By means of adaptive parameter sets , the user can temporarily modify single parameters within the parameter setting groups. Adaptive parameters drop-out automatically if the acknowledged signal that has activated ...

  • Page 307

    Edr-3000 im02602003e adaptive parameter set activation signals name description -.- no assignment sotf.Enabled signal: switch onto fault enabled. This signal can be used to modify overcurrent protection settings. Clpu.Enabled signal: cold load enabled ar.Running signal: auto reclosing running ar.Pre...

  • Page 308

    Edr-3000 im02602003e name description logic.Le4.Gate out signal: output of the logic gate logic.Le4.Timer out signal: timer output logic.Le4.Out signal: latched output (q) logic.Le4.Out inverted signal: negated latched output (q not) logic.Le5.Gate out signal: output of the logic gate logic.Le5.Time...

  • Page 309

    Edr-3000 im02602003e name description logic.Le13.Timer out signal: timer output logic.Le13.Out signal: latched output (q) logic.Le13.Out inverted signal: negated latched output (q not) logic.Le14.Gate out signal: output of the logic gate logic.Le14.Timer out signal: timer output logic.Le14.Out signa...

  • Page 310

    Edr-3000 im02602003e name description logic.Le22.Out signal: latched output (q) logic.Le22.Out inverted signal: negated latched output (q not) logic.Le23.Gate out signal: output of the logic gate logic.Le23.Timer out signal: timer output logic.Le23.Out signal: latched output (q) logic.Le23.Out inver...

  • Page 311

    Edr-3000 im02602003e name description logic.Le31.Out inverted signal: negated latched output (q not) logic.Le32.Gate out signal: output of the logic gate logic.Le32.Timer out signal: timer output logic.Le32.Out signal: latched output (q) logic.Le32.Out inverted signal: negated latched output (q not)...

  • Page 312

    Edr-3000 im02602003e name description logic.Le41.Gate out signal: output of the logic gate logic.Le41.Timer out signal: timer output logic.Le41.Out signal: latched output (q) logic.Le41.Out inverted signal: negated latched output (q not) logic.Le42.Gate out signal: output of the logic gate logic.Le4...

  • Page 313

    Edr-3000 im02602003e name description logic.Le50.Timer out signal: timer output logic.Le50.Out signal: latched output (q) logic.Le50.Out inverted signal: negated latched output (q not) logic.Le51.Gate out signal: output of the logic gate logic.Le51.Timer out signal: timer output logic.Le51.Out signa...

  • Page 314

    Edr-3000 im02602003e name description logic.Le59.Out signal: latched output (q) logic.Le59.Out inverted signal: negated latched output (q not) logic.Le60.Gate out signal: output of the logic gate logic.Le60.Timer out signal: timer output logic.Le60.Out signal: latched output (q) logic.Le60.Out inver...

  • Page 315

    Edr-3000 im02602003e name description logic.Le68.Out inverted signal: negated latched output (q not) logic.Le69.Gate out signal: output of the logic gate logic.Le69.Timer out signal: timer output logic.Le69.Out signal: latched output (q) logic.Le69.Out inverted signal: negated latched output (q not)...

  • Page 316

    Edr-3000 im02602003e name description logic.Le78.Gate out signal: output of the logic gate logic.Le78.Timer out signal: timer output logic.Le78.Out signal: latched output (q) logic.Le78.Out inverted signal: negated latched output (q not) logic.Le79.Gate out signal: output of the logic gate logic.Le7...

  • Page 317

    Edr-3000 im02602003e access authorizations (access areas) passwords – areas the following table shows the access areas and the authorization passwords that they require in order to access them. Area symbol authorization password access to: read only-lv0 level 0 provides read only access to all setti...

  • Page 318

    Edr-3000 im02602003e if the device was not active within the parameter setting mode for a longer time (can be set between 20 – 3600 seconds) it changes into »read only-lv0« mode automatically. This parameter (t-max-edit) can be modified within menu [device para\hmi]. Access areas (password level): y...

  • Page 319

    Edr-3000 im02602003e during setting parameters the c-button will be used for the cancelling of parameter changes. Because of that it is not possible, to acknowledge (leds, output relays...) as long as there are non saved (cached only) parameters. Acknowledgement can only be executed, when the upper ...

  • Page 320

    Edr-3000 im02602003e available levels/access authorizations the access authorizations are designed in form of two hierachic strings. The supervisor (administrator) password provides access to all parameters and settings. Www.Eaton.Com 308 supervisor-lv3 device configuration read only-lv0 read only p...

  • Page 321

    Edr-3000 im02602003e how to find out what access areas/levels are unlocked? The menu [device para\access levels] provides the information, which access areas (authorizations) are currently unlocked. As soon as there is an unlocked access area (authorization) above »read only-lv0« , this will be indi...

  • Page 322

    Edr-3000 im02602003e changing passwords passwords can be changed at the device in menu [device para/passwords] or by means of the power-port-e software. A password must be a user-defined combination of the numerics 1, 2, 3 and 4. All other characters and keys won´t be accepted. When you want to chan...

  • Page 323

    Edr-3000 im02602003e adaptive parameters via hmi the use of adaptive parameters via the hmi (panel) differs a bit to the use via powerport-e. Adaptive parameters can be also used via the hmi (instead of using the recommended powerport-e ). The principle method of using them via the hmi is as follows...

  • Page 324

    Edr-3000 im02602003e application example during a “switch-onto-fault” condition, the user is usually requested to make the embedded protective function tripping of the faulted line faster, instantaneous, or sometimes non-directional. Such a “switch-onto-fault” application can easily be realized usin...

  • Page 325

    Edr-3000 im02602003e the screen shot above shows the adaptive setting configurations following applications based on only one simple overcurrent protection element: 1. Standard set: default settings; 2. Adaptive set 1: sotf application (switch-onto-fault); 3. Adaptive set 2: clpu application (cold l...

  • Page 326

    Edr-3000 im02602003e access authorizations (access areas) passwords – areas the following table shows the access areas and the authorization passwords that they require in order to access them. Area symbol authorization password access to: read only-lv0 level 0 provides read only access to all setti...

  • Page 327

    Edr-3000 im02602003e if the device was not active within the parameter setting mode for a longer time (can be set between 20 – 3600 seconds) it changes into »read only-lv0« mode automatically. This parameter (t-max-edit) can be modified within menu [device para\hmi]. Www.Eaton.Com 315.

  • Page 328

    Edr-3000 im02602003e access areas (password level): you have to ensure, that the access authorizations are protected by secure passwords. These passwords have to be kept as a secret and to be known only by the authorized persons. A lock symbol indicates in the upper right corner of the display if th...

  • Page 329

    Edr-3000 im02602003e the passwords are part of the device (fixed assignments). That means, passwords will not be overwritten, if a parameter file is transmitted into a device. Existing passwords are persistent (assined to a device). If an offline created parameter file is transmitted into a device, ...

  • Page 330

    Edr-3000 im02602003e available levels/access authorizations the access authorizations are designed in form of two hierachic strings. The supervisor (administrator) password provides access to all parameters and settings. How to find out what access areas/levels are unlocked? The menu [device para\ac...

  • Page 331

    Edr-3000 im02602003e unlocking access areas within the menu [device para\access level] access areas can be unlocked or locked (at the hmi). Changing passwords passwords can be changed at the device in menu [device para/passwords] or by means of the power-port-e s oftware. A password must be a user-d...

  • Page 332

    Edr-3000 im02602003e changing passwords via power-port-e download the parameter file from the device. Passwords can be changed by a double-click within menu [device para\password\change password] on the corresponding password. Enter the old password and the new password twice confirm the changes by ...

  • Page 333

    Edr-3000 im02602003e parameter setting at the hmi every parameter belongs to an access area. Editing and changing of a parameter requires a sufficient access authorization. The user can obtain the required access authorizations by unlocking access areas in advance of parameter changes or context-dep...

  • Page 334

    Edr-3000 im02602003e in addition to the star trace to the temporary saved parameter changes, a general parameter changing symbol is faded-in at the left corner of the display, and so it is possible from each point of the menu tree to see that there are parameter changes still not adopted by the devi...

  • Page 335

    Edr-3000 im02602003e option 2: context-dependent access authorization navigate to the parameter, that is to be changed. If the parameter is selected, the lower right corner of the display shows a » key« -symbol. This symbol indicates, that the device is still within the »read only lv0« -level, or th...

  • Page 336

    Edr-3000 im02602003e plausibility check: in order to prevent obvious wrong settings the device monitors constantly all temporary saved parameter changes. If the device detects an implausibility, this is indicated by a question mark in front of the respective parameter. In order to make things easier...

  • Page 337

    Edr-3000 im02602003e parameter setting via power-port-e power-port-e shows within the windows, where parameters are edited also the required access level for the parameters and settings. The required access authorizations will be verified when the parameter file should be transferred into the protec...

  • Page 338

    Edr-3000 im02602003e close this window by clicking the »ok« key. A star symbol in front of the changed parameters indicates that the alterations have only been saved temporarily. They are not yet finally stored and adopted by the software/device. In order to make things easier to follow, especially ...

  • Page 339

    Edr-3000 im02602003e additional parameters can be changed if required. There are two options available to transfer changed parameters into the device within menu »device«. 1. »transfer all parameters into the device« . This always requires the supervisor (administrator) password. 2. »transfer only m...

  • Page 340

    Edr-3000 im02602003e setting groups setting group switch within the »protection para/p-set switch« menu, the user has the following possibilities: to manually set one of the four setting groups active; to assign a signal to each setting group that sets this group to active; and scada switches the se...

  • Page 341

    Edr-3000 im02602003e signals that can be used for pss name description -.- no assignment di-4p x1.Di 1 signal: digital input di-4p x1.Di 2 signal: digital input di-4p x1.Di 3 signal: digital input di-4p x1.Di 4 signal: digital input di-8p x1.Di 1 signal: digital input di-8p x1.Di 2 signal: digital i...

  • Page 342

    Edr-3000 im02602003e name description logic.Le6.Out signal: latched output (q) logic.Le6.Out inverted signal: negated latched output (q not) logic.Le7.Gate out signal: output of the logic gate logic.Le7.Timer out signal: timer output logic.Le7.Out signal: latched output (q) logic.Le7.Out inverted si...

  • Page 343

    Edr-3000 im02602003e name description logic.Le15.Out inverted signal: negated latched output (q not) logic.Le16.Gate out signal: output of the logic gate logic.Le16.Timer out signal: timer output logic.Le16.Out signal: latched output (q) logic.Le16.Out inverted signal: negated latched output (q not)...

  • Page 344

    Edr-3000 im02602003e name description logic.Le25.Gate out signal: output of the logic gate logic.Le25.Timer out signal: timer output logic.Le25.Out signal: latched output (q) logic.Le25.Out inverted signal: negated latched output (q not) logic.Le26.Gate out signal: output of the logic gate logic.Le2...

  • Page 345

    Edr-3000 im02602003e name description logic.Le34.Timer out signal: timer output logic.Le34.Out signal: latched output (q) logic.Le34.Out inverted signal: negated latched output (q not) logic.Le35.Gate out signal: output of the logic gate logic.Le35.Timer out signal: timer output logic.Le35.Out signa...

  • Page 346

    Edr-3000 im02602003e name description logic.Le43.Out signal: latched output (q) logic.Le43.Out inverted signal: negated latched output (q not) logic.Le44.Gate out signal: output of the logic gate logic.Le44.Timer out signal: timer output logic.Le44.Out signal: latched output (q) logic.Le44.Out inver...

  • Page 347

    Edr-3000 im02602003e name description logic.Le52.Out inverted signal: negated latched output (q not) logic.Le53.Gate out signal: output of the logic gate logic.Le53.Timer out signal: timer output logic.Le53.Out signal: latched output (q) logic.Le53.Out inverted signal: negated latched output (q not)...

  • Page 348

    Edr-3000 im02602003e name description logic.Le62.Gate out signal: output of the logic gate logic.Le62.Timer out signal: timer output logic.Le62.Out signal: latched output (q) logic.Le62.Out inverted signal: negated latched output (q not) logic.Le63.Gate out signal: output of the logic gate logic.Le6...

  • Page 349

    Edr-3000 im02602003e name description logic.Le71.Timer out signal: timer output logic.Le71.Out signal: latched output (q) logic.Le71.Out inverted signal: negated latched output (q not) logic.Le72.Gate out signal: output of the logic gate logic.Le72.Timer out signal: timer output logic.Le72.Out signa...

  • Page 350

    Edr-3000 im02602003e name description logic.Le80.Out signal: latched output (q) logic.Le80.Out inverted signal: negated latched output (q not) sys.Maint mode active signal: arc flash reduction maintenance active sys.Maint mode inactive signal: arc flash reduction maintenance inactive www.Eaton.Com 3...

  • Page 351

    Edr-3000 im02602003e setting group switch via powerport-e if powerport-e is not running, please start the application. If the device data have not been loaded, click »receive data from the device« in the »device« menu. Double click the »protection para« icon in the navigation tree. Double click the ...

  • Page 352

    Edr-3000 im02602003e copying setting groups (parameter sets) via powerport-e setting groups can only be copied if there are no conflicts (no red question marks). For applications using multiple settings groups, one can use the configuration file from the first group to create the second group. With ...

  • Page 353

    Edr-3000 im02602003e comparing parameter files via powerport-e with the help of powerport-e, the user can simply compare/differentiate the currently open parameter/device file against a file on the hard disk. The precondition is that the versions and type of devices match. To compare the parameter f...

  • Page 354

    Edr-3000 im02602003e converting parameter files via powerport-e parameter files of the same type can be converted. During this process, the new parameter file will keep all active settings from the source parameter file and, at the same time, remove all inactive settings. As many parameters as possi...

  • Page 355

    Edr-3000 im02602003e program mode by means of the program mode , parameter settings can be locked against any changes as long as one or all of the breaker(s) are in the » closed« position. The program mode can be activated within the [system para/general settings/program mode bypass] menu. »both bkr...

  • Page 356

    Edr-3000 im02602003e system parameters system para within the system parameters, the user can set all parameters that are relevant for the primary side and the mains operational method like frequency, primary and secondary values, and the star point treatment. General system parameters parameter des...

  • Page 357

    Edr-3000 im02602003e system parameters – current related parameter description setting range default menu path ct con current transformer connection 3-wire, 4th ct in, 4th ct ig 3-wire [system para /general settings] ct pri nominal current of the primary side of the current transformers. 1 - 50000a ...

  • Page 358

    Edr-3000 im02602003e blocking the device provides a function for temporary blocking of the complete protection functionality or of single protections. Make absolutely sure that no illogical or even life-threatening blockings are allocated. Make sure not to carelessly deactivate protection functions ...

  • Page 359

    Edr-3000 im02602003e to block a complete protection module temporarily by an active assignment in order to establish a temporary blockage of a protection module, the parameter »exblo fc« of the module has to be set to »active« . This gives the permission: »this module can be blocked«. Within the gen...

  • Page 360

    Edr-3000 im02602003e to activate or deactivate the tripping command of a protection module www.Eaton.Com 348 in ac tiv e ac tiv e n am e. B lo t rip c m d in ac tiv e ac tiv e n am e. Ex bl o tr ip c m d fc 1. .N , a ss ig nm en t l is t na m e. Ex bl o tr ip c m d n am e. E xb lo t rip c m d tr ip ...

  • Page 361

    Edr-3000 im02602003e activate, deactivate respectively to block temporary protection functions www.Eaton.Com 349 an d in ac tiv e ac tiv e n am e. Fu nc tio n in ac tiv e ac tiv e n am e. Ex bl o fc n am e. A ct iv e pr ot . A ct iv e 1. .N , a ss ig nm en t l is t n am e. Ex bl o 1 n am e. E xb lo ...

  • Page 362

    Edr-3000 im02602003e current protective functions cannot only be blocked permanently ( »f unction = inactive« ) or temporarily by any blocking signal from the »assignment list«, but also by »reverse interlocking« . All other protection functions can be activated, deactivated, or blocked in the same ...

  • Page 363

    Edr-3000 im02602003e protection (prot) module prot the »protection« module serves as the outer frame for all other protection modules (i.E.: they are all enclosed by the »protection« module). In the case where the »protection« module is blocked, the complete protective function of the device is disa...

  • Page 364

    Edr-3000 im02602003e www.Eaton.Com 352 an d in ac tiv e ac tiv e pr ot .E xb lo f c pr ot .Ac tiv e 1. .N , a ss ig nm en t l is t pr ot .E xb lo 1 p ro t.Ex bl o p ro t - a ct iv e 1. .N , a ss ig nm en t l is t pr ot .E xb lo 2 pr ot .Ex b lo 1- i pr ot .Ex b lo 2- i an d p ro t.A va ila bl e m ea...

  • Page 365

    Edr-3000 im02602003e each protection element generates its own pickup and trip signals, which are automatically passed onto the »prot« module where the phase based and general (collective) pickup and trip signals are generated. The »prot« module serves as a top level and a common place to group all ...

