Eaton MX Frame 15000 RT Installation And User Manual - 3. Operation

Manual is about: Pulsar Series

Summary of MX Frame 15000 RT

  • Page 1

    Www.Eaton.Com installation and user manual mx frame 15000 rt 20000 rt pulsar series.

  • Page 2: Introduction

    34008486en/ac - page 3 introduction environmental protection eaton has implemented an environmental-protection policy. Products are developed according to an eco-design approach. Substances this product does not contain cfcs, hcfcs or asbestos. Packing to improve waste treatment and facilitate recyc...

  • Page 3: Introduction

    34008486en/ac - page 4 introduction pictograms important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audio signal. In the illustrations on the following pages, the symbols below are used: led off led on.

  • Page 4: Contents

    34008486en/ab - page 5 contents 1. Presentation 1.1 wheels position ............................................................................................................................. 8 1.2 rack position .........................................................................................

  • Page 5: Contents

    34008486en/ab - page 6 contents 2.7 connections of input/output power cables ..............................................................................23 input connection ..........................................................................................................................23 ...

  • Page 6: Contents

    34008486en/ab - page 7 contents 6. Life cycle monitoring (lcm) 6.1 description ................................................................................................................................... 38 get free offers .........................................................................

  • Page 7: 1. Presentation

    34008486en/ac - page 8 1. Presentation wheels position rack position sub-modules dimensions (h x w x d) mx frame 15 000 rt/ 20 000 rt (on wheels) 688x445x738 mm 27 x 18 x 29 inches weights mx frame 71 kg 157 lbs mx frame 15 000 rt 194 kg 428 lbs mx frame 20 000 rt 239 kg 527 lbs dimensions (h x w x ...

  • Page 8: 1. Presentation

    34008486en/ac - page 9 1. Presentation rear panels mx frame 15000 rt / 20000 rt (1) normal ac source input switch (2) single phase or three-phase input selection (3) residual-current earth-leakage circuit breaker 30ma for pdu1 and pdu2 (4) groups of 2 (10a) outlets for connection of equipment (5) gr...

  • Page 9: 1. Presentation

    34008486en/ac - page 10 1. Presentation display and control panel sub-module pictograms on display (1) load protected led (2) downgraded operation led (3) load not protected led (4) alphanumeric display (a) upper line exists, access by (6) (b) lower menu exists, access by (8) (c) active line (d) low...

  • Page 10: 1. Presentation

    34008486en/ac - page 11 1. Presentation battery extension mx frame offers a standard backup time of 5 minutes at full load. To increase backup time up to 62 minutes (at full load), it is possible to connect mx exb rt modules to the upss. Battery extensions for mx frame mx exb rt (optional battery mo...

  • Page 11: 2. Installation

    34008486en/ac - page 12 2. Installation unpacking and contents check unpacking contents check keep the packaging parts for wheels removal. ( (1) mx frame 15 000 rt or 20 000 rt ups. (2) solution-pac power management suite cd-rom. (3) product documentation. (4) rack mounting kit (5) screw driver. (6)...

  • Page 12: 2. Installation

    34008486en/ac - page 13 2. Installation rack mounting wheels removal rack mounting kit the battery sub-modules and power sub-modules must no be mounted yet. It is not allowed to install the ups or battery module in a hermetically closed environment without any exchange of air. 1 - use packaging as s...

  • Page 13: 2. Installation

    34008486en/ac - page 14 2. Installation ups module rack mounting the battery sub-modules and power sub-modules must no be mounted yet. It is not allowed to install the ups or battery module in a hermetically closed environment without any exchange of air. Follow steps 1 to 4 for rack mounting the up...

  • Page 14: 2. Installation

    34008486en/ac - page 15 2. Installation mounting sub-modules a dangerous voltage is present inside the power module and the battery module. Any operations to be carried out on these modules must be done by qualified staff. You must mount the modules from the lowest level to the highest level. All th...

  • Page 15: 2. Installation

    34008486en/ac - page 16 2. Installation communication ports mx rt provides 3 communication methods that can be used simultaneously: ◗ 2 com ports provide rs232 or usb communications using eaton shut protocol. Compatible with most power management software applications available into the enclosed sol...

