- DL manuals
- Eaton
- Industrial Electrical
- MTL7700
- Instruction Manual
Eaton MTL7700 Instruction Manual
Summary of MTL7700
Page 1
Mtl7700 range shunt-diode safety barriers september 2017 inm 7700 rev 12 instruction manual mtl intrinsic safety solutions.
Page 2
Ii inm 7700 rev 12 declaration of conformity a printed version of the declaration of conformity has been provided separately within the original shipment of goods. However, you can find a copy of the latest version at http://www.Mtl-inst.Com/certificates note the following mtl7700 range of shunt dio...
Page 3
Iii inm 7700 rev 12 declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ii note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 4
Iv inm 7700 rev 12 iv atex safety instructions the following information is in accordance with the essential health and safety requirements (annex ii) of the eu directive 2014/34/eu [the atex directive - safety of apparatus] and is provided for those locations where the atex directive is applicable....
Page 5
1 inm 7700 rev 12 mtl7700 range shunt-diode safety barriers figure 1: mtl7700 range of shunt-diode safety barriers 1 overview this instruction manual contains all information needed to install, maintain, fault-find and test mtl7700 range of shunt-diode safety barriers. Section 3 includes a checklist...
Page 6
2 inm 7700 rev 12 2 .3 mtl7700 range – accessories mtl7700 range of barriers mount directly onto din-rail. A comprehensive selection of mounting, tagging, power and earthing accessories is available. Installation details are given in section 4.3. Essential accessories the following are usually consi...
Page 7
3 inm 7700 rev 12 figure 3: mtl7700 range of earthing accessories note: module earth terminals may be used for cable screen earth connections. See figure 17 erb57o nickel-plated offset earth-rail bracket, supplied with two push fasteners, one 14mm earth-rail clamp and one 9mm earth clamp 2 . Erl7 ni...
Page 8
4 inm 7700 rev 12 figure 4: dimensions (mm) of an mtl7700 range of barrier tagging accessories section 4 .3 .5, 4 .3 .6 power links section 4 .3 .7, 4 .3 .8 4 .3 .1 din-rail (thr2 and thr7000) eaton can supply both standard (thr2) and plated (thr7000) low- profile t-section din-rail. Although standa...
Page 9
5 inm 7700 rev 12 figure 5: clearance for accessories note : for high profile (15mm) din rail, add 7.5mm to vertical dimension 1 2 3 1 2 figure 6: clamping an mtl7700 range of barrier on to a din-rail figure 7: removing an mtl7700 range of barrier from a din-rail 250mm low-profile rail (7.5mm) high-...
Page 10
6 inm 7700 rev 12 high - profile din rail or low - profile din rail 2 off m4 x 16 m6 x 16 50mm 62mm 14.6mm 20mm figure 9: mounting isp7000 insulating spacers etl7000 earth terminal clamping screw earth terminal screws figure 10: mounting an etl7000 din-rail earth terminal figure 11: installing a th7...
Page 11
7 inm 7700 rev 12 5 wiring connections 5 .1 general this section describes wiring connections as follows: a) barrier connections section 5.2 b) connections to plant earth section 5.3 c) connections to dummy barriers section 5.4 5 .2 barrier connections each barrier has 4 or 8 terminals, 2 or 4 on ea...
Page 12
8 inm 7700 rev 12 5 .3 .2 earthing an installation see figure 15. Connections from the din-rail to a suitable plant earth are made from etl7000 earth terminals. These clip onto the din-rail as described in section 4.3.3 to make the vital earth connection with the rail and the barriers. They are prov...
Page 13
9 inm 7700 rev 12 5 .3 .5 bonding practice when hazardous-area equipment cannot meet prescribed insulation standards where hazardous-area equipment is connected to earth (either directly or indirectly) and/or it will not withstand a 500v insulation test to ground or the alternative described in sect...
Page 14
10 inm 7700 rev 12 check that: a) barriers are of the types and polarities specified in the safety documentation. B) the barriers are attached securely and correctly to the din-rail to make sure the earth connection is safe. C) there are no apparent signs of damage or corrosion to the barriers, the ...
Page 15
11 inm 7700 rev 12 7 .2 power supply check check that the power supply to an individual barrier circuit (or to an mtl7798 power feed module or an mtl7799 dummy barrier sourcing the power bus ) is functional and that the voltage across the supply with respect to earth is correct. For example, in figu...
Page 16
12 inm 7700 rev 12 12 8 .2 .2 multimeter tests see tables 4 to 10. The use of a digital multimeter for testing barriers is described in section 7. The tables assume that the multimeter is set to a suitable Ω range for the end-to-end resistance tests (except for diode return channels) and for the con...
Page 17
13 inm 7700 rev 12 input output line fault open circuit open closed short circuit closed closed 620Ω closed open 10kΩ open open 8 .3 .3 .2 testing mtl7742 barriers the mtl7742 is a single channel switch/prox input barrier with an open collector solid state interface to the safe area equipment. To ve...
Page 18
14 inm 7700 rev 12 8 .4 test tables for passive barriers tables 4 to 10 detail the tests for all mtl7700 range of ‘passive’ barriers. In the ‘diode test’ columns, the figures adjacent to the diode description indicate the number of forward-biased diodes used in the barrier chain. Using the multimete...
Page 19
15 inm 7700 rev 12 table 6: single channel table 7: dual-channel ac barriers table 9: dual-channel star-connected ac barriers table 8: 2/3 channel low voltage ac barriers note: vf d is the voltage dropped by a forward biased rectifier diode - 0.6v typically barrier data multimeter tests constant-cur...
Page 20
16 inm 7700 rev 12 table 10: diode return barriers note: vf z is the voltage dropped by a forward biased zener diode - 0.6v typically barrier data multimeter tests constant-current tests model no . Safety description end-to-end resistance Ω diode test +ve diode test -ve terminal voltage @ 10µa termi...
Page 21
17 inm 7700 rev 12 appendix a: typical wiring connections for specific applications . Hazardous area hazardous area figure a1: 2- wire transmitters hazardous area figure a5: 2-channel switch inputs hazardous area figure a6: low-level analogue inputs (rtd’s) figure a2: 2- wire transmitters with 250Ω ...
Page 22
18 inm 7700 rev 12 hazardous area safe area 3 4 1 2 mtl7728+ 3 4 1 2 mtl7787+ mtl7787p+ 3 4 1 2 mtl7787+ mtl7787p+ figure a9: analogue output hazardous area safe area 3 4 1 2 +7v 3 4 1 2 mtl7761ac mtl7764ac 3 4 1 2 mtl7761ac --7v 0v output (mv) sense + — figure a13: strain-gauge bridges hazardous ar...
Page 23
19 inm 7700 rev 12 model no . V Ω ma mtl7706+ 28 300 93 mtl7707+ 28 300 93 28 - mtl7707p+ 28 164 171 28 - mtl7710+/- 10 50 200 mtl7715+ 15 100 150 mtl7715p+ 15 50 291 mtl7722+/- 22 150 147 mtl7728+ 28 300 93 mtl7728– 28 300 93 mtl7728ac 28 300 93 mtl7728p+ 28 234 119 mtl7729p+ 28 164 170 mtl774x 10 ...
Page 24
Europe (emea): +44 (0)1582 723633 mtlenquiry@eaton.Com the americas: +1 800 835 7075 mtl-us-info@eaton.Com asia-pacific: +65 6 645 9888 sales.Mtlsing@eaton.Com the given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the i...