  • Page 366

    Edr-3000 im02602003e www.Eaton.Com 354 p ro t.T rip n am e. Tr ip n am e = e ach tr ip o f a n ac tiv e, tr ip a ut ho riz ed p ro te ct io n m od ul e w ill le ad to a g en er al tr ip . N am e. Tr ip p ro t.T rip n am e[ n] .T rip ... 15 15 15 o r.

  • Page 367

    Edr-3000 im02602003e www.Eaton.Com 355 pr ot .P ic ku p p ro t.P ic ku p n am e. Pi ck up n am e. Pi ck up n am e. Pi ck up n am e = e ac h pi ck up o f a m od ul e (e xc ep t f ro m s up er vi si on m od ul es b ut in cl ud in g b f) w ill le ad to a g en er al p ic ku p (c ol le ct iv e pi ck up )...

  • Page 368

    Edr-3000 im02602003e www.Eaton.Com 356 50 r[ 1] ... [n ].T rip * 59 [n ].T rip cm d* p ro t.T rip ix o r i r 51 r [1 ].. .[n ].T rip * pr ot .T rip e a ch p h a se s e le ct iv e tr ip o f a t ri p a u th o riz e d m o d u le ( i, i g , v , v x d e p e n d in g o n t h e d e vi ce t yp e) w ill le a...

  • Page 369

    Edr-3000 im02602003e www.Eaton.Com 357 50 r[ 1] ... [n ].P ic ku p* 59 [n ].P ic ku p* p ro t.P ic ku p ix o r i r 51 r[ 1] ... [n ].P ic ku p* p ro t.P ic ku p e ac h p ha se s e le ct iv e p ic ku p o f a m od ul e ( i, ig , v , v x d ep e nd in g o n th e de vi ce t yp e) w ill le a d to a p h as...

  • Page 370

    Edr-3000 im02602003e direct commands of the protection module parameter description setting range default menu path res fault a mains no resetting of fault number and number of grid faults. Inactive, active inactive [operation /reset] global protection parameters of the protection module parameter d...

  • Page 371

    Edr-3000 im02602003e protection module input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /prot] exblo2-i module input state: external blocking2 [protection para /global prot para /prot] protection module signals (output st...

  • Page 372

    Edr-3000 im02602003e values of the protection module parameter description faultno waveform no. No of grid faults number of grid faults: a grid fault, e.G. A short circuit, might cause several faults with trip and autoreclosing, each fault being identified by an increased fault number. In this case,...

  • Page 373

    Edr-3000 im02602003e switchgear/breaker - manager bkr warning: misconfiguration of the breaker could result in death or serious injury. Breaker configuration for the configuration of the breaker, great attention has to be payed to the following steps: • wiring • switching authority • pos indicators ...

  • Page 374

    Edr-3000 im02602003e switching authority for the switching authority [control\general settings], the following general settings are possible: none: no switching authority (switching not allowed); local: switching only via push buttons at the panel; remote: switching only via scada, digital inputs, o...

  • Page 375

    Edr-3000 im02602003e single line diagram the single line diagram includes the graphically description of the switchgear and its designation (name) as well as its features (short circuit proof or not ...). For displaying in the devices software, the switchgear' designations (e. G. Qa1, qa2, instead o...

  • Page 376

    Edr-3000 im02602003e pos indicators wiring in the menu [control/breaker/pos indicators wiring], the signals for the switchgear status indication (position and ready) are to be assigned. Position indication with two contacts - 52a and 52b (recommended) to identify the current position of the switchge...

  • Page 377

    Edr-3000 im02602003e the following table shows how breaker positions are validated based on 52a and 52b: states of the digital inputs validated breaker positions cinbkr52a-i cinbkr52b-i pos close pos open pos indeterm pos disturb breaker state 0 0 0 0 1 (while a moving timer is running) 0 (while a m...

  • Page 378

    Edr-3000 im02602003e if for any reason only one breaker contact (52a or 52b) is wired, the single contact indication can be used. Single contact indication the moving time supervision works only in one direction. If the 52a signal is connected to the device, only the “close command” can be supervise...

  • Page 379

    Edr-3000 im02602003e single contact indication – 52b only if only the 52b signal is used for the monitoring of the “open command”, the switch command will start the moving timer. The position indication will indicate an intermediate position. If the moving time elapsed before the switchgear has reac...

  • Page 380

    Edr-3000 im02602003e general settings in the menu [control/breaker/general settings], the moving times for opening and closing of the breaker can be set. Trip manager in the trip manger all tripping commands are combined by an “or” logic. The actual tripping command to the breaker is exclusively giv...

  • Page 381

    Edr-3000 im02602003e www.Eaton.Com 369 signal breaker close signal breaker open signal breaker ready trigger [x] trigger [x] trigger [x] b re a ke r breaker open command breaker close command protection trip command position indication: open, close, indeterminated, disturbed trip command 50p[x] trip...

  • Page 382

    Edr-3000 im02602003e www.Eaton.Com 370 b kr .T rip b kr bk r.T rip c m d n am e. Tr ip c m d 1 bk r.T -t rip cm d t . . . . Ac tiv e in ac tiv e bk r.L at ch ed + r tr ip c m d cr bk r.R es t rip c m dc r n am e. Tr ip c m d n am e. Tr ip c m d n am e. Tr ip c m d n am e. Tr ip c m d ac kn ow le dg ...

  • Page 383

    Edr-3000 im02602003e interlockings there are three interlocking inputs for each switching direction (open/close) available. Switching into the corresponding switching direction can be inhibited via these inputs. Please note: the protection trip commands and the reclosure command of the auto reclosur...

  • Page 384

    Edr-3000 im02602003e www.Eaton.Com 372 an d sw itc h co m m an d re qu es t v ia d ig ita l i np ut : (m an ua l s w itc h c om m an d) c om m un ic at io n is su es th e fo llo w in g co m m an ds : (m an ua l s w itc h c om m an d) h m i i ss ue s th e fo llo w in g co m m an ds : (m an ua l s w i...

  • Page 385

    Edr-3000 im02602003e ex open/close if the breaker should be opened or closed by an external signal, the user can assign one signal that will trigger the close and one signal that will trigger the open command (e.G.: digital inputs or output signals of the logics). An applied close command will be ov...

  • Page 386

    Edr-3000 im02602003e direct commands of the switchgear/breaker parameter description setting range default menu path res bwear sl breaker resetting the slow breaker alarm inactive, active inactive [operation /reset] ack tripcmd acknowledge trip command inactive, active inactive [operation /reset] ww...

  • Page 387

    Edr-3000 im02602003e global protection parameters of the switchgear/breaker parameter description setting range default menu path cinbkr-52a the breaker is in close-position if the state of the assigned signal is true (52a). 1..N, dig inputs di-4p x1.Di 1 [control /bkr /pos indicatrs wirng] cinbkr-5...

  • Page 388

    Edr-3000 im02602003e parameter description setting range default menu path sc open switching open command, e.G. The state of the logics or the state of the digital input 1..N, di-logiclist -.- [control /bkr /ex open/close cmd] t-tripcmd minimum hold time of the open-command (breaker, load break swit...

  • Page 389

    Edr-3000 im02602003e parameter description setting range default menu path trigger8 open command to the breaker if the state of the assigned signal becomes true. 1..N, trip cmds 50r[2].Tripcmd [control /bkr /trip manager] trigger9 open command to the breaker if the state of the assigned signal becom...

  • Page 390

    Edr-3000 im02602003e parameter description setting range default menu path trigger19 open command to the breaker if the state of the assigned signal becomes true. 1..N, trip cmds -.- [control /bkr /trip manager] trigger20 open command to the breaker if the state of the assigned signal becomes true. ...

  • Page 391

    Edr-3000 im02602003e switchgear/breaker input states name description assignment via cinbkr-52a-i module input state: feed-back signal of the bkr (52a) [control /bkr /pos indicatrs wirng] cinbkr-52b-i module input state: feed-back signal of the bkr. (52b) [control /bkr /pos indicatrs wirng] ready-i ...

  • Page 392

    Edr-3000 im02602003e name description assignment via sc close-i state of the module input: switching close command, e.G. The state of the logics or the state of the digital input [control /bkr /ex open/close cmd] sc open-i state of the module input: switching open command, e.G. The state of the logi...

  • Page 393

    Edr-3000 im02602003e signal description tripcmd signal: trip command ack tripcmd signal: acknowledge trip command bwear slow breaker signal: slow breaker alarm res bwear sl breaker signal: resetting the slow breaker alarm close cmd signal: close command issued to the switchgear. Depending on the set...

  • Page 394

    Edr-3000 im02602003e switching the breaker at the panel manually switching a switchgear at the device panel is possible at the following switching authorities: local local and remote assumed the device displays the main screen: 1. Press the » menu« softkey. 2. Select the » control« menu by using the...

  • Page 395

    Edr-3000 im02602003e direct commands of the switching authority parameter description setting range default menu path switching authority switching authority none, local, remote, local and remote local [control /general settings] signals of the switching authority signal description local switching ...

  • Page 396

    Edr-3000 im02602003e breaker wear the protective relay offers the following breaker wear features: • monitoring of the accumulated interrupted currents. • slow breaker alarm • calculation of the breaker open capacity » bkr open capacity« . 100% means that breaker maintenance is mandatory now. • brea...

  • Page 397

    Edr-3000 im02602003e breaker wear curve in order to keep the breaker in good working condition, the breaker needs to be monitored. The breaker health (operation life) depends above all on: the number of close/open cycles and the amplitudes of the interrupting currents. The user has to maintain the b...

  • Page 398

    Edr-3000 im02602003e global protection parameters of the breaker wear module parameter description setting range default menu path operations alarm service alarm, too many operations 1 - 100000 9999 [control /bkr /bwear] isum intr alarm alarm, the sum (limit) of interrupting currents has been exceed...

  • Page 399

    Edr-3000 im02602003e parameter description setting range default menu path count2 open counts allowed #2 only available if:bwear curve fc = active 1 - 32000 10000 [control /bkr /bwear] current3 interrupted current level #3 only available if:bwear curve fc = active 0.00 - 2000.00ka 1.15ka [control /b...

  • Page 400

    Edr-3000 im02602003e parameter description setting range default menu path current8 interrupted current level #8 only available if:bwear curve fc = active 0.00 - 2000.00ka 16.00ka [control /bkr /bwear] count8 open counts allowed #8 only available if:bwear curve fc = active 1 - 32000 75 [control /bkr...

  • Page 401

    Edr-3000 im02602003e breaker wear signals (output states) signal description operations alarm signal: service alarm, too many operations isum intr trip: ia signal: maximum permissible summation of the interrupting (tripping) currents exceeded: ia isum intr trip: ib signal: maximum permissible summat...

  • Page 402

    Edr-3000 im02602003e breaker wear counter values value description default size menu path tripcmd cr counter: total number of trips of the switchgear (breaker, load break switch…). Resettable with total or all. 0 0 - 200000 [operation /count and revdata /control /bkr] breaker wear values value descr...

  • Page 403

    Edr-3000 im02602003e direct commands of the breaker wear module parameter description setting range default menu path res tripcmdcr resetting of the counter: total number of trip commands inactive, active inactive [operation /reset] res isum trip reset summation of the tripping currents inactive, ac...

  • Page 404

    Edr-3000 im02602003e name description di-8p x1.Di 6 signal: digital input di-8p x1.Di 7 signal: digital input di-8p x1.Di 8 signal: digital input logic.Le1.Gate out signal: output of the logic gate logic.Le1.Timer out signal: timer output logic.Le1.Out signal: latched output (q) logic.Le1.Out invert...

  • Page 405

    Edr-3000 im02602003e name description logic.Le9.Out signal: latched output (q) logic.Le9.Out inverted signal: negated latched output (q not) logic.Le10.Gate out signal: output of the logic gate logic.Le10.Timer out signal: timer output logic.Le10.Out signal: latched output (q) logic.Le10.Out inverte...

  • Page 406

    Edr-3000 im02602003e name description logic.Le18.Out inverted signal: negated latched output (q not) logic.Le19.Gate out signal: output of the logic gate logic.Le19.Timer out signal: timer output logic.Le19.Out signal: latched output (q) logic.Le19.Out inverted signal: negated latched output (q not)...

  • Page 407

    Edr-3000 im02602003e name description logic.Le28.Gate out signal: output of the logic gate logic.Le28.Timer out signal: timer output logic.Le28.Out signal: latched output (q) logic.Le28.Out inverted signal: negated latched output (q not) logic.Le29.Gate out signal: output of the logic gate logic.Le2...

  • Page 408

    Edr-3000 im02602003e name description logic.Le37.Timer out signal: timer output logic.Le37.Out signal: latched output (q) logic.Le37.Out inverted signal: negated latched output (q not) logic.Le38.Gate out signal: output of the logic gate logic.Le38.Timer out signal: timer output logic.Le38.Out signa...

  • Page 409

    Edr-3000 im02602003e name description logic.Le46.Out signal: latched output (q) logic.Le46.Out inverted signal: negated latched output (q not) logic.Le47.Gate out signal: output of the logic gate logic.Le47.Timer out signal: timer output logic.Le47.Out signal: latched output (q) logic.Le47.Out inver...

  • Page 410

    Edr-3000 im02602003e name description logic.Le55.Out inverted signal: negated latched output (q not) logic.Le56.Gate out signal: output of the logic gate logic.Le56.Timer out signal: timer output logic.Le56.Out signal: latched output (q) logic.Le56.Out inverted signal: negated latched output (q not)...

  • Page 411

    Edr-3000 im02602003e name description logic.Le65.Gate out signal: output of the logic gate logic.Le65.Timer out signal: timer output logic.Le65.Out signal: latched output (q) logic.Le65.Out inverted signal: negated latched output (q not) logic.Le66.Gate out signal: output of the logic gate logic.Le6...

  • Page 412

    Edr-3000 im02602003e name description logic.Le74.Timer out signal: timer output logic.Le74.Out signal: latched output (q) logic.Le74.Out inverted signal: negated latched output (q not) logic.Le75.Gate out signal: output of the logic gate logic.Le75.Timer out signal: timer output logic.Le75.Out signa...

  • Page 413

    Edr-3000 im02602003e control - example: switching of a breaker ctrl the following example shows how to switch a breaker via the hmi at the device. Change into the menu »control« by pushing the »right arrow« softkey. Change to the control page by pushing the »right arrow« softkey. Information only: o...

  • Page 414

    Edr-3000 im02602003e pushing the softkey »mode« leads to the menu »general settings«. In this menu the switching authority can be changed. Select between »local« or »local and remote«. Now it is possible to execute switching commands at the hmi. Push the »right arrow« softkey to get to the control p...

  • Page 415

    Edr-3000 im02602003e the switching command will be given to the breaker. The display shows the intermediate position of the switchgear. It will be shown on the display when the switchgear reaches the new end position. Further possible switching operations (open) will be displayed by softkeys. Notice...

  • Page 416

    Edr-3000 im02602003e protective elements 50p - deft overcurrent protection elements 50p[1] ,50p[2] ,50p[3] if using inrush blockings, the tripping delay of the current protection functions must be at least 30 ms or more in order to prevent faulty trippings (applies only to devices which are equipped...

  • Page 417

    Edr-3000 im02602003e www.Eaton.Com 405 50 p[ 1] ... [n ] n am e = 50 p [1 ].. .[n ] fu nd . Rm s na m e. C rit er io n φ n am e. Tr ip c m d n am e. P ic ku p ia n am e. P ic ku p ib n am e. P ic ku p ic n am e. Tr ip ih 2. B lo p ha se a ih 2. Bl o ph as e b ih 2. Bl o ph as e c p le a se r ef er t...

  • Page 418

    Edr-3000 im02602003e device planning parameters of the 50p module parameter description options default menu path mode mode 50p[1]: non-directional 50p[2]: non-directional 50p[3]: do not use, non-directional non-directional [device planning] global protection parameters of the 50p module parameter d...

  • Page 419

    Edr-3000 im02602003e parameter description setting range default menu path adaptset 3 assignment adaptive parameter 3 adaptset -.- [protection para /global prot para /i-prot /50p[1]] adaptset 4 assignment adaptive parameter 4 adaptset -.- [protection para /global prot para /i-prot /50p[1]] www.Eaton...

  • Page 420

    Edr-3000 im02602003e setting group parameters of the 50p module parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active 50p[1]: active 50p[2]: active 50p[3]: inactive [protection para / /i-prot /50p[1]] exblo fc activate...

  • Page 421

    Edr-3000 im02602003e parameter description setting range default menu path t tripping delay only available if: characteristic = deft 0.00 - 300.00s 50p[1]: 0s 50p[2]: 0.25s 50p[3]: 0.25s [protection para / /i-prot /50p[1]] www.Eaton.Com 409.

  • Page 422

    Edr-3000 im02602003e 50p module input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /i-prot /50p[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /i-prot /50p[1]] exblo tripcmd-i module ...

  • Page 423

    Edr-3000 im02602003e 50p module signals (output states) signal description active signal: active exblo signal: external blocking rvs blo signal: reverse blocking blo tripcmd signal: trip command blocked exblo tripcmd signal: external blocking of the trip command pickup ia signal: pickup ia pickup ib...