  • Page 16: 2. Installation

    34008486en/ac - page 17 2. Installation installation of communication card remote power off communication port it is not necessary to shutdown the ups before installing a communications card. 1 - remove the slot cover (1) secured by two screws. 2 - insert the communication card (2) in the slot. 3 - ...

  • Page 17: 2. Installation

    34008486en/ac - page 18 2. Installation required protective devices and cable cross-sections recommended upstream protection recommended downstream protection required cable cross-sections ◗ terminal-block cable capacity: 25 mm², solid or stranded wire (maximum 25 mm² or awg 2). ◗ capacity for earth...

  • Page 18: 2. Installation

    34008486en/ac - page 19 2. Installation installation depending on the system earthing arrangement (sea) single phase input ups with common normal and bypass ac inputs main low- voltage switchboard (mlvs) load change in sea between upstream and downstream or galvanic isolation required main low- volt...

  • Page 19: 2. Installation

    34008486en/ac - page 20 2. Installation ups with separate normal and bypass ac inputs, supplied by separate sources mlvs 1 mlvs 2 mlvs 1 mlvs 2 load load change in sea between upstream and downstream or galvanic isolation required mlvs 1 mlvs 2 load frequency converter (without bypass ac input) conf...

  • Page 20: 2. Installation

    34008486en/ac - page 21 2. Installation three phases input mx frame must be fed from a 3-phase source with neutral. Ups with common normal and bypass ac inputs main low- voltage switchboard (mlvs) load change in sea between upstream and downstream or galvanic isolation required main low- voltage swi...

  • Page 21: 2. Installation

    34008486en/ac - page 22 2. Installation ups with separate normal and bypass ac inputs, supplied by separate sources mlvs 1 mlvs 2 mlvs 1 mlvs 2 load load change in sea between upstream and downstream or galvanic isolation required mlvs 1 mlvs 2 load frequency converter (without bypass ac input) conf...

  • Page 22: 2. Installation

    34008486en/ac - page 23 2. Installation connections of input/output power cables input connection access to terminal block this type of connection must be carried out by qualified electrical personnel before carrying out any connection, check that the upstream protection device normal ac source is o...

  • Page 23: 2. Installation

    34008486en/ac - page 24 2. Installation single phase input this type of connection must be carried out by qualified electrical personnel common sources separate sources 1 - be sure that the one-phase metal strap is installed 2 - be sure that the metal jumper is installed 3 - connect the 3 cables to ...

  • Page 24: 2. Installation

    34008486en/ac - page 25 2. Installation three phases input this type of connection must be carried out by qualified electrical personnel common sources separate sources 1 - remove the one-phase metal strap (1) 2 - be sure that the metal jumper (2) is installed 3 - connect the 5 cables to the normal ...

  • Page 25: 2. Installation

    34008486en/ac - page 26 2. Installation fix the terminal block cover this type of connection must be carried out by qualified electrical personnel 1 - push up the moving tray (1). 2 - push in the moving tray (1). 3 - fix the 2 screws of the terminal block cover (2). 1 1 2 1 3 2.

  • Page 26: 2. Installation

    34008486en/ac - page 27 2. Installation extended battery (exb) connections connection of iec cables to output receptacles this type of connection must be carried out by qualified electrical personnel it is not necessary to shutdown the ups in order to install the extended battery (exb) module. Up to...

  • Page 27: 3. Operation

    34008486en/ac - page 28 3. Operation initial start-up final start-up sequence it is essential to contact our customer service to ensure that your system is commissionned in complete safety and to benefit from the manufacturer’s guarantee. 1 - be sure that the manual bypass switch (1) is in normal po...

  • Page 28: 3. Operation

    34008486en/ac - page 29 3. Operation operating modes normal mode battery mode when the normal ac source is not available, the load continues to be protected by the ups. Power is supplied by the battery. Transfer to battery power low battery warning end of backup time return on normal ac source after...

  • Page 29: 3. Operation

    34008486en/ac - page 30 3. Operation ups shutdown 1 - press the "0" button (1) more than 3s. The buzzer beeps once, and the load is no longer protected by the ups. It is powered via the bypass ac source. If the ups is set in frequency converter mode, the equipments will not be powered. If the normal...

