Eaton IM01005012E Instruction Manual - 2 I

Manual is about: Eaton Electrical Power Supply Instruction Manual

Summary of IM01005012E

  • Page 1

    Effective date 2/2007 for more information visit: www.Itvss.Com contents page 1 introduction ............................................................................. 1 1.1 scope......................................................................... 1 1.2 xt-40 catalog numbering system...........

  • Page 2: Http://www.Itvss.Com/

    Im01005012e xt-40 & it-rss installation page a rev. 1 – 2/2007 register your warranty on-line at http://www.Itvss.Com/ notice: product improvements and enhancements are continuous; therefore the specifications and information contained in this document may change without notice. Eaton corporation sh...

  • Page 3: 1 I

    Xt-40 & it-rss installation im01005012e rev. 1 – 2/2007 page 1 1 i ntroduction 1.1 scope this installation manual contains the information necessary to install eaton corporation’s xt-40 and it-rss surge protective devices (spds). System wiring and voltage information for these devices are provided i...

  • Page 4

    Im01005012e xt-40 & it-rss installation page 2 rev. 1 – 2/2007 1.4 safety precautions a licensed/qualified electrician must complete all instructions and measurements described in this instruction in accordance with the u.S. National electrical code, state and local codes, or other applicable countr...

  • Page 5: 2 I

    Xt-40 & it-rss installation im01005012e rev. 1 – 2/2007 page 3 2 i nstallation 2.1 before installation perform or plan the following before installing the spd: 1. Locate your electrical system’s applicable wiring diagram in sections 2.2 & 2.3 2. Verify that your electrical system’s voltage and wirin...

  • Page 6

    Im01005012e xt-40 & it-rss installation page 4 rev. 1 – 2/2007 2.2 xt-40 wiring diagrams single phase (1p101, 1p201) circuit interrupt device phase a ground netural or phase b use interrupt device if connected to phase b not neutral xt-40 split phase (1s101) circuit interrupt device phase a neutral ...

  • Page 7

    Xt-40 & it-rss installation im01005012e rev. 1 – 2/2007 page 5 2.3 it-rss wiring diagram split phase – 288 vac phase to phase max. It-rss circuit interrupt device phase a ground phase b 2.4 installing circuit interrupt devices the spd must be connected to the electrical system through a 30 a circuit...

  • Page 8

    Im01005012e xt-40 & it-rss installation page 6 rev. 1 – 2/2007 2.5 conduit installation when planning the conduit installation, avoid using 90° elbows and keep the conduit run as short and straight as possible. See figure 2-1. When applicable, use weatherproof (corrosion resistant) conduit and fitti...

  • Page 9

    Xt-40 & it-rss installation im01005012e rev. 1 – 2/2007 page 7 figure 2-2. Xt-40 & it-rss mounting dimensions 2.40 (61.0) 1.77 (45.0) 3.15 (80.0) 2.48 (63.0) 4.17 (105.9) 3.23 (82.0) 4.73 (120.1) 5.58 (141.7) 4.80 (121.9) 3.15 (80.0) 0.25 (6.4) m ounting hole shafts m ounting holes under lid (4) 0.7...

  • Page 10

    Im01005012e xt-40 & it-rss installation page 8 rev. 1 – 2/2007 2.8 power up and system checkout apply system power and observe that the led(s) on the front of the spd should glow. One led should glow for each phase voltage being monitored. Should there be a significant difference in brightness, chec...

  • Page 11

    Xt-40 & it-rss installation im01005012e rev. 1 – 2/2007 page 9 notes:.

  • Page 12

    Eaton corporation 1000 cherrington parkway moon township, pa 15108-4312 usa http://www.Itvss.Com © 2007 eaton corporation for additional information please call: all rights reserved power quality technical support center publication no. Im01005012e 1-800-809-2772 rev. 1 – february 2007.