  • Page 424

    Edr-3000 im02602003e commissioning: overcurrent protection, non-directional [ansi 50p] object to be tested: • signals to be measured for each current protection element: the threshold values, total tripping time (recommended), or alternatively tripping delays and the drop-out ratios; each time 3 x s...

  • Page 425

    Edr-3000 im02602003e 51p - inv overcurrent-protection elements 51p[1] ,51p[2] ,51p[3] if using inrush blockings, the tripping delay of the current protection functions must be at least 30 ms or more in order to prevent faulty trippings (applies only to devices which are equipped with inrush protecti...

  • Page 426

    Edr-3000 im02602003e www.Eaton.Com 414 fu nd . Rm s na m e. C rit er io n φ n am e. P ic ku p ia n am e. P ic ku p ib n am e. P ic ku p ic n am e. Tr ip ih 2. Bl o ph as e a ih 2. Bl o ph as e b ih 2. Bl o ph as e c p le as e r ef er to d ia gr am : b lo ck in gs ** n am e. P ick up ia ib ic an d an...

  • Page 427

    Edr-3000 im02602003e device planning parameters of the 51p module parameter description options default menu path mode mode 51p[1]: non-directional 51p[2]: do not use, non-directional 51p[3]: do not use, non-directional non-directional [device planning] global protection parameters of the 51p module...

  • Page 428

    Edr-3000 im02602003e parameter description setting range default menu path adaptset 3 assignment adaptive parameter 3 adaptset -.- [protection para /global prot para /i-prot /51p[1]] adaptset 4 assignment adaptive parameter 4 adaptset -.- [protection para /global prot para /i-prot /51p[1]] www.Eaton...

  • Page 429

    Edr-3000 im02602003e setting group parameters of the 51p module parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active 51p[1]: active 51p[2]: active 51p[3]: inactive [protection para / /i-prot /51p[1]] exblo fc activate...

  • Page 430

    Edr-3000 im02602003e parameter description setting range default menu path curve shape characteristic iec ninv, iec vinv, iec einv, iec linv, ansi minv, ansi vinv, ansi einv, therm flat, it, i2t, i4t ansi minv [protection para / /i-prot /51p[1]] t-multiplier time multiplier/tripping characteristic f...

  • Page 431

    Edr-3000 im02602003e 51p module input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /i-prot /51p[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /i-prot /51p[1]] exblo tripcmd-i module ...

  • Page 432

    Edr-3000 im02602003e 51p module signals (output states) signal description active signal: active exblo signal: external blocking rvs blo signal: reverse blocking blo tripcmd signal: trip command blocked exblo tripcmd signal: external blocking of the trip command pickup ia signal: pickup ia pickup ib...

  • Page 433

    Edr-3000 im02602003e commissioning: overcurrent protection, non-directional [ansi 51p] object to be tested signals to be measured for each current protection element: the threshold values, total tripping time (recommended), or alternatively tripping delays and the drop-out ratios; each time 3 x sing...

  • Page 434

    Edr-3000 im02602003e 50x deft measured ground fault protection elements 50x[1] ,50x[2] if using inrush blockings, the tripping delay of the ground current protection functions must be at least 30 ms or more in order to prevent faulty trippings. All ground current elements are identically structured....

  • Page 435

    Edr-3000 im02602003e www.Eaton.Com 423 50 x [1 ].. .[n ] n am e = 50 x [1 ].. .[n ] n am e. Tr ip c m d n am e. Tr ip p le as e r ef er to d ia gr am : b lo ck in gs ** n am e. P ic ku p p le as e r ef er to d ia gr am : tr ip b lo ck in gs (e le m en t i s no t d ea ct iva te d an d no a ct ive b l...

  • Page 436

    Edr-3000 im02602003e device planning parameters of the 50x ground fault protection parameter description options default menu path mode mode non-directional non-directional [device planning] global protection parameters of the 50x ground fault protection parameter description setting range default m...

  • Page 437

    Edr-3000 im02602003e parameter description setting range default menu path adaptset 3 assignment adaptive parameter 3 adaptset -.- [protection para /global prot para /i-prot /50x[1]] adaptset 4 assignment adaptive parameter 4 adaptset -.- [protection para /global prot para /i-prot /50x[1]] www.Eaton...

  • Page 438

    Edr-3000 im02602003e setting group parameters of the 50x ground fault protection parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active active [protection para / /i-prot /50x[1]] exblo fc activate (allow) or inactivate ...

  • Page 439

    Edr-3000 im02602003e parameter description setting range default menu path pickup (sensitive) if the pickup value is exceeded, the module/element will be started. 0.002 - 2.000in 0.02in [protection para / /i-prot /50x[1]] t tripping delay only available if: characteristic = deft 0.00 - 300.00s 0.5s ...

  • Page 440

    Edr-3000 im02602003e 50x ground fault protection input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /i-prot /50x[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /i-prot /50x[1]] exblo ...

  • Page 441

    Edr-3000 im02602003e 50x ground fault protection signals (output states) signal description active signal: active exblo signal: external blocking rvs blo signal: reverse blocking blo tripcmd signal: trip command blocked exblo tripcmd signal: external blocking of the trip command pickup signal: picku...

  • Page 442

    Edr-3000 im02602003e commissioning: ground fault protection – non-directional [ansi 50x] please test the non-directional ground overcurrent analog to the non-directional phase overcurrent protection. Www.Eaton.Com 430

  • Page 443

    Edr-3000 im02602003e 51x inv measured ground fault protection elements 51x[1] ,51x[2] all ground current elements are identically structured. For each element the following characteristics are available: • ninv (iec/ xinv ); • vinv (iec/ xinv ); • linv (iec/ xinv ); • einv (iec/ xinv ); • minv (ansi...

  • Page 444

    Edr-3000 im02602003e www.Eaton.Com 432 n am e. Tr ip c m d n am e. Tr ip p le as e r ef er to d ia gr am : b lo ck in gs ** n am e. P ic ku p p le as e r ef er to d ia gr am : tr ip b lo ck in gs (e le m en t i s no t d ea ct iv at ed a nd n o ac tiv e bl oc ki ng s ig na ls ) (t rip pi ng c om m an...

  • Page 445

    Edr-3000 im02602003e device planning parameters of the 51x ground fault protection parameter description options default menu path mode mode 51x[1]: non-directional 51x[2]: do not use, non-directional non-directional [device planning] global protection parameters of the 51x ground fault protection p...

  • Page 446

    Edr-3000 im02602003e parameter description setting range default menu path adaptset 3 assignment adaptive parameter 3 adaptset -.- [protection para /global prot para /i-prot /51x[1]] adaptset 4 assignment adaptive parameter 4 adaptset -.- [protection para /global prot para /i-prot /51x[1]] www.Eaton...

  • Page 447

    Edr-3000 im02602003e setting group parameters of the 51x ground fault protection parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active active [protection para / /i-prot /51x[1]] exblo fc activate (allow) or inactivate ...

  • Page 448

    Edr-3000 im02602003e parameter description setting range default menu path pickup (sensitive) if the pickup value is exceeded, the module/element will be started. 0.002 - 2.000in 0.02in [protection para / /i-prot /51x[1]] curve shape characteristic iec ninv, iec vinv, iec einv, iec linv, ansi minv, ...

  • Page 449

    Edr-3000 im02602003e 51x ground fault protection input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /i-prot /51x[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /i-prot /51x[1]] exblo ...

  • Page 450

    Edr-3000 im02602003e 51x ground fault protection signals (output states) signal description active signal: active exblo signal: external blocking rvs blo signal: reverse blocking blo tripcmd signal: trip command blocked exblo tripcmd signal: external blocking of the trip command pickup signal: picku...

  • Page 451

    Edr-3000 im02602003e commissioning: ground fault protection – non-directional [ansi 51x] please test the non-directional ground overcurrent analog to the non-directional phase overcurrent protection. Www.Eaton.Com 439.

  • Page 452

    Edr-3000 im02602003e 50r deft calculated ground fault protection module elements 50r[1] ,50r[2] if using inrush blockings, the tripping delay of the ground current protection functions must be at least 30 ms or more in order to prevent faulty trippings. All ground current elements are identically st...

  • Page 453

    Edr-3000 im02602003e www.Eaton.Com 441 n am e. Tr ip c m d n am e. Tr ip p le a se re fe r to d ia g ra m : b lo ck in g s* * n am e. Pi ck up p le a se re fe r to d ia g ra m : tr ip b lo ck in gs (e le m en t i s no t d ea ct iv at ed a nd n o ac tiv e bl oc kin g si gn al s) (t rip pi ng c om m a...

  • Page 454

    Edr-3000 im02602003e device planning parameters of the 50r ground fault protection parameter description options default menu path mode mode non-directional non-directional [device planning] global protection parameters of the 50r ground fault protection parameter description setting range default m...

  • Page 455

    Edr-3000 im02602003e parameter description setting range default menu path adaptset 3 assignment adaptive parameter 3 adaptset -.- [protection para /global prot para /i-prot /50r[1]] adaptset 4 assignment adaptive parameter 4 adaptset -.- [protection para /global prot para /i-prot /50r[1]] www.Eaton...

  • Page 456

    Edr-3000 im02602003e setting group parameters of the 50r ground fault protection parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active active [protection para / /i-prot /50r[1]] exblo fc activate (allow) or inactivate ...

  • Page 457

    Edr-3000 im02602003e parameter description setting range default menu path t tripping delay only available if: characteristic = deft 0.00 - 300.00s 0.5s [protection para / /i-prot /50r[1]] www.Eaton.Com 445.

  • Page 458

    Edr-3000 im02602003e 50r ground fault protection input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /i-prot /50r[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /i-prot /50r[1]] exblo ...

  • Page 459

    Edr-3000 im02602003e 50r ground fault protection signals (output states) signal description active signal: active exblo signal: external blocking rvs blo signal: reverse blocking blo tripcmd signal: trip command blocked exblo tripcmd signal: external blocking of the trip command pickup signal: picku...

  • Page 460

    Edr-3000 im02602003e commissioning: ground fault protection – non-directional [ansi 50r] please test the non-directional ground overcurrent using the procedure for non-directional phase overcurrent protection. Www.Eaton.Com 448.

  • Page 461

    Edr-3000 im02602003e 51r inv calculated ground fault protection elements 51r[1] ,51r[2] all ground current elements are identically structured. For each element the following characteristics are available: • ninv (iec/ xinv ); • vinv (iec/ xinv ); • linv (iec/ xinv ); • einv (iec/ xinv ); • minv (an...

  • Page 462

    Edr-3000 im02602003e www.Eaton.Com 450 n am e. Tr ip c m d n am e. Tr ip p le as e r ef er to d ia gr am : b lo ck in gs ** n am e. P ic ku p p le as e r ef er to d ia gr am : tr ip b lo ck in gs (e le m en t i s no t d ea ct iv at ed a nd n o ac tiv e bl oc ki ng s ig na ls ) (t rip pi ng c om m an...

  • Page 463

    Edr-3000 im02602003e device planning parameters of the 51r ground fault protection parameter description options default menu path mode mode 51r[1]: non-directional 51r[2]: do not use, non-directional non-directional [device planning] global protection parameters of the 51r ground fault protection p...

  • Page 464

    Edr-3000 im02602003e parameter description setting range default menu path adaptset 3 assignment adaptive parameter 3 adaptset -.- [protection para /global prot para /i-prot /51r[1]] adaptset 4 assignment adaptive parameter 4 adaptset -.- [protection para /global prot para /i-prot /51r[1]] www.Eaton...

  • Page 465

    Edr-3000 im02602003e setting group parameters of the 51r ground fault protection parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active active [protection para / /i-prot /51r[1]] exblo fc activate (allow) or inactivate ...

  • Page 466

    Edr-3000 im02602003e parameter description setting range default menu path curve shape characteristic iec ninv, iec vinv, iec einv, iec linv, ansi minv, ansi vinv, ansi einv, therm flat, it, i2t, i4t ansi minv [protection para / /i-prot /51r[1]] t-multiplier time multiplier/tripping characteristic f...

  • Page 467

    Edr-3000 im02602003e 51r ground fault protection input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /i-prot /51r[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /i-prot /51r[1]] exblo ...

  • Page 468

    Edr-3000 im02602003e 51r ground fault protection signals (output states) signal description active signal: active exblo signal: external blocking rvs blo signal: reverse blocking blo tripcmd signal: trip command blocked exblo tripcmd signal: external blocking of the trip command pickup signal: picku...

  • Page 469

    Edr-3000 im02602003e commissioning: ground fault protection – non-directional [ansi 51r] please test the non-directional ground overcurrent analog to the non-directional phase overcurrent protection. Www.Eaton.Com 457.

  • Page 470

    Edr-3000 im02602003e zi - zone interlocking elements zi principle – general use the purpose of zone interlocking is to speed up tripping for some faults without sacrificing the coordination of the system and interjecting nuisance trips into the system. Zone interlocking devices can communicate acros...

  • Page 471

    Edr-3000 im02602003e small trip delay (about three cycles – settable) to wait for downstream devices interlocking signals. Zone interlocking trip signal only possible by absence of zone interlocking input signals. Configurable zone interlocking trip functions (protective functions serve as zone inte...

  • Page 472

    Edr-3000 im02602003e device planning parameters of the zone interlocking parameter description options default menu path mode mode use use [device planning] www.Eaton.Com 460

  • Page 473

    Edr-3000 im02602003e global protection parameters of the zone interlocking in the global parameter menu for zone interlocking, two external blocking inputs (» ex block1/ex block2«), as with other protection modules, can be assigned to the input of the zone interlocking function so that the zone inte...

  • Page 474

    Edr-3000 im02602003e setting group parameters of the zone interlocking the zone interlocking setting group parameters consists of three groups of setting to configure the zone interlocking module to adapt to various application philosophies accordingly: general: this group comprises the settings use...

  • Page 475

    Edr-3000 im02602003e parameter description setting range default menu path exblo fc activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those m...

  • Page 476

    Edr-3000 im02602003e zone interlocking output logic [x2] the following current protective function elements serve as the phase zone interlock output start functions: 51p[1]; 50p[1]; and 50p[2]. The following current protective function serves as the ground zone interlock output start functions: 51x[...

  • Page 477

    Edr-3000 im02602003e www.Eaton.Com 465 zi.Out zone interlocking output logic timing started standby tripped reset standby state transfer 51p[1].Trip 51p[1].Pickup zi.Bkr blo t t 0 1 0 1 t 0 1 t 0 1 t 0 1 reset timer 10 cycles.

  • Page 478

    Edr-3000 im02602003e www.Eaton.Com 466 o r o r o r o r o r o r o r an d an d an d an d an d an d ph as e g ro un d fa ul t t yp e bo th 50 p[ 1] .P ic ku p 51 p[ 1] .P ic ku p 50 p[ 2] .P ic ku p 50 p[ 1] .T rip cm d 51 p [1 ].T rip c m d 50 p[ 2] .T rip c m d 50 x[ 1] .P ic ku p 51 x[ 1] .P ic ku p...

  • Page 479

    Edr-3000 im02602003e zone interlocking trip logic [x2] the following overcurrent protection elements trigger phase zone-interlock trip functions: 1.5 * 51p[1]; 50p[1]; and 50p[2]. The following overcurrent protection elements trigger ground zone interlock trip functions: 51x[1]; 50x[1]; 50x[2]; 51r[...

  • Page 480

    Edr-3000 im02602003e www.Eaton.Com 468 zone interlocking trip logic timing started standby tripped standby interlocked standby zi.Trip state transfer 51p[1].Pickup zi.Pickup t t 0 1 0 1 t 0 1 t 0 1 t 0 1 trip delay timer 3 cycles zi.In.

  • Page 481

    Edr-3000 im02602003e www.Eaton.Com 469 an d an d o r 5 0 m s t 5 0 m s t o r o r o r o r an d an d ph as e g ro un d fa ul t t yp e bo th 50 p[ 1] .P ick up 1. 5* 51 p[ 1] .P ick up 50 p[ 2] .P ick up 50 x[ 1] .P ick up 51 x[ 1] .P ick up 50 x[ 2] .P ick up 50 r[ 1] .P ic ku p 51 r[ 1] .P ic ku p 50...

  • Page 482

    Edr-3000 im02602003e zone interlocking input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /zi] exblo2-i module input state: external blocking2 [protection para /global prot para /zi] exblo tripcmd-i module input state: exte...

  • Page 483

    Edr-3000 im02602003e zone interlocking signals (output states) signal description active signal: active exblo signal: external blocking blo tripcmd signal: trip command blocked exblo tripcmd signal: external blocking of the trip command bkr blo signal: blocked by breaker failure phase pickup signal:...

  • Page 484

    Edr-3000 im02602003e zone interlocking wiring the zi outputs are for use with connection to electronic inputs only. The zone interlocking connection between relays is done by means of a twisted shielded cable. Downstream zone interlock outputs may be paralleled from up to ten devices (fp-5000 or dt-...