  • Page 30

    34008486en/ac - page 31 4. Access to measurements and personalisation data display organisation access to measurements access to ups set-up and maintenance press the scroll button (see section 1.5, page 10) to access measurements for voltage, current, frequency, power output and battery capacity. ◗ ...

  • Page 31

    34008486en/ac - page 32 4. Access to measurements and personalisation data ups set-up local settings output settings on/off settings function factory setting options language english french, german, italian, portuguese, spanish date / time format international (dd-mm-yyyy/hh :mm) us (mm-dd-yyyy/hh:m...

  • Page 32

    34008486en/ac - page 33 4. Access to measurements and personalisation data battery settings maintenance personalisation using external software function factory setting options comments auto battery test everyweek no test / everyday / everyweek /everymonth low batt warning 20% 0 to 100% 1% increment...

  • Page 33: 5. Troubleshooting

    34008486en/ac - page 34 5. Troubleshooting troubleshooting leds if led (1) is on: the equipments are protected by the ups but the operation is downgraded. If led (2) is on: the equipments are no longer protected by the ups. Press the escape button (3) to stop the audible alarm. Note : in case of "mu...

  • Page 34: 5. Troubleshooting

    34008486en/ac - page 35 5. Troubleshooting system diagnosis fault a internal sub-module fault is detected .. Check power or battery sub-module connections (see section 7, page 39). If the connections are correct, call the after-sales support department and follow the sub-module replacement procedure...

  • Page 35: 5. Troubleshooting

    34008486en/ac - page 36 5. Troubleshooting environment faults press the "enter" button (1) to display the details below : displayed details signification correction the number of detected batteries of a level is low compared to the other levels. Check the external battery connection (detection cable...

  • Page 36: 5. Troubleshooting

    34008486en/ac - page 37 5. Troubleshooting internal faults display signification correction power module fault internal power sub-module fault detected. Use "enter" button (1) to display details. Call the after-sales support department. Follow the power sub-module replacement procedure (see section ...

  • Page 37

    34008486en/ac - page 38 6. Life cycle monitoring (lcm) description this function, embedded in the ups, displays messages, on screen and communication channels, at every important stage of the ups’s life, allowing you to: secure your installation power continuity anticipate maintenance actions thanks...

  • Page 38: 7. Maintenance

    34008486en/ac - page 39 7. Maintenance hot swapping the power sub-module disconnecting the power sub-module : reconnecting the power sub-module : hot swapping the battery sub-module disconnecting the battery sub-module : reconnecting the battery sub-module : this operation must be carried out by qua...

  • Page 39: 7. Maintenance

    34008486en/ac - page 40 7. Maintenance service position (bypass position) this operation must be carried out by qualified electrical personnel only. The equipments should be powered via the normal ac source, and not protected by the ups. 1 - press and hold the (0) (off) button (1) for 3 seconds/ the...

  • Page 40: 7. Maintenance

    34008486en/ac - page 41 7. Maintenance normal position (online mode) this operation must be carried out by qualified electrical personnel only. Return to normal position from service position (bypass position). 1 - push the red padlock in the center of the manual bypass switch (1) to unlock it 2 - s...

  • Page 41: 7. Maintenance

    34008486en/ac - page 42 7. Maintenance training centre to fully master operation of your eaton product and carry out level 1 servicing, see our complete range of technical training courses, available in both french and english. For further information, please visit our website: www.Eaton.Com.

  • Page 42: 8. Appendices

    34008486en/ac - page 43 8. Appendices technical specifications (1) if the output voltage is 200v - 250v, the output power is 15 kva / 12 kw. (2) with one exb module or more, the standard output power is 20 kva / 16 kw. (3) values for 70% / 100% of ups output. (4) programmable: 200v / 208v / 220v / 2...

  • Page 43: 8. Appendices

    34008486en/ac - page 44 8. Appendices glossary backup time time that the connected equipments can operate on battery power. Bypass ac source source supplying the bypass line. The equipments can be transferred to the bypass line if an overload occurs on the ups output, for maintenance or in the event...