  • Page 485

    Edr-3000 im02602003e www.Eaton.Com 473 zone 1 j3 fp-x000 1 4 2 out in com x2 13 14 15 shield out com zone 2 16 17 18 shield in com edr-x000 zone 3 j3 fp-x000 1 4 2 out in com dt-3000 13 14 15 out in out 16 18 in com ground phase j3 fp-x000 1 4 2 out in com x2 13 14 15 shield out com 16 17 18 shield ...

  • Page 486

    Edr-3000 im02602003e hardware terminals for zone interlocking by means of the zone interlocking terminals, the device can be connected to other eaton protective devices such as an fp5000, dt3000, etc. As an upstream device, the terminals - phase/ground in should be connected to the out terminals of ...

  • Page 487

    Edr-3000 im02602003e terminal marking x2 for device: edr-3000 terminal marking x2 for device: edr-4000, edr-5000, emr-4000, emr-5000, egr-4000 and egr-5000 www.Eaton.Com 475 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 ro3 x?. Do not use do not use com out in com ro4 ro1 ro2 1 2 3 4 5 6 7 8 9 10 11 ...

  • Page 488

    Edr-3000 im02602003e 46 - current unbalance protection elements: 46[1] ,46[2] this is the 46 device current unbalance setting, which works similar to the 47 device voltage unbalance setting. The positive and negative sequence currents are calculated from the 3-phase currents. The threshold setting d...

  • Page 489

    Edr-3000 im02602003e www.Eaton.Com 477 n am e. Tr ip c m d n am e. Tr ip p le as e r ef er to d ia gr am : b lo ck in gs ia n am e. Pi ck up p le as e r ef er to d ia gr am : tr ip b lo ck in gs 46 [1 ].. .[n ] (e le m en t i s no t d ea ct iva te d an d no a ct iv e bl oc ki ng s ig na ls ) (t rip ...

  • Page 490

    Edr-3000 im02602003e device planning parameters of the current unbalance module parameter description options default menu path mode mode do not use, use use [device planning] global protection parameters of the current unbalance module parameter description setting range default menu path exblo1 ex...

  • Page 491

    Edr-3000 im02602003e setting group parameters of the current unbalance module parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active inactive [protection para / /unbalance-prot /46[1]] exblo fc activate (allow) or inact...

  • Page 492

    Edr-3000 im02602003e current unbalance module input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /unbalance-prot /46[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /unbalance-prot /46...

  • Page 493

    Edr-3000 im02602003e commissioning: current unbalance module object to be tested: test of the unbalanced load protection function. Necessary means: three-phase current source with adjustable current unbalance; and timer. Procedure: check the phase sequence: ensure that the phase sequence is the same...

  • Page 494

    Edr-3000 im02602003e apply a balanced three-phase current system (nominal currents). Switch off ia (the threshold value » threshold« for » i2 fund.« must be below 33%). Measure the tripping time. The present current unbalance » i2 fund.« corresponds with 1/3 of the existing phase current displayed. ...

  • Page 495

    Edr-3000 im02602003e testing the threshold values configure minimum » %(i2/i1)« setting (2%) and an arbitrary threshold value » threshold« (i2 fund.). For testing the threshold value, a current has to be fed to phase a which is lower than three times the adjusted threshold value » threshold« (i2 fun...

  • Page 496

    Edr-3000 im02602003e clpu - supervision module cold load pickup available elements: clpu when manually or automatically closing a breaker after it has been open for a prolonged time, a greater than normal load current may be experienced due to the load inrush . This high starting current causes some...

  • Page 497

    Edr-3000 im02602003e please be aware of the meaning of the two delay timers. T load off (pickup delay): after this time expires, the load is no longer diversified. T max block (release delay): after the starting condition is fulfilled (e.G.: breaker switched on manually), the “clpu.Enabled” signal w...

  • Page 498

    Edr-3000 im02602003e example mode: breaker position www.Eaton.Com 486 n am e = c lp u c lp u c in b kr -5 2a 0 1 0 1 c lp u. De te ct ed t-l oa d o ff t-m ax b lo ck c ol d lo ad 0 1.

  • Page 499

    Edr-3000 im02602003e www.Eaton.Com 487 p le as e r efe r t o d ia gr am : b lo ck in gs (e le m en t i s no t d ea ct iv at ed a nd n o ac tiv e bl oc ki ng s ig na ls ) n am e = c lp u 2 c lp u .E na bl ed cl pu .I ia ib ic c lp u .I ar .R un ni ng * c lp u an d an d an d i b kr s ta te a nd i c lp...

  • Page 500

    Edr-3000 im02602003e device planning parameters of the cold load pickup module parameter description options default menu path mode mode do not use, use use [device planning] global protection parameter of the cold load pickup module parameter description setting range default menu path mode mode bk...

  • Page 501

    Edr-3000 im02602003e set parameters of the cold load pickup module parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active inactive [protection para / /clpu] exblo fc activate (allow) or inactivate (disallow) blocking of...

  • Page 502

    Edr-3000 im02602003e states of the inputs of the cold load pickup module name description assignment via exblo1-i module input state: external blocking [protection para /global prot para /clpu] exblo2-i module input state: external blocking [protection para /global prot para /clpu] rvs blo-i module ...

  • Page 503

    Edr-3000 im02602003e commissioning of the cold load pickup module object to be tested: testing the cold load pickup module according to the configured operating mode: • i • bkr state (breaker position); • i • i necessary means: • three-phase current source (if the enable mode depends on current); • ...

  • Page 504

    Edr-3000 im02602003e • after the »t load off« timer has expired, the signal ”cplu.E nabled “=1 has to become true. • write down the measured time. Successful test result: the measured total tripping delays or individual tripping delays, threshold values, and drop-out ratios correspond with those val...

  • Page 505

    Edr-3000 im02602003e sotf - switch onto fault protection sotf in case a faulty line is energized (e.G.: when an grounding switch is in the close position), an instantaneous trip is required. The sotf module is provided to generate a permissive signal for other protection functions such as overcurren...

  • Page 506

    Edr-3000 im02602003e www.Eaton.Com 494 p le as e r ef er to d ia gr am : b lo ck in gs (e le m en t i s no t d ea ct iv at ed a nd n o ac tiv e bl oc ki ng s ig na ls ) n am e = s o tf 2 s o tf .E na bl ed so tf .I ia ib ic s o tf .I s o tf .A r b lo * ar .R un ni ng * s o t f . T- en ab le t t ex t...

  • Page 507

    Edr-3000 im02602003e device planning parameters of the switch onto fault module parameter description options default menu path mode mode do not use, use use [device planning] www.Eaton.Com 495.

  • Page 508

    Edr-3000 im02602003e global protection parameters of the switch onto fault module parameter description setting range default menu path mode mode bkr state, i bkr state and i bkr manual close, ext sotf bkr manual close [protection para /global prot para /sotf] exblo1 external blocking of the module,...

  • Page 509

    Edr-3000 im02602003e setting group parameters of the switch onto fault module parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active inactive [protection para / /sotf] exblo fc activate (allow) or inactivate (disallow) ...

  • Page 510

    Edr-3000 im02602003e switch onto fault module input states name description assignment via exblo1-i module input state: external blocking [protection para /global prot para /sotf] exblo2-i module input state: external blocking [protection para /global prot para /sotf] rvs blo-i module input state: r...

  • Page 511

    Edr-3000 im02602003e commissioning: switch onto fault [ansi 50hs] object to be tested: testing the module switch onto fault according to the configured operating mode : i bkr state (breaker position); i bkr manual close. Necessary means: three-phase current source (if the enable mode depends on curr...

  • Page 512

    Edr-3000 im02602003e successful test result: the measured total tripping delays or individual tripping delays, threshold values, and drop-out ratios correspond with those values, specified in the adjustment list. Permissible deviations/tolerances can be found in the technical data section. Www.Eaton...

  • Page 513

    Edr-3000 im02602003e 79 - automatic reclosure ar the autoreclosure is used to minimize outages on overhead lines. The majority 1 (>60% in medium voltage and >85% in high voltage) of faults (arc flash over) on overhead lines are temporary and can be cleared by means of the autoreclosure element. De-s...

  • Page 514

    Edr-3000 im02602003e automatic autoreclose result evaluation (successful/unsuccessful). Separate counters to register total, successful/unsuccessful reclosing numbers. Www.Eaton.Com 502.

  • Page 515

    Edr-3000 im02602003e via the pre shot (fast trip), the ar-module is able to trip the breaker ahead of the protection stage that has activated the ar-module. As a general rule, a fast trip is either issued before the first reclosure attempt or after the last permitted reclosure attempt. 1. At the beg...

  • Page 516

    Edr-3000 im02602003e the following table gives a folder (structure) overview. Ar menu folder purpose ar path: [protection para\global prot para\ar] within this menu, external blockings, external lockings, external shot increments and external resets can be assigned. Those external events can only be...

  • Page 517

    Edr-3000 im02602003e ar states the following diagram shows the state transitions between the various states of the autoreclosure function. This diagram visualizes the run time logic and timing sequence according to the state transition direction and the events which trigger the transitions. State tr...

  • Page 518

    Edr-3000 im02602003e www.Eaton.Com 506 standby 1 ready 3 lockout 6 t-manualcloseblock 2 t-reset lockout 7 blocked 5 ar cycle start t-dead t-run2ready 4 lock=true initiate ar in itia te fc =t ru e su cc es sf ul bk r= po s c lo se lock=true bk r= po s c lo se & t-m an ua lc lo se b lo ck =t im er e l...

  • Page 519

    Edr-3000 im02602003e in general, the autoreclosure function is only active (will be initiated) when all of the following conditions are met: autoreclosure function is enabled (in ar general setting: function =active); breaker contact(s) (52a or/and 52b) is (are) installed and has (have) been program...

  • Page 520

    Edr-3000 im02602003e 3 ready an activated autoreclose function is considered to be in »r eady « state when all of the following conditions are true: the breaker is in closed position; the manual-close-block-timer elapses after a breaker manual/remote close operation; the autoreclose function is not ...

  • Page 521

    Edr-3000 im02602003e 5 blocked an activated autoreclose function goes into the »b locked « state when one of the assigned blocking functions is true. The autoreclose function exits the »b locked « state if the assigned blocking signal is no longer present. Www.Eaton.Com 509.

  • Page 522

    Edr-3000 im02602003e 6 lockout an activated autoreclose function goes into the »l ockout « state when one of the following conditions is true: an unsuccessful autoreclose is detected after all programmed autoreclose shots. The fault is of permanent nature; reclose failure (incomplete sequence); auto...

  • Page 523

    Edr-3000 im02602003e ar cycle (shot) 4 run (cycle) the following drawing shows the state transitions in detail inside an ar run cycle. Www.Eaton.Com 511 tr2r=out&& bkr=pos close -------------------------- ar.Successful td=out& cb=off& cb_ready=true& trip =false --------------------------------------...

  • Page 524

    Edr-3000 im02602003e 11 ready an activated autoreclose function is considered to be in »r eady « state when all of the following conditions are true: the breaker is in closed position; the manual-close-block-timer elapses after a breaker manual/remote close operation; the autoreclose function is not...

  • Page 525

    Edr-3000 im02602003e 14 t-dead while in the dead timing state » t-dead« , the pre-set dead timer for current ar shot is timing and cannot be interrupted unless there are any blocking or lockout conditions coming. After dead timer elapses, the autoreclosure issues the breaker reclosing command and go...

  • Page 526

    Edr-3000 im02602003e 15 reclosing if there is no other blocking or lockout conditions and the breaker is closed while the breaker reclosing supervision timer is timing, the autoreclosure starts the » t-run2ready« timer and goes into the state: » t -r un 2r eady «. 16 t-run2ready successful autoreclo...

  • Page 527

    Edr-3000 im02602003e timing diagrams auto reclosing timing diagram for unsuccessful 2-shot auto reclosing scheme with acceleration at pre-shot. Www.Eaton.Com 515 pre shot shot ar.Running shot 1 shot 2 ar - module states t 0 1 ready running lockout reclosing t 0 1 bkr state t 0 1 protection t 0 1 pro...

  • Page 528

    Edr-3000 im02602003e auto reclosing timing diagram for successful 2-shot auto reclosing scheme with acceleration at pre-shot. Www.Eaton.Com 516 pre shot shot ar.Running shot 1 shot 2 ar - module states t 0 1 ready running ready reclosing t 0 1 bkr state t 0 1 protection t 0 1 protection t 0 1 fault ...

  • Page 529

    Edr-3000 im02602003e auto reclosing states during manual breaker closing. Protection trip while manual close blocking time is timing what happens if while the timer manual close block time is timing down the protective device gets a trip signal? While the timer manual close block time is timing, any...

  • Page 530

    Edr-3000 im02602003e ar lockout reset logic in case lockout reset coming before manual breaker closed. Ar lockout reset logic in case lockout reset coming after manual breaker closed. Www.Eaton.Com 518 lockout reset ar - module states t 0 1 lockout t-man close blo ready manual breaker close t 0 1 t ...

  • Page 531

    Edr-3000 im02602003e zone coordination general description what does zone coordination mean? Zone coordination means that the upstream protection device is doing a virtual autoreclosure while the downstream protective device is doing a “real” autoreclosure. By means of the zone coordination, selecti...

  • Page 532

    Edr-3000 im02602003e incremented shot number. In this way, the upstream feeder will “follow” the protective settings of downstream recloser shot by shot. For a transient fault, the autoreclose with zone coordination will not be initiated again because of absence of the fault current and will be rese...

  • Page 533

    Edr-3000 im02602003e www.Eaton.Com 521 protective device recloser shot 1 (triggered by: i [1]) tripping curve of the fuse shot 2 (triggered by: i [2]) shot 1 (triggered by: i [1]) shot 2 (triggered by: i [2]) i t i t i t.

  • Page 534

    Edr-3000 im02602003e direct commands of the automatic reclosure module parameter description setting range default menu path res totno suc unsuc reset all statistic ar counters: total number of ar, successful and unsuccessful no of ar. Inactive, active inactive [operation /reset] res servicecr reset...

  • Page 535

    Edr-3000 im02602003e global protection parameters of the module automatic reclosure parameter description setting range default menu path exblo1 external blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true. 1..N, assignmen...

  • Page 536

    Edr-3000 im02602003e parameter description setting range default menu path comm reset ex lock the lockout state of the ar can be reset by communication. -.-, modbus.Comm cmd 1, modbus.Comm cmd 2, modbus.Comm cmd 3, modbus.Comm cmd 4, modbus.Comm cmd 5, modbus.Comm cmd 6, modbus.Comm cmd 7, modbus.Co...

  • Page 537

    Edr-3000 im02602003e setting group parameters of the module automatic reclosure parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active inactive [protection para / /ar /general settings] exblo fc activate (allow) or inac...

  • Page 538

    Edr-3000 im02602003e parameter description setting range default menu path t-d1 dead time between trip and reclosure attempt. Can be initiated either by a phase or a ground fault. Only available if: shots = 1-6 0.01 - 9999.00s 1s [protection para / /ar /shot manager /shot 1] t-d2 dead time between t...

  • Page 539

    Edr-3000 im02602003e parameter description setting range default menu path t-lock2ready this timer is started by the lockout reset signal, and before the timer expire the ar cannot go to any other state. 0.01 - 9999.00s 10.0s [protection para / /ar /general settings] t-run2ready examination time: if...

  • Page 540

    Edr-3000 im02602003e parameter description setting range default menu path initiate ar: initiatefc2 initiate auto reclosure : initiate function start fct -.- [protection para / /ar /shot manager /initiate ar] initiate ar: initiatefc3 initiate auto reclosure : initiate function start fct -.- [protect...

  • Page 541

    Edr-3000 im02602003e parameter description setting range default menu path shot 2: initiatefc1 automatic reclosure attempt : initiate function only available if: shots = 2-6 start fct -.- [protection para / /ar /shot manager /shot 2] shot 2: initiatefc2 automatic reclosure attempt : initiate functio...

  • Page 542

    Edr-3000 im02602003e parameter description setting range default menu path shot 3: initiatefc4 automatic reclosure attempt : initiate function only available if: shots = 3-6 start fct -.- [protection para / /ar /shot manager /shot 3] shot 4: initiatefc1 automatic reclosure attempt : initiate functio...

  • Page 543

    Edr-3000 im02602003e parameter description setting range default menu path shot 5: initiatefc3 automatic reclosure attempt : initiate function only available if: shots = 5-6 start fct -.- [protection para / /ar /shot manager /shot 5] shot 5: initiatefc4 automatic reclosure attempt : initiate functio...

  • Page 544

    Edr-3000 im02602003e module automatic reclosure input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /ar /general settings] exblo2-i module input state: external blocking2 [protection para /global prot para /ar /general setti...

  • Page 545

    Edr-3000 im02602003e module automatic reclosure signals (output states) signal description active signal: active exblo signal: external blocking standby signal: standby t-man close blo signal: ar blocked after breaker was switched on manually. This timer will be started if the breaker was switched o...

  • Page 546

    Edr-3000 im02602003e automatic reclosure module values value description default size menu path ar shot no. Counter - auto reclosure attempts 0 0 - 6 [operation /count and revdata /ar] total number cr total number of all executed automatic reclosures attempts 0 0 - 65536 [operation /count and revdat...

  • Page 547

    Edr-3000 im02602003e global protection parameters of the of the ar abort functions parameter description setting range default menu path abort::1 abort the ar-cycle, if the state of the assigned signal is true. If the state of this function is true the ar will be aborted. 1..N, assignment list -.- [...

  • Page 548

    Edr-3000 im02602003e input states of the ar abort functions name description assignment via abort::1 abort the ar-cycle, if the state of the assigned signal is true. If the state of this function is true the ar will be aborted. [protection para /global prot para /ar /blockfct] abort::2 abort the ar-...

  • Page 549

    Edr-3000 im02602003e ar start functions name description -.- no assignment 50p[1].Tripcmd signal: trip command 50p[2].Tripcmd signal: trip command 50p[3].Tripcmd signal: trip command 51p[1].Tripcmd signal: trip command 51p[2].Tripcmd signal: trip command 51p[3].Tripcmd signal: trip command 50x[1].Tr...

  • Page 550

    Edr-3000 im02602003e exp - external protection available elements: exp[1] ,exp[2] ,exp[3] ,exp[4] all element s of the external protection exp[1]...[4] are identically structured. By means of these elements, the protective device can detect and execute pickups and trips that are issued by other exte...

  • Page 551

    Edr-3000 im02602003e www.Eaton.Com 539 1. .N , a ss ig nm en t l is t n am e. Al ar m n am e. Tr ip c m d 1. .N , a ss ig nm en t l is t n am e. Tr ip an d an d n am e. Tr ip n am e. A la rm p le as e r ef er to d ia gr am : b lo ck in gs p le as e r ef er to d ia gr am : tr ip b lo ck in gs (e le m...

  • Page 552

    Edr-3000 im02602003e device planning parameters of the external protection module parameter description options default menu path mode mode do not use, use do not use [device planning] global protection parameters of the external protection module parameter description setting range default menu pat...

  • Page 553

    Edr-3000 im02602003e setting group parameters of the external protection module parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active inactive [protection para / /exp /exp[1]] exblo fc activate (allow) or inactivate (d...

  • Page 554

    Edr-3000 im02602003e external protection module input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /exp /exp[1]] exblo2-i module input state: external blocking2 [protection para /global prot para /exp /exp[1]] exblo tripcmd...

  • Page 555

    Edr-3000 im02602003e commissioning: external protection object to be tested: test of the external protection module. Necessary means: dependent on the application. Procedure: simulate the functionality of the external protection (pickup, trip, and blockings) by (de-)energizing the digital inputs. Su...

  • Page 556

    Edr-3000 im02602003e supervision bf- breaker failure [50bf*/62bf] *=only available in protective relays that offer current measurement. Available elements: bf principle – general use the breaker failure (bf) protection is used to provide backup protection in the event that a breaker fails to operate...

  • Page 557

    Edr-3000 im02602003e locking a locking signal will be issued simultaneously with the bf -signal (trip). The locking signal is permanent. This signal has to be acknowledged at the hmi. Note on devices that offer wide frequency range measurement: the supervision scheme 50bf will be blocked as soon as ...

  • Page 558

    Edr-3000 im02602003e supervision schemes up to three supervision schemes are available depending on the ordered device type and variant in order to detect a breaker failure. 50bf* a supervision timer will be started as soon as the bf- module is triggered by a trip signal. A breaker failure will be d...

  • Page 559

    Edr-3000 im02602003e • external trips : all external trips that are assigned to this breaker (within the trip manager) will start the bf module (please refer also to section „trigger signals of the breaker failure“). •in addition, the user can also select none (e.G.: if the user intends to use one o...

  • Page 560

    Edr-3000 im02602003e tabular summary supervision schemes where? Within [protection para\global prot para\supervision\bf] cb pos 2) 50bf 3) cbpos und 50bf 4) which breaker is to be monitored? Where to select? Within [protection para\global prot para\supervision\bf] selection ot the breaker that is to...

  • Page 561

    Edr-3000 im02602003e 1) it is recommended to set the i by means of that it is possible to shorten the bf supervision timer and hence reduce thermal and mechanical damage of the electrical equipment in case of a breaker failure. The lower the threshold, the longer the time that is needed to detect, t...

  • Page 562

    Edr-3000 im02602003e breaker failure protection for devices that offer current measurement www.Eaton.Com 550 φ b f. I- b f > b f .T- b f s 1 r 1 1 tr ig ge r * al l t rip s c ur re nt t rip s ex te rn al t rip s bk r[x ].T rip c m d * c ur re nt .T rip c m d * ex tt rip [x ].T rip cm d * 1. .N , 1 ....

  • Page 563

    Edr-3000 im02602003e breaker failure protection for devices that offer voltage measurement only www.Eaton.Com 551 φ b f. T- b f s 1 r 1 1 tr ig ge r * a ll t rip s ex te rn al t rip s bk r[x ].T rip c m d * ex tt rip [x ].T rip c m d * 1. .N , 1 ..N , a ss ig nm en t li st bf .T rig ge r3 1. .N , a ...

  • Page 564

    Edr-3000 im02602003e device planning parameters of the bf parameter description options default menu path mode mode use use [device planning] global protection parameters of the bf parameter description setting range default menu path scheme scheme 50bf, cb pos, 50bf and cb pos 50bf [protection para...

  • Page 565

    Edr-3000 im02602003e parameter description setting range default menu path trigger3 trigger that will start the bf trigger -.- [protection para /global prot para /supervision /bf] direct commands of the bf parameter description setting range default menu path res lockout reset lockout inactive, acti...

  • Page 566

    Edr-3000 im02602003e setting group parameters of the bf in order to prevent a faulty activation of the bf module, the pickup (alarm) time must be greater than the sum of: operating time of the protective relay +the close-open time of the breaker (please refer to the technical data of the manufacture...

  • Page 567

    Edr-3000 im02602003e bf input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /supervision /bf] exblo2-i module input state: external blocking2 [protection para /global prot para /supervision /bf] trigger1-i module input: trig...

  • Page 568

    Edr-3000 im02602003e trigger signals of the breaker failure these trips will start the bf module if » all trips« have been selected as the trigger event. Name description -.- no assignment 50p[1].Tripcmd signal: trip command 50p[2].Tripcmd signal: trip command 50p[3].Tripcmd signal: trip command 51p...

  • Page 569

    Edr-3000 im02602003e name description logic.Le1.Gate out signal: output of the logic gate logic.Le1.Timer out signal: timer output logic.Le1.Out signal: latched output (q) logic.Le1.Out inverted signal: negated latched output (q not) logic.Le2.Gate out signal: output of the logic gate logic.Le2.Time...

  • Page 570

    Edr-3000 im02602003e name description logic.Le10.Timer out signal: timer output logic.Le10.Out signal: latched output (q) logic.Le10.Out inverted signal: negated latched output (q not) logic.Le11.Gate out signal: output of the logic gate logic.Le11.Timer out signal: timer output logic.Le11.Out signa...

  • Page 571

    Edr-3000 im02602003e name description logic.Le19.Out signal: latched output (q) logic.Le19.Out inverted signal: negated latched output (q not) logic.Le20.Gate out signal: output of the logic gate logic.Le20.Timer out signal: timer output logic.Le20.Out signal: latched output (q) logic.Le20.Out inver...

  • Page 572

    Edr-3000 im02602003e name description logic.Le28.Out inverted signal: negated latched output (q not) logic.Le29.Gate out signal: output of the logic gate logic.Le29.Timer out signal: timer output logic.Le29.Out signal: latched output (q) logic.Le29.Out inverted signal: negated latched output (q not)...

  • Page 573

    Edr-3000 im02602003e name description logic.Le38.Gate out signal: output of the logic gate logic.Le38.Timer out signal: timer output logic.Le38.Out signal: latched output (q) logic.Le38.Out inverted signal: negated latched output (q not) logic.Le39.Gate out signal: output of the logic gate logic.Le3...

  • Page 574

    Edr-3000 im02602003e name description logic.Le47.Timer out signal: timer output logic.Le47.Out signal: latched output (q) logic.Le47.Out inverted signal: negated latched output (q not) logic.Le48.Gate out signal: output of the logic gate logic.Le48.Timer out signal: timer output logic.Le48.Out signa...

  • Page 575

    Edr-3000 im02602003e name description logic.Le56.Out signal: latched output (q) logic.Le56.Out inverted signal: negated latched output (q not) logic.Le57.Gate out signal: output of the logic gate logic.Le57.Timer out signal: timer output logic.Le57.Out signal: latched output (q) logic.Le57.Out inver...

  • Page 576

    Edr-3000 im02602003e name description logic.Le65.Out inverted signal: negated latched output (q not) logic.Le66.Gate out signal: output of the logic gate logic.Le66.Timer out signal: timer output logic.Le66.Out signal: latched output (q) logic.Le66.Out inverted signal: negated latched output (q not)...

  • Page 577

    Edr-3000 im02602003e name description logic.Le75.Gate out signal: output of the logic gate logic.Le75.Timer out signal: timer output logic.Le75.Out signal: latched output (q) logic.Le75.Out inverted signal: negated latched output (q not) logic.Le76.Gate out signal: output of the logic gate logic.Le7...

  • Page 578

    Edr-3000 im02602003e name description 50x[1].Tripcmd signal: trip command 50x[2].Tripcmd signal: trip command 51x[1].Tripcmd signal: trip command 51x[2].Tripcmd signal: trip command 50r[1].Tripcmd signal: trip command 50r[2].Tripcmd signal: trip command 51r[1].Tripcmd signal: trip command 51r[2].Tri...

  • Page 579

    Edr-3000 im02602003e these trips will start the bf module if »external trips« have been selected as the trigger event. Name description -.- no assignment exp[1].Tripcmd signal: trip command exp[2].Tripcmd signal: trip command exp[3].Tripcmd signal: trip command exp[4].Tripcmd signal: trip command ww...

  • Page 580

    Edr-3000 im02602003e commissioning example: supervision scheme 50bf object to be tested: test of the breaker failure protection (supervision scheme 50bf). Necessary means: current source; ammeter; and timer. When testing, the applied test current must always be higher than the tripping threshold »i-...

  • Page 581

    Edr-3000 im02602003e cts - current transformer supervision cts most functions of metering, protection, and control in the relay rely on correct current measurements. It is important to make sure the ct connections and their operations are correct. The failures (including ct secondary wire broken, in...

  • Page 582

    Edr-3000 im02602003e if the current is measured in two phases only (for example only ia/ib) or if there is no separate ground current measuring (e.G.: normally via a zero sequence ct), the supervision function should be deactivated. Www.Eaton.Com 570

  • Page 583

    Edr-3000 im02602003e www.Eaton.Com 571 p le a se r e fe r to d ia gr am : b lo ck in g s ix c al cu la te d ia c ts .P ic ku p c ts (e le m en t i s no t d ea ct iv at ed a nd n o ac tiv e bl oc ki ng si gn al s) ic ib ix Σ + - kd ct s. Δi 2 an d 40 c ts . T t 0 p ha se o r g ro un d c ur re nt t ra...

  • Page 584

    Edr-3000 im02602003e device planning parameters of the current transformer supervision parameter description options default menu path mode mode do not use, use do not use [device planning] global protection parameter of the current transformer supervision parameter description setting range default...

  • Page 585

    Edr-3000 im02602003e setting group parameters of the current transformer supervision parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active inactive [protection para / /supervision /cts] exblo fc activate (allow) or ina...

  • Page 586

    Edr-3000 im02602003e current transformer supervision input states name description assignment via exblo1-i module input state: external blocking1 [protection para /global prot para /supervision /cts] exblo2-i module input state: external blocking2 [protection para /global prot para /supervision /cts...

  • Page 587

    Edr-3000 im02602003e commissioning: current transformer failure supervision preconditions: 1.Measurement of all three-phase currents (are applied to the measuring inputs of the device). 2.The ground current is detected via a zero sequence transformer (not in residual connection). Object to be tested...

  • Page 588

    Edr-3000 im02602003e 74tc - trip circuit monitoring tcm the trip circuit monitoring is used for monitoring if the trip circuit is ready for opening operations. The monitoring can be fulfilled by two ways. The first assumes only 52a is used in the trip circuit. The second assumes that, in addition to...

  • Page 589

    Edr-3000 im02602003e one breaker application examples trip circuit monitoring for one breaker: auxiliary contacts (52a and 52b) in trip circuit. Www.Eaton.Com 577 breaker 1 (bkr[1]) control voltage 1 2 3 4 5 6 7 8 pe 9 10 11 12 com1 13 14 15 16 17 18 v+ di1 com2 di2 v- x1 tc w1-52a w1-52b +dc - dc 5...

  • Page 590

    Edr-3000 im02602003e trip circuit monitoring for one breaker: auxiliary contacts (52a only) in trip circuit. Www.Eaton.Com 578 breaker 1 (bkr[1]) control voltage 1 2 3 4 5 6 7 8 pe 9 10 11 12 com1 13 14 15 16 17 18 v+ di1 v- x1 tc w1-52a w1-52b +dc - dc 52a 52b trip relay control voltage and bkr.Pos...

  • Page 591

    Edr-3000 im02602003e device planning parameters of the trip circuit monitoring module parameter description options default menu path mode mode do not use, use use [device planning] www.Eaton.Com 579.

  • Page 592

    Edr-3000 im02602003e global protection parameters of the trip circuit monitoring module parameter description setting range default menu path mode select if trip circuit is going to be monitored when the breaker is closed or when the breaker is either open or close. Closed, either closed [protection...

  • Page 593

    Edr-3000 im02602003e setting group parameters of the trip circuit monitoring module parameter description setting range default menu path function permanent activation or deactivation of module/element. Inactive, active inactive [protection para / /supervision /tcm] exblo fc activate (allow) or inac...

  • Page 594

    Edr-3000 im02602003e trip circuit monitoring module input states name description assignment via cinbkr-52a-i module input state: feed-back signal of the bkr (52a) [protection para /global prot para /supervision /tcm] cinbkr-52b-i module input state: feed-back signal of the bkr. (52b) [protection pa...

  • Page 595

    Edr-3000 im02602003e commissioning: trip circuit monitoring for breakers for breakers that trip by means of little energy (e.G.: via an optocoupler), it has to be ensured that the current applied by the digital inputs will not cause false tripping of the breaker. Object to be tested: test of the tri...

  • Page 596

    Edr-3000 im02602003e self supervision the system-ok contact (sc relay, life-contact) cannot be configured. The system contact is a form “c” contact that picks up when the device is free from internal faults. While the device is booting up, the system ok relay (sc) remains dropped-off (unenergized). ...

  • Page 597

    Edr-3000 im02602003e the measuring unit continuously checks the measured data by comparing received data with data from a second channel sampled in parallel. The auxiliary voltage is monitored continuously. If the voltage of one of the different supply circuits falls below a certain threshold, a res...

  • Page 598

    Edr-3000 im02602003e error messages / codes after a reboot of the device, the reason for rebooting will be displayed under [operation/status display/sys/reboot]. For more information about the reboot reason, please refer to the information in this section. The reboot will also be logged within the e...

  • Page 599

    Edr-3000 im02602003e programmable logic available elements (equations): logic general description the protective device includes programmable logic equations for programming inputs, outputs, blocking of protective functions, and custom logic functions in the relay. The logic provides control of the ...

  • Page 600

    Edr-3000 im02602003e if no signal is assigned to a logic gate (all inputs are "0"), then the output of the gate will be set as follows: "0" for an and gate "1" for a nand gate "0" for an or gate "1" for a nor gate if at least one input signal is assigned to a gate all not assigned inputs are set to:...

  • Page 601

    Edr-3000 im02602003e detailed overview – overall logic diagram. Www.Eaton.Com 589 φ a n d o r n a n d n o r t- o n d el ay t- o ff d e la y g at e o u t t im e r o u t o ut o ut in ve rt e d d el ay t im er 1. .N , a ss ig nm en t l is t le [x ].I n 1 ac tiv e in ac tiv e in ve rti ng 1 x o r 1. .N ...

  • Page 602

    Edr-3000 im02602003e available gates (operators) within the logic equation, the following gates can be used. Input signals the user can assign up to four input signals (from the assignment list) to the inputs of the gate. As an option, each of the four input signals can be inverted (negated). Timer ...

  • Page 603

    Edr-3000 im02602003e cascading logical outputs the device will evaluate output states of the logic equations starting from “logic equation 1” up to the logic equation with the highest number. This evaluation cycle will be continuously repeated. Cascading logic equations in an ascending sequence. Cas...

  • Page 604

    Edr-3000 im02602003e www.Eaton.Com 592 logic equation1 le1.In1 le1.In2 le1.In3 le1.In4 output of logic equation 1 logic equation2 le2.In2 le2.In3 le2.In4 output of logic equation 2 update within the same evaluation cycle update within the next evaluation cycle (1 cycle delay ) logic equation2 le2.In...

  • Page 605

    Edr-3000 im02602003e programmable logic at the panel warning improper use of logic equations might result in personal injury or damage the electrical equipment. Do not use logic equations unless the user can ensure the safe functionality. How to configure a logic equation? Within the device planning...

  • Page 606

    Edr-3000 im02602003e how to configure a logic equation? Within the device planning, set the number of required logic equations. Call up the [logic] menu. Set the input signals (where necessary, invert them). If required, configure the timer (» on delay« and » off delay« ). If the latched output sign...

  • Page 607

    Edr-3000 im02602003e selection list for logic input signals name description -.- no assignment prot.Active signal: active prot.Available signal: protection is available. Prot.Pickup signal: general pickup prot.Trip signal: general trip bkr.Si singlecontactind signal: the position of the switchgear i...

  • Page 608

    Edr-3000 im02602003e name description bkr.Open cmd signal: open command issued to the switchgear. Depending on the setting the signal may include the open command of the prot module. Bkr.Close cmd manual signal: close cmd manual bkr.Open cmd manual signal: open cmd manual bkr.Sync close request sign...

  • Page 609

    Edr-3000 im02602003e name description 50r[1].Tripcmd signal: trip command 50r[2].Pickup signal: pickup ix or ir 50r[2].Trip signal: trip 50r[2].Tripcmd signal: trip command 51r[1].Pickup signal: pickup ix or ir 51r[1].Trip signal: trip 51r[1].Tripcmd signal: trip command 51r[2].Pickup signal: pickup...

  • Page 610

    Edr-3000 im02602003e name description clpu.Settle time signal: settle time exp[1].Alarm signal: alarm exp[1].Trip signal: trip exp[1].Tripcmd signal: trip command exp[2].Alarm signal: alarm exp[2].Trip signal: trip exp[2].Tripcmd signal: trip command exp[3].Alarm signal: alarm exp[3].Trip signal: tr...

  • Page 611

    Edr-3000 im02602003e name description wired inputs.Toca m2-i state of the module input: main 2 breaker connected wired inputs.43/10 m2-i state of the module input: main 2 breaker selected to trip wired inputs.52a t-i state of the module input: tie breaker closed wired inputs.52b t-i state of the mod...

  • Page 612

    Edr-3000 im02602003e name description iec61850.Virtout3-i module input state: binary state of the virtual output (ggio) iec61850.Virtout4-i module input state: binary state of the virtual output (ggio) iec61850.Virtout5-i module input state: binary state of the virtual output (ggio) iec61850.Virtout...

  • Page 613

    Edr-3000 im02602003e name description iec61850.Virtinp8 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp9 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp10 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp11 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp12 s...

  • Page 614

    Edr-3000 im02602003e name description logic.Le4.Gate out signal: output of the logic gate logic.Le4.Timer out signal: timer output logic.Le4.Out signal: latched output (q) logic.Le4.Out inverted signal: negated latched output (q not) logic.Le5.Gate out signal: output of the logic gate logic.Le5.Time...

  • Page 615

    Edr-3000 im02602003e name description logic.Le13.Timer out signal: timer output logic.Le13.Out signal: latched output (q) logic.Le13.Out inverted signal: negated latched output (q not) logic.Le14.Gate out signal: output of the logic gate logic.Le14.Timer out signal: timer output logic.Le14.Out signa...

  • Page 616

    Edr-3000 im02602003e name description logic.Le22.Out signal: latched output (q) logic.Le22.Out inverted signal: negated latched output (q not) logic.Le23.Gate out signal: output of the logic gate logic.Le23.Timer out signal: timer output logic.Le23.Out signal: latched output (q) logic.Le23.Out inver...

  • Page 617

    Edr-3000 im02602003e name description logic.Le31.Out inverted signal: negated latched output (q not) logic.Le32.Gate out signal: output of the logic gate logic.Le32.Timer out signal: timer output logic.Le32.Out signal: latched output (q) logic.Le32.Out inverted signal: negated latched output (q not)...

  • Page 618

    Edr-3000 im02602003e name description logic.Le41.Gate out signal: output of the logic gate logic.Le41.Timer out signal: timer output logic.Le41.Out signal: latched output (q) logic.Le41.Out inverted signal: negated latched output (q not) logic.Le42.Gate out signal: output of the logic gate logic.Le4...

  • Page 619

    Edr-3000 im02602003e name description logic.Le50.Timer out signal: timer output logic.Le50.Out signal: latched output (q) logic.Le50.Out inverted signal: negated latched output (q not) logic.Le51.Gate out signal: output of the logic gate logic.Le51.Timer out signal: timer output logic.Le51.Out signa...

  • Page 620

    Edr-3000 im02602003e name description logic.Le59.Out signal: latched output (q) logic.Le59.Out inverted signal: negated latched output (q not) logic.Le60.Gate out signal: output of the logic gate logic.Le60.Timer out signal: timer output logic.Le60.Out signal: latched output (q) logic.Le60.Out inver...

  • Page 621

    Edr-3000 im02602003e name description logic.Le68.Out inverted signal: negated latched output (q not) logic.Le69.Gate out signal: output of the logic gate logic.Le69.Timer out signal: timer output logic.Le69.Out signal: latched output (q) logic.Le69.Out inverted signal: negated latched output (q not)...

  • Page 622

    Edr-3000 im02602003e name description logic.Le78.Gate out signal: output of the logic gate logic.Le78.Timer out signal: timer output logic.Le78.Out signal: latched output (q) logic.Le78.Out inverted signal: negated latched output (q not) logic.Le79.Gate out signal: output of the logic gate logic.Le7...

  • Page 623

    Edr-3000 im02602003e global protection parameter of the programmable logic parameter description setting range default menu path le1.Gate logic gate and, or, nand, nor and [logic /le 1] le1.In1 assignment of the input signal 1..N, logiclist -.- [logic /le 1] le1.Inverting1 inverting the input signal...

  • Page 624

    Edr-3000 im02602003e parameter description setting range default menu path le1.T-off delay switch off delay 0.00 - 36000.00s 0.00s [logic /le 1] le1.Reset latched reset signal for the latching 1..N, logiclist -.- [logic /le 1] le1.Inverting reset inverting reset signal for the latching inactive, act...

  • Page 625

    Edr-3000 im02602003e programmable logic inputs name description assignment via le1.Gate in1-i state of the module input: assignment of the input signal [logic /le 1] le1.Gate in2-i state of the module input: assignment of the input signal [logic /le 1] le1.Gate in3-i state of the module input: assig...

  • Page 626

    Edr-3000 im02602003e programmable logic outputs signal description le1.Gate out signal: output of the logic gate le1.Timer out signal: timer output le1.Out signal: latched output (q) le1.Out inverted signal: negated latched output (q not) www.Eaton.Com 614.

  • Page 627

    Edr-3000 im02602003e commissioning before starting work on an open switchboard, it is required that the switchboard is de-energized and the following five safety regulations have been met. Safety precautions: disconnect the power supply; secure against reconnection; verify that the equipment is de-e...

  • Page 628

    Edr-3000 im02602003e commissioning/protection test commissioning/protection test must be carried out by authorized and qualified personnel. Before the device is put into operation, the related documentation must be read and understood. With any test of the protection functions, the following has to ...

  • Page 629

    Edr-3000 im02602003e decommissioning – removing the plug from the relay dismounting the relay will lead to a loss of the protection functionality. Ensure that there is a back-up protection. If you are not aware of the consequences of decommissioning the device – stop! Do not start. Inform scada befo...

  • Page 630

    Edr-3000 im02602003e service and commissioning support within the service menu, various functions support maintenance and commissioning of the device. General within the [service/general] menu, the user can initiate a reboot of the device. Www.Eaton.Com 618.

  • Page 631

    Edr-3000 im02602003e maintenance mode principle – general use the maintenance mode can be used to reduce arc flash levels. Refer to std. Nfpa70e. Do not attempt to install or perform maintenance on equipment while it is energized. Severe personal injury or death can result from contact with energize...

  • Page 632

    Edr-3000 im02602003e before use the sensitivity settings for the maintenance mode have to be calculated and programmed into the device (according to std. Nfpa70e). They are not part of the device by default. When the maintenance mode is enabled and fault current causes its operation, the fault clear...

  • Page 633

    Edr-3000 im02602003e www.Eaton.Com 621 1. .N , d ig in pu ts sy s. M ai nt m od e ac tiv at ed b y in ac tiv e sy s. M ai nt m od e m od e ac tiv at io n m an ua lly ac tiv at io n vi a c om m a ct iv at io n via d i in ac tiv e sy s. M ai nt m od e m an ua lly ac tiv e c om m c m d sy s. M ai nt m ...

  • Page 634

    Edr-3000 im02602003e forcing the relay output contacts the parameters, their defaults, and setting ranges have to be taken from relay output contacts section. Principle – general use the user must ensure that the relay output contacts operate normally after maintenance is completed. If the relay out...

  • Page 635

    Edr-3000 im02602003e disarming the relay output contacts the parameters, their defaults, and setting ranges have to be taken from the relay output contacts section. Principle – general use within this mode [service/test mode (prot inhibit)/warning! Cont?/disarmed], entire groups of relay output cont...

  • Page 636

    Edr-3000 im02602003e a relay output contact will be disarmed if it is not latched and: if there is no running t-off-delay timer (hold time of a relay output contact); and if the disarm control is set to active; and if the direct command disarm is applied. Www.Eaton.Com 624.

  • Page 637

    Edr-3000 im02602003e forcing rtds* * = availability depends on ordered device. The parameters, their defaults, and setting ranges have to be taken from rtd/utrd section. Principle – general use the user must ensure that the rtds operate normally after maintenance is completed. If the rtds do not ope...

  • Page 638

    Edr-3000 im02602003e forcing analog outputs* * = availability depends on ordered device. The parameters, their defaults, and setting ranges have to be taken from analog output section. Principle – general use the user must ensure that the analog outputs operate normally after maintenance is complete...

  • Page 639

    Edr-3000 im02602003e forcing analog inputs* * = availability depends on ordered device. The parameters, their defaults, and setting ranges have to be taken from analog inputs section. Principle – general use the user must ensure that the analog inputs operate normally after maintenance is completed....

  • Page 640

    Edr-3000 im02602003e failure simulator (sequencer)* available elements: sgen * = availability depends on ordered device. This applies especially to the availability of voltage and current. Voltage simulation is only available in voltage relays, current simulation is only available in current relays....

  • Page 641

    Edr-3000 im02602003e the simulation voltages are always phase to neutral voltages, irrespectively of the mains voltage transformers' connection method (phase-to-phase / wey / open delta). Www.Eaton.Com 629.

  • Page 642

    Edr-3000 im02602003e application options of the fault simulator**: stop options cold simulation (option 1) hot simulation (option 2) do not stop run complete: pre failure, failure, post failure. How to?: call up [s ervice/test mode (prot inhibit)/warning! Cont?/sine wave gen/process ] ex force post ...

  • Page 643

    Edr-3000 im02602003e device planning parameters of the failure simulator parameter description options default menu path mode mode do not use, use use [device planning] global protection parameter of the failure simulator parameter description setting range default menu path prefault pre fault durat...

  • Page 644

    Edr-3000 im02602003e parameter description setting range default menu path ex start simulation external start of fault simulation (using the test parameters) 1..N, assignment list -.- [service /test mode (prot inhibit) /warning! Cont? /sgen /process] exblo external blocking of the module, if blockin...

  • Page 645

    Edr-3000 im02602003e parameter description setting range default menu path ib fund. Current fundamental magnitude in pre state: phase b 0.00 - 40.00in 0.0in [service /test mode (prot inhibit) /warning! Cont? /sgen /configuration /prefault /ct] ic fund. Current fundamental magnitude in pre state: pha...

  • Page 646

    Edr-3000 im02602003e parameter description setting range default menu path angle ib fund. Start position respectively start angle of the current phasor during pre phase:phase b -360 - 360° 240° [service /test mode (prot inhibit) /warning! Cont? /sgen /configuration /prefault /ct] angle ic fund. Star...

  • Page 647

    Edr-3000 im02602003e parameter description setting range default menu path ib fund. Current fundamental magnitude in fault state: phase b 0.00 - 40.00in 0.0in [service /test mode (prot inhibit) /warning! Cont? /sgen /configuration /faultsimulation /ct] ic fund. Current fundamental magnitude in fault...

  • Page 648

    Edr-3000 im02602003e parameter description setting range default menu path angle ib fund. Start position respectively start angle of the current phasor during fault phase:phase b -360 - 360° 240° [service /test mode (prot inhibit) /warning! Cont? /sgen /configuration /faultsimulation /ct] angle ic f...

  • Page 649

    Edr-3000 im02602003e parameter description setting range default menu path ib fund. Current fundamental magnitude during post phase: phase b 0.00 - 40.00in 0.0in [service /test mode (prot inhibit) /warning! Cont? /sgen /configuration /postfault /ct] ic fund. Current fundamental magnitude during post...

  • Page 650

    Edr-3000 im02602003e parameter description setting range default menu path angle ib fund. Start position respectively start angle of the current phasor during post phase: phase b -360 - 360° 240° [service /test mode (prot inhibit) /warning! Cont? /sgen /configuration /postfault /ct] angle ic fund. S...

  • Page 651

    Edr-3000 im02602003e states of the inputs of the failure simulator name description assignment via ex start simulation-i state of the module input:external start of fault simulation (using the test parameters) [service /test mode (prot inhibit) /warning! Cont? /sgen /process] exblo module input stat...

  • Page 652

    Edr-3000 im02602003e parameter description setting range default menu path stop simulation stop fault simulation (using the test parameters) inactive, active inactive [service /test mode (prot inhibit) /warning! Cont? /sgen /process] failure simulator values value description default size menu path ...

  • Page 653

    Edr-3000 im02602003e technical data use copper conductors only, 75°c (167°f). Conductor size awg 14 [2.5 mm]. Climatic environmental conditions storage temperature: -30°c to +70°c (-22°f to 158°f) operating temperature: -20°c to +60°c (-4°f to 140°f) permissible humidity at ann. Average: 75% rel. (o...

  • Page 654

    Edr-3000 im02602003e housing housing b1: height/ width 183 mm (7.205 in.) / 141.5 mm (5.571 in.) housing depth (incl. Terminals): 208 mm (8.189 in.) material, housing: aluminum extruded section material, front panel: aluminum / foil front mounting position: horizontal ( ± 45° around the x-axis must ...

  • Page 655

    Edr-3000 im02602003e current and ground current measurement plug-in connector with integrated short-circuiter (conventional current inputs) phase and ground current inputs: nominal currents: 1 a / 5 a max. Measuring range: up to 40 x in (phase currents) up to 25 x in (ground current standard) capaci...

  • Page 656

    Edr-3000 im02602003e phase and ground current inputs: screws m4, captive type acc. To vdew connection cross sections: 1 x or 2 x 2.5 mm² (2 x awg 14) with wire end ferrule 1 x or 2 x 4.0 mm² (2 x awg 12) with ring cable sleeve or cable sleeve 1 x or 2 x 6 mm² (2 x awg 10) with ring cable sleeve or c...

  • Page 657

    Edr-3000 im02602003e voltage supply aux. Voltage: 24 - 270 vdc / 48 - 230 vac (-20/+10%) ≂ buffer time in case of supply failure: >= 50 ms at minimal aux. Voltage interrupted communication is permitted. Max. Permissible making current: 18 a peak value for 0.25 ms 12 a peak value for 1 ms the voltage...

  • Page 658

    Edr-3000 im02602003e display display type: lcd with led background illumination resolution - graphics display: 128 x 64 pixel led - type: two colored: red / green number of leds, housing b2: 8 front interface rs232 baud rates: 115,200 baud handshake: rts and cts connection: 9-pole d-sub plug www.Eat...

  • Page 659

    Edr-3000 im02602003e real time clock running reserve of the real time clock: 1 year min. Www.Eaton.Com 647.

  • Page 660

    Edr-3000 im02602003e digital inputs max. Input voltage: 300 vdc / 259 vac input current: dc ac reaction time: fallback time: shorted inputs open inputs (safe state of the digital inputs) switching thresholds: un = 24 vdc, 48 vdc, 60 vdc, 110 vac / dc, 230 vac / dc un = 24 vdc switching threshold 1 o...

  • Page 661

    Edr-3000 im02602003e relay outputs continuous current: 5 a ac / dc max. Make current 25 a ac / 25 a dc for 4 s 48w (va) at l/r = 40ms 30 a / 230vac according to ansi ieee std c37.90-2005 30 a / 250vdc according to ansi ieee std c37.90-2005 max. Breaking current: 5 a ac up to 240 v ac 4 a ac at 230v ...

  • Page 662

    Edr-3000 im02602003e time synchronization irig-b00x nominal input voltage: 5 v connection: screw-type terminals (twisted pair) www.Eaton.Com 650

  • Page 663

    Edr-3000 im02602003e zone interlocking only for zone interlock tripping outputs (zone interlock, semiconductor output): 5 vdc, zone out: output voltage (high) 4.75 to 5.25 vdc output voltage (low) 0.0 to +0.5 vdc zone in: nominal input voltage +5 vdc max. Input voltage +5.5 vdc switching threshold o...

  • Page 664

    Edr-3000 im02602003e rs485* master/slave: slave connection: 6 screw-clamping terminals rm 3.5 mm (138 mil) (terminating resistors internal) the rs485 interface is realized via terminals. The communication cable has to be shielded. The shielding has to be fixed at the screw that is marked with the gr...

  • Page 665

    Edr-3000 im02602003e boot phase after switching on the power supply, the protection will be available in approximately 15 seconds. After approximately 70 seconds, the boot phase is completed (hmi and communication initialized). Www.Eaton.Com 653.

  • Page 666

    Edr-3000 im02602003e standards approvals ul-listed file: e154862 design standards generic standard en 61000-6-2 , 2005 en 61000-6-3 , 2006 product standard ec 60255-1; 2009 iec 60255-27, 2013 en 50178, 1998 ul 508 (industrial control equipment), 2005 csa c22.2 no. 14-95 (industrial control equipment...

  • Page 667

    Edr-3000 im02602003e emc immunity tests fast transient disturbance immunity test (burst) iec 60255-22-4 iec 61000-4-4 ansi c37.90.1 class 4 power supply, mains inputs other in- and outputs ± 4 kv, 2.5 khz ± 2 kv, 5 khz (coupling network) ±4 kv, 2.5 khz (coupling clamp) surge immunity test (surge) ie...

  • Page 668

    Edr-3000 im02602003e electrical discharge immunity test (esd) iec 60255-22-2 iec 61000-4-2 class 3 air discharge contact discharge 8 kv 6 kv radiated radio frequency electromagnetic field immunity test iec 60255-22-3 iec 61000-4-3 26 mhz – 80 mhz 80 mhz – 1 ghz 1 ghz – 3 ghz 10 v/m 35 v/m 10 v/m imm...

  • Page 669

    Edr-3000 im02602003e environmental tests classification: iec 60068-1 climatic classification 20/060/56 iec 60721-3-1 classification of ambient conditions (sto- rage) 1k5/1b1/1c1l/1s1/1m2 but min. -30°c (-22°f) iec 60721-3-2 classification of ambient conditions (transportation) 2k2/2b1/2c1/2s1/2m2 bu...

  • Page 670

    Edr-3000 im02602003e environmental tests test nb:temperature change iec 60255 (6.12.3.5) iec 60068-2-14 temperature cycle test duration 60°c/-20°c 5 1°c/5min test bd: dry heat transport and storage test iec 60255 (6.12.3.3) iec 60068-2-2 temperature test duration 70°c 16 h test ab: cold transport an...

  • Page 671

    Edr-3000 im02602003e mechanical tests test fc: vibration response test iec 60068-2-6 iec 60255-21-1 class 1 (10 hz – 59 hz) displacement (59hz – 150hz) acceleration number of cycles in each axis 0.0014 in. (0.035 mm) 0.5 gn 1 test fc: vibration endurance test iec 60068-2-6 iec 60255-21-1 class 1 (10...

  • Page 672

    Edr-3000 im02602003e specifications specifications of the real time clock resolution: 1 ms tolerance: time synchronization tolerances the different protocols for time synchronization vary in their accuracy: used protocol time drift over one month deviation to time generator without time synchronizat...

  • Page 673

    Edr-3000 im02602003e specifications of the measured value acquisition phase and ground current measuring frequency range: 50 hz / 60 hz ± 10% accuracy: class 0.5 amplitude error if i ±0.5% of the rated current *3) amplitude error if i > in: ±0.5% of the measured current *3) amplitude error if i > 2 ...

  • Page 674

    Edr-3000 im02602003e protection elements accuracy the tripping delay relates to the time between alarm and trip. The accuracy of the operating time relates to the time between fault entry and the time when the protection element is picked-up. Reference conditions for all protection elements: sine wa...

  • Page 675

    Edr-3000 im02602003e *3) for earth current sensitive the precision does not depend on the nominal value but is referenced to 100 ma (with in =1 a) respectively 500 ma (with in = 5 a) current unbalance: 46[x] accuracy *1) threshold ±2% of the setting value or 1% in %(i2/i1) ±1% t deft ±1% or ±10 ms o...

  • Page 676

    Edr-3000 im02602003e current transformer supervision: cts accuracy Δi ±2% of the setting value or 1.5% in dropout ratio 94% pickup delay ±1% or ± 10 ms www.Eaton.Com 664.

  • Page 677

    Edr-3000 im02602003e appendix the following terms, abbreviations, and acronyms are used in this manual. Please refer to this section for their meanings / definitions. A ampere(s), amp(s) ac alternating current a/d analog to digital ack. Acknowledge amp ampere(s), amp(s) and logical gate (the output ...

  • Page 678

    Edr-3000 im02602003e comp compensated, comparison conn connection cont continuous, contact cpu central processing unit cr. Counter(s) crt, crnt current csa canadian standards association ct control transformer ctrl. Control cts current transformer supervision d day d/a digital to analog d-sub-plug c...

  • Page 679

    Edr-3000 im02602003e ex external exblo external blocking(s) exp external protection ext extension, external °f degrees fahrenheit f field fc function (enable or disable functionality = allow or disallow.) fifo first in first out fifo principal first in first out fla full load current fo fiber optic ...

  • Page 680

    Edr-3000 im02602003e i-bf tripping threshold ic phase c current ic's manufacturer internal product designation ica phase c minus a current id identification iec international electrotechnical commission ied intelligent electronic device ieee institute of electrical and electronics engineers ig groun...

  • Page 681

    Edr-3000 im02602003e ka kiloampere kg kilogram khz kilohertz kv kilovolt(s) kvdc or kvdc kilovolt(s) direct current l1 phase a l2 phase b l3 phase c l/ln ratio of current to nominal current. Led light emitting diode lb-in pound-inch linv long time inverse tripping characteristic lv low voltage m met...

  • Page 682

    Edr-3000 im02602003e mva mega volt-ampere (total 3-phase) mva a mega volt-ampere (phase a) mva b mega volt-ampere (phase b) mva c mega volt-ampere (phase c) mvar mega var (total 3-phase) mvar a mega var (phase a) mvar b mega var (phase b) mvar c mega var (phase c) mvarh mega var-hour mw megawatt(s) ...

  • Page 683

    Edr-3000 im02602003e pe protected earth pf power factor (total 3-phase) pf a power factor (phase a) pf b power factor (phase b) pf c power factor (phase c) ph phase pos positive press pressure pri, pri primary prot, prot protection module (master module), protection ps1 parameter set 1 ps2 parameter...

  • Page 684

    Edr-3000 im02602003e rst reset rtd resistance-temperature detector rx (rx) receive, receiver s second s sensitive sat ct saturation sc supervision contact sca scada scada communication module, supervisory control and data acquistion sec second(s) sec, sec secondary sens sensitive seq sequence sig. S...

  • Page 685

    Edr-3000 im02602003e toc time overcurrent tov time overvoltage trans transient tripcmd trip command tx (tx) transmit, transmitter txt text uc undercurrent ul underwriters laboratories umz deft (definite time tripping characteristic) urtd universal resistance-temperature detector usb universal serial...

  • Page 686

    Edr-3000 im02602003e vts voltage transformer supervision w watt(s) wdc watch dog contact (supervision contact) wdg winding wh watthour www world wide web x reactance xct 4 th current measuring input (ground or neutral current) xinv inverse characteristic z impedance, zone www.Eaton.Com 674.

  • Page 687

    Edr-3000 im02602003e instantaneous current curves (phase) explanation: www.Eaton.Com 675 t = tripping delay i = fault current pickup = if the pickup value is exceeded, the module/element starts to time out to trip . T [s] pickup i 1 10 0.01 0.1 1 10 100 1 10 0.01 0.1 1 10 100 tt 40 40 3 00 s 3 00 s ...

  • Page 688

    Edr-3000 im02602003e time current curves (phase) the following characteristics are available: ninv (iec/ xinv ); vinv (iec/ xinv ); linv (iec/ xinv ); einv (iec/ xinv ); minv (ansi/ xinv ); vinv (ansi/ xinv ); einv (ansi/ xinv ); thermal flat; therm flat it; therm flat i2t; and therm flat i4t. Expla...

  • Page 689

    Edr-3000 im02602003e www.Eaton.Com 677 t-multiplier x * pickup (multiples of pickup) trip reset t = 0.14 *t-multiplier [s] pickup -1 i ( ) 2 t = 0.14 *t-multiplier [s] pickup -1 i ( ) 0.02 t [s] notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . Ie...

  • Page 690

    Edr-3000 im02602003e www.Eaton.Com 678 t [s] t-multiplier t = 13.5 *t-multiplier [s] pickup -1 i ( ) t = 13.5 *t-multiplier [s] pickup -1 i ( ) 2 trip reset x * pickup (multiples of pickup) notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . Iec vin...

  • Page 691

    Edr-3000 im02602003e www.Eaton.Com 679 t [s] t-multiplier t = 120 *t-multiplier [s] pickup -1 i ( ) 2 t = 120 *t-multiplier [s] pickup -1 i ( ) trip reset x * pickup (multiples of pickup) notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . Iec linv.

  • Page 692

    Edr-3000 im02602003e www.Eaton.Com 680 t [s] t-multiplier t = 80 *t-multiplier [s] pickup -1 i ( ) 2 t = 80 *t-multiplier [s] pickup -1 i ( ) 2 trip reset x * pickup (multiples of pickup) notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . Iec einv.

  • Page 693

    Edr-3000 im02602003e www.Eaton.Com 681 t [s] t-multiplier t = 4.85 *t-multiplier [s] pickup -1 i ( ) 2 t = 0.0515 *t-multiplier [s] pickup -1 i ( ) 0.02 + 0.1140 ( ) trip reset x * pickup (multiples of pickup) notice! Various reset modes are available . Resetting via characteristic, delayed, and ins...

  • Page 694

    Edr-3000 im02602003e www.Eaton.Com 682 t [s] t-multiplier trip reset x * pickup (multiples of pickup) t = 19.61 *t-multiplier [s] pickup -1 i ( ) 2 + 0.491 ( ) t = 21.6 *t-multiplier [s] pickup -1 i ( ) 2 notice! Various reset modes are available . Resetting via characteristic, delayed, and instanta...

  • Page 695

    Edr-3000 im02602003e www.Eaton.Com 683 t [s] t-multiplier t = 29.1 *t-multiplier [s] pickup -1 i ( ) 2 trip reset x * pickup (multiples of pickup) t = 28.2 *t-multiplier [s] pickup -1 i ( ) 2 + 0.1217 ( ) notice! Various reset modes are available . Resetting via characteristic, delayed, and instanta...

  • Page 696

    Edr-3000 im02602003e www.Eaton.Com 684 t [s] t-multiplier x * in (multiples of the nominal current) trip reset t = 5*3 *t-multiplier [s] 2 in i ( ) 0 t = 5*1 *t-multiplier [s] in i ( ) 0 2 notice! Various reset modes are available . Resetting via characteristic, delayed , and instantaneous . Therm f...

  • Page 697

    Edr-3000 im02602003e www.Eaton.Com 685 t [s] t-multiplier x * in (multiples of the nominal current) trip reset t = 5*3 *t-multiplier [s] 2 in i ( ) 0 notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . It t = 5*3 *t-multiplier [s] 1 in i ( ) 1 0.01 ...

  • Page 698

    Edr-3000 im02602003e www.Eaton.Com 686 0.01 0.1 1 10 100 0.01 0.1 1 10 100 1 10 3 × 1 10 4 × tm[s]= 10 5 2 1.0 0.5 0.05 t [s] t-multiplier x * in (multiples of the nominal current) trip reset t = 5*3 *t-multiplier [s] 2 in i ( ) 0 notice! Various reset modes are available . Resetting via characteris...

  • Page 699

    Edr-3000 im02602003e www.Eaton.Com 687 t [s] t-multiplier x * in (multiples of the nominal current) trip reset t = 5*3 *t-multiplier [s] 2 in i ( ) 0 notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . I4t t = 5*3 *t-multiplier [s] in i ( ) 4 4 0.01...

  • Page 700

    Edr-3000 im02602003e instantaneous current curves (ground current calculated) the following characteristics is available: deft (definite time). Explanation: the ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can...

  • Page 701

    Edr-3000 im02602003e www.Eaton.Com 689 t [s] 1 10 0.01 0.1 1 10 100 1 10 0.01 0.1 1 10 100 i/i> tt 40 20 300 s 300 s 0.0 s 0.0 s 0.01 0.01 pickup ir calc pickup ir calc deft.

  • Page 702

    Edr-3000 im02602003e instantaneous current curves (ground current measured) the following characteristics is available: deft (definite time). Explanation: the ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can a...

  • Page 703

    Edr-3000 im02602003e www.Eaton.Com 691 t [s] 1 10 0.01 0.1 1 10 100 1 10 0.01 0.1 1 10 100 i/i> tt 40 20 300 s 300 s 0.0 s 0.0 s 0.01 0.01 pickup ix pickup ix deft.

  • Page 704

    Edr-3000 im02602003e time current curves (ground current) the following characteristics are available: ninv (iec/ xinv ); vinv (iec/ xinv ); linv (iec/ xinv ); einv (iec/ xinv ); minv (ansi/ xinv ); vinv (ansi/ xinv ); einv (ansi/ xinv ); thermal flat; therm flat it; therm flat i2t; and therm flat i...

  • Page 705

    Edr-3000 im02602003e www.Eaton.Com 693 t-multiplier t = 0.14 *t-multiplier [s] pickup -1 ig ( ) 0.02 trip reset t = 0.14 *t-multiplier [s] pickup -1 ig ( ) 2 x * pickup (multiples of pickup) t [s] notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . ...

  • Page 706

    Edr-3000 im02602003e www.Eaton.Com 694 t [s] t-multiplier trip reset x * pickup (multiples of pickup) t = 13.5 *t-multiplier [s] pickup -1 ig ( ) 2 t = 13.5 *t-multiplier [s] pickup -1 ig ( ) notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . Iec v...

  • Page 707

    Edr-3000 im02602003e www.Eaton.Com 695 t [s] t-multiplier x * pickup (multiples of pickup) trip reset t = 120 *t-multiplier [s] pickup -1 ig ( ) t = 120 *t-multiplier [s] -1 ig ( ) 2 pickup notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . Iec lin...

  • Page 708

    Edr-3000 im02602003e www.Eaton.Com 696 t [s] t-multiplier x * pickup (multiples of pickup) trip reset t = 80 *t-multiplier [s] pickup -1 ig ( ) 2 t = 80 *t-multiplier [s] pickup -1 ig ( ) 2 notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . Iec ein...

  • Page 709

    Edr-3000 im02602003e www.Eaton.Com 697 t [s] t-multiplier x * pickup (multiples of pickup) t = 0.0515 *t-multiplier [s] pickup -1 ig ( ) 0.02 + 0.1140 ( ) t = 4.85 *t-multiplier [s] -1 ig ( ) 2 pickup trip reset notice! Various reset modes are available . Resetting via characteristic, delayed, and i...

  • Page 710

    Edr-3000 im02602003e www.Eaton.Com 698 t [s] t-multiplier x * pickup (multiples of pickup) trip reset t = 21.6 *t-multiplier [s] -1 ig ( ) 2 pickup t = 19.61 *t-multiplier [s] pickup -1 ig ( ) 2 + 0.491 ( ) notice! Various reset modes are available . Resetting via characteristic, delayed, and instan...

  • Page 711

    Edr-3000 im02602003e www.Eaton.Com 699 t [s] t-multiplier x * pickup (multiples of pickup) trip reset t = 28.2 *t-multiplier [s] pickup -1 ig ( ) 2 + 0.1217 ( ) t = 29.1 *t-multiplier [s] -1 ig ( ) 2 pickup notice! Various reset modes are available . Resetting via characteristic, delayed, and instan...

  • Page 712

    Edr-3000 im02602003e www.Eaton.Com 700 t [s] t-multiplier trip reset t = 5*1 *t-multiplier [s] 2 ig ( ) 0 ignom x * in (multiples of the nominal current) notice! Various reset modes are available . Resetting via characteristic, delayed , and instantaneous . Therm flat t = 5 *t-multiplier [s] ignom i...

  • Page 713

    Edr-3000 im02602003e www.Eaton.Com 701 t [s] t-multiplier trip reset x * in (multiples of the nominal current) t = 5*1 *t-multiplier [s] 2 ig ( ) 0 ignom notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . It t = 5*1 *t-multiplier [s] ignom ig ( ) 1...

  • Page 714

    Edr-3000 im02602003e www.Eaton.Com 702 t [s] t-multiplier trip reset x * in (multiples of the nominal current) t = 5*1 *t-multiplier [s] 2 ig ( ) 0 ignom notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . I2t t = 5*1 *t-multiplier [s] ignom ig ( ) ...

  • Page 715

    Edr-3000 im02602003e www.Eaton.Com 703 t [s] t-multiplier trip reset x * in (multiples of the nominal current) t = notice! Various reset modes are available . Resetting via characteristic, delayed, and instantaneous . I4t t = 5*1 *t-multiplier [s] ignom ig ( ) 4 4 5*1 *t-multiplier [s] 2 ignom ig ( ...

  • Page 716

    Edr-3000 im02602003e assignment list the » assignment list « below summarizes all module outputs (signals) and inputs (e.G.: states of the assignments). Name description -.- no assignment prot.Available signal: protection is available. Prot.Active signal: active prot.Exblo signal: external blocking ...

  • Page 717

    Edr-3000 im02602003e name description bkr.Ces fail tripcmd signal: command execution supervision: command execution failed because trip command is pending. Bkr.Ces switchgdir signal: command execution supervision respectivly switching direction control: this signal becomes true, if a switch command ...

  • Page 718

    Edr-3000 im02602003e name description bkr.Isum intr trip: ia signal: maximum permissible summation of the interrupting (tripping) currents exceeded: ia bkr.Isum intr trip: ib signal: maximum permissible summation of the interrupting (tripping) currents exceeded: ib bkr.Isum intr trip: ic signal: max...

  • Page 719

    Edr-3000 im02602003e name description 50p[1].Adaptset3-i module input state: adaptive parameter3 50p[1].Adaptset4-i module input state: adaptive parameter4 50p[2].Active signal: active 50p[2].Exblo signal: external blocking 50p[2].Rvs blo signal: reverse blocking 50p[2].Blo tripcmd signal: trip comm...

  • Page 720

    Edr-3000 im02602003e name description 50p[3].Pickup signal: pickup 50p[3].Trip phase a signal: general trip phase a 50p[3].Trip phase b signal: general trip phase b 50p[3].Trip phase c signal: general trip phase c 50p[3].Trip signal: trip 50p[3].Tripcmd signal: trip command 50p[3].Defaultset signal:...

  • Page 721

    Edr-3000 im02602003e name description 51p[1].Adaptset 4 signal: adaptive parameter 4 51p[1].Exblo1-i module input state: external blocking1 51p[1].Exblo2-i module input state: external blocking2 51p[1].Exblo tripcmd-i module input state: external blocking of the trip command 51p[1].Rvs blo-i module ...

  • Page 722

    Edr-3000 im02602003e name description 51p[3].Exblo signal: external blocking 51p[3].Rvs blo signal: reverse blocking 51p[3].Blo tripcmd signal: trip command blocked 51p[3].Exblo tripcmd signal: external blocking of the trip command 51p[3].Pickup ia signal: pickup ia 51p[3].Pickup ib signal: pickup i...

  • Page 723

    Edr-3000 im02602003e name description 50x[1].Adaptset 3 signal: adaptive parameter 3 50x[1].Adaptset 4 signal: adaptive parameter 4 50x[1].Exblo1-i module input state: external blocking1 50x[1].Exblo2-i module input state: external blocking2 50x[1].Exblo tripcmd-i module input state: external blocki...

  • Page 724

    Edr-3000 im02602003e name description 51x[1].Trip signal: trip 51x[1].Tripcmd signal: trip command 51x[1].Defaultset signal: default parameter set 51x[1].Adaptset 1 signal: adaptive parameter 1 51x[1].Adaptset 2 signal: adaptive parameter 2 51x[1].Adaptset 3 signal: adaptive parameter 3 51x[1].Adapt...

  • Page 725

    Edr-3000 im02602003e name description 50r[1].Exblo signal: external blocking 50r[1].Rvs blo signal: reverse blocking 50r[1].Blo tripcmd signal: trip command blocked 50r[1].Exblo tripcmd signal: external blocking of the trip command 50r[1].Pickup signal: pickup ix or ir 50r[1].Trip signal: trip 50r[1...

  • Page 726

    Edr-3000 im02602003e name description 50r[2].Adaptset1-i module input state: adaptive parameter1 50r[2].Adaptset2-i module input state: adaptive parameter2 50r[2].Adaptset3-i module input state: adaptive parameter3 50r[2].Adaptset4-i module input state: adaptive parameter4 51r[1].Active signal: acti...

  • Page 727

    Edr-3000 im02602003e name description 51r[2].Adaptset 4 signal: adaptive parameter 4 51r[2].Exblo1-i module input state: external blocking1 51r[2].Exblo2-i module input state: external blocking2 51r[2].Exblo tripcmd-i module input state: external blocking of the trip command 51r[2].Rvs blo-i module ...

  • Page 728

    Edr-3000 im02602003e name description zi.Ground trip signal: zone interlocking ground trip zi.Pickup signal: pickup zone interlocking zi.Trip signal: zone interlocking trip zi.Tripcmd signal: zone interlocking trip command zi.Phase out signal: zone interlocking phase out zi.Ground out signal: zone i...

  • Page 729

    Edr-3000 im02602003e name description exp[1].Alarm signal: alarm exp[1].Trip signal: trip exp[1].Tripcmd signal: trip command exp[1].Exblo1-i module input state: external blocking1 exp[1].Exblo2-i module input state: external blocking2 exp[1].Exblo tripcmd-i module input state: external blocking of ...

  • Page 730

    Edr-3000 im02602003e name description exp[4].Trip signal: trip exp[4].Tripcmd signal: trip command exp[4].Exblo1-i module input state: external blocking1 exp[4].Exblo2-i module input state: external blocking2 exp[4].Exblo tripcmd-i module input state: external blocking of the trip command exp[4].Ala...

  • Page 731

    Edr-3000 im02602003e name description ar.Ready signal: ready to shoot ar.Running signal: auto reclosing running ar.T-dead signal: dead time between trip and reclosure attempt ar.Bkr close cmd signal: bkr. Switch on (close) command ar.T-run2ready signal: examination time: if the breaker remains after...

  • Page 732

    Edr-3000 im02602003e name description ar. 2 abort the ar-cycle, if the state of the assigned signal is true. If the state of this function is true the ar will be aborted. Ar. 3 abort the ar-cycle, if the state of the assigned signal is true. If the state of this function is true the ar will be abort...

  • Page 733

    Edr-3000 im02602003e name description di-8p x1.Di 2 signal: digital input di-8p x1.Di 3 signal: digital input di-8p x1.Di 4 signal: digital input di-8p x1.Di 5 signal: digital input di-8p x1.Di 6 signal: digital input di-8p x1.Di 7 signal: digital input di-8p x1.Di 8 signal: digital input ro-3zi x2....

  • Page 734

    Edr-3000 im02602003e name description waveform rec.Man. Trigger signal: manual trigger waveform rec.Start1-i state of the module input:: trigger event / start recording if: waveform rec.Start2-i state of the module input:: trigger event / start recording if: waveform rec.Start3-i state of the module...

  • Page 735

    Edr-3000 im02602003e name description iec61850.Virtinp10 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp11 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp12 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp13 signal: virtual input (iec61850 ggio ind) iec61850.Virtinp14...

  • Page 736

    Edr-3000 im02602003e name description iec61850.Virtout15-i module input state: binary state of the virtual output (ggio) iec61850.Virtout16-i module input state: binary state of the virtual output (ggio) iec61850.Virtout17-i module input state: binary state of the virtual output (ggio) iec61850.Virt...

  • Page 737

    Edr-3000 im02602003e name description sntp.Sntp active signal: if there is no valid sntp signal for 120 sec, sntp is regarded as inactive. Statistics.Resfc all signal: resetting of all statistic values (current demand, power demand, min, max) statistics.Resfc i demand signal: resetting of statistics...

  • Page 738

    Edr-3000 im02602003e name description logic.Le4.Gate in1-i state of the module input: assignment of the input signal logic.Le4.Gate in2-i state of the module input: assignment of the input signal logic.Le4.Gate in3-i state of the module input: assignment of the input signal logic.Le4.Gate in4-i stat...

  • Page 739

    Edr-3000 im02602003e name description logic.Le8.Gate in2-i state of the module input: assignment of the input signal logic.Le8.Gate in3-i state of the module input: assignment of the input signal logic.Le8.Gate in4-i state of the module input: assignment of the input signal logic.Le8.Reset latch-i s...

  • Page 740

    Edr-3000 im02602003e name description logic.Le12.Gate in3-i state of the module input: assignment of the input signal logic.Le12.Gate in4-i state of the module input: assignment of the input signal logic.Le12.Reset latch-i state of the module input: reset signal for the latching logic.Le13.Gate out ...

  • Page 741

    Edr-3000 im02602003e name description logic.Le16.Gate in4-i state of the module input: assignment of the input signal logic.Le16.Reset latch-i state of the module input: reset signal for the latching logic.Le17.Gate out signal: output of the logic gate logic.Le17.Timer out signal: timer output logic...

  • Page 742

    Edr-3000 im02602003e name description logic.Le20.Reset latch-i state of the module input: reset signal for the latching logic.Le21.Gate out signal: output of the logic gate logic.Le21.Timer out signal: timer output logic.Le21.Out signal: latched output (q) logic.Le21.Out inverted signal: negated lat...

  • Page 743

    Edr-3000 im02602003e name description logic.Le25.Gate out signal: output of the logic gate logic.Le25.Timer out signal: timer output logic.Le25.Out signal: latched output (q) logic.Le25.Out inverted signal: negated latched output (q not) logic.Le25.Gate in1-i state of the module input: assignment of...

  • Page 744

    Edr-3000 im02602003e name description logic.Le29.Timer out signal: timer output logic.Le29.Out signal: latched output (q) logic.Le29.Out inverted signal: negated latched output (q not) logic.Le29.Gate in1-i state of the module input: assignment of the input signal logic.Le29.Gate in2-i state of the ...

  • Page 745

    Edr-3000 im02602003e name description logic.Le33.Out signal: latched output (q) logic.Le33.Out inverted signal: negated latched output (q not) logic.Le33.Gate in1-i state of the module input: assignment of the input signal logic.Le33.Gate in2-i state of the module input: assignment of the input sign...

  • Page 746

    Edr-3000 im02602003e name description logic.Le37.Out inverted signal: negated latched output (q not) logic.Le37.Gate in1-i state of the module input: assignment of the input signal logic.Le37.Gate in2-i state of the module input: assignment of the input signal logic.Le37.Gate in3-i state of the modu...

  • Page 747

    Edr-3000 im02602003e name description logic.Le41.Gate in1-i state of the module input: assignment of the input signal logic.Le41.Gate in2-i state of the module input: assignment of the input signal logic.Le41.Gate in3-i state of the module input: assignment of the input signal logic.Le41.Gate in4-i ...

  • Page 748

    Edr-3000 im02602003e name description logic.Le45.Gate in2-i state of the module input: assignment of the input signal logic.Le45.Gate in3-i state of the module input: assignment of the input signal logic.Le45.Gate in4-i state of the module input: assignment of the input signal logic.Le45.Reset latch...

  • Page 749

    Edr-3000 im02602003e name description logic.Le49.Gate in3-i state of the module input: assignment of the input signal logic.Le49.Gate in4-i state of the module input: assignment of the input signal logic.Le49.Reset latch-i state of the module input: reset signal for the latching logic.Le50.Gate out ...

  • Page 750

    Edr-3000 im02602003e name description logic.Le53.Gate in4-i state of the module input: assignment of the input signal logic.Le53.Reset latch-i state of the module input: reset signal for the latching logic.Le54.Gate out signal: output of the logic gate logic.Le54.Timer out signal: timer output logic...

  • Page 751

    Edr-3000 im02602003e name description logic.Le57.Reset latch-i state of the module input: reset signal for the latching logic.Le58.Gate out signal: output of the logic gate logic.Le58.Timer out signal: timer output logic.Le58.Out signal: latched output (q) logic.Le58.Out inverted signal: negated lat...

  • Page 752

    Edr-3000 im02602003e name description logic.Le62.Gate out signal: output of the logic gate logic.Le62.Timer out signal: timer output logic.Le62.Out signal: latched output (q) logic.Le62.Out inverted signal: negated latched output (q not) logic.Le62.Gate in1-i state of the module input: assignment of...

  • Page 753

    Edr-3000 im02602003e name description logic.Le66.Timer out signal: timer output logic.Le66.Out signal: latched output (q) logic.Le66.Out inverted signal: negated latched output (q not) logic.Le66.Gate in1-i state of the module input: assignment of the input signal logic.Le66.Gate in2-i state of the ...

  • Page 754

    Edr-3000 im02602003e name description logic.Le70.Out signal: latched output (q) logic.Le70.Out inverted signal: negated latched output (q not) logic.Le70.Gate in1-i state of the module input: assignment of the input signal logic.Le70.Gate in2-i state of the module input: assignment of the input sign...

  • Page 755

    Edr-3000 im02602003e name description logic.Le74.Out inverted signal: negated latched output (q not) logic.Le74.Gate in1-i state of the module input: assignment of the input signal logic.Le74.Gate in2-i state of the module input: assignment of the input signal logic.Le74.Gate in3-i state of the modu...

  • Page 756

    Edr-3000 im02602003e name description logic.Le78.Gate in1-i state of the module input: assignment of the input signal logic.Le78.Gate in2-i state of the module input: assignment of the input signal logic.Le78.Gate in3-i state of the module input: assignment of the input signal logic.Le78.Gate in4-i ...

  • Page 757

    Edr-3000 im02602003e name description sys.Maint mode inactive signal: arc flash reduction maintenance inactive sys.Maintmode manually signal: arc flash reduction maintenance manual mode sys.Maint mode comm signal: arc flash reduction maintenance comm mode sys.Maint mode di signal: arc flash reductio...

  • Page 758

    Edr-3000 im02602003e special assignment list for all digital input signals and all logic outputs name description -.- no assignment di-4p x1.Di 1 signal: digital input di-4p x1.Di 2 signal: digital input di-4p x1.Di 3 signal: digital input di-4p x1.Di 4 signal: digital input di-8p x1.Di 1 signal: di...

  • Page 759

    Edr-3000 im02602003e name description logic.Le6.Out signal: latched output (q) logic.Le6.Out inverted signal: negated latched output (q not) logic.Le7.Gate out signal: output of the logic gate logic.Le7.Timer out signal: timer output logic.Le7.Out signal: latched output (q) logic.Le7.Out inverted si...

  • Page 760

    Edr-3000 im02602003e name description logic.Le15.Out inverted signal: negated latched output (q not) logic.Le16.Gate out signal: output of the logic gate logic.Le16.Timer out signal: timer output logic.Le16.Out signal: latched output (q) logic.Le16.Out inverted signal: negated latched output (q not)...

  • Page 761

    Edr-3000 im02602003e name description logic.Le25.Gate out signal: output of the logic gate logic.Le25.Timer out signal: timer output logic.Le25.Out signal: latched output (q) logic.Le25.Out inverted signal: negated latched output (q not) logic.Le26.Gate out signal: output of the logic gate logic.Le2...

  • Page 762

    Edr-3000 im02602003e name description logic.Le34.Timer out signal: timer output logic.Le34.Out signal: latched output (q) logic.Le34.Out inverted signal: negated latched output (q not) logic.Le35.Gate out signal: output of the logic gate logic.Le35.Timer out signal: timer output logic.Le35.Out signa...

  • Page 763

    Edr-3000 im02602003e name description logic.Le43.Out signal: latched output (q) logic.Le43.Out inverted signal: negated latched output (q not) logic.Le44.Gate out signal: output of the logic gate logic.Le44.Timer out signal: timer output logic.Le44.Out signal: latched output (q) logic.Le44.Out inver...

  • Page 764

    Edr-3000 im02602003e name description logic.Le52.Out inverted signal: negated latched output (q not) logic.Le53.Gate out signal: output of the logic gate logic.Le53.Timer out signal: timer output logic.Le53.Out signal: latched output (q) logic.Le53.Out inverted signal: negated latched output (q not)...

  • Page 765

    Edr-3000 im02602003e name description logic.Le62.Gate out signal: output of the logic gate logic.Le62.Timer out signal: timer output logic.Le62.Out signal: latched output (q) logic.Le62.Out inverted signal: negated latched output (q not) logic.Le63.Gate out signal: output of the logic gate logic.Le6...

  • Page 766

    Edr-3000 im02602003e name description logic.Le71.Timer out signal: timer output logic.Le71.Out signal: latched output (q) logic.Le71.Out inverted signal: negated latched output (q not) logic.Le72.Gate out signal: output of the logic gate logic.Le72.Timer out signal: timer output logic.Le72.Out signa...

  • Page 767

    Edr-3000 im02602003e name description logic.Le80.Out signal: latched output (q) logic.Le80.Out inverted signal: negated latched output (q not) list of the digital inputs the following list comprises all digital inputs. This list is used in various protective elements (e.G. Tcs...). The availability ...

  • Page 768

    Edr-3000 im02602003e list of ansi codes eee c 37.2:2008 ansi functions 14 underspeed 24 overexcitation protection (volts per hertz) 25 synchronizing or synchronism-check via 4 th measuring channel of voltage measurement card 27 undervoltage protection 27(t) undervoltage (time dependent) protection 2...

  • Page 769

    Edr-3000 im02602003e ansi functions 66 starts per h (start inhibit) 67 directional overcurrent 67n directional neutral overcurrent 67ns sensitive directional neutral overcurrent 74tc trip circuit supervision 78v vector surge protection 79 auto reclosure 81 frequency protection 81u underfrequency pro...

  • Page 770

    Instruction leaflet effective 18.06.14 edr-3000 this instruction leaflet is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized eaton sales representative. The sale of the product shown in this lit...