Eaton powerwave 9315 Installation Manual

Manual is about: 200–300 kVA

Summary of powerwave 9315

  • Page 1

    Powerware 9315 ups 200–300 kva installation manual ®.

  • Page 2

    Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...

  • Page 3

    I eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com table of contents 1 introduction 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 using this manual 1−2 . . . . . . . . . ...

  • Page 4

    Table of contents ii eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com list of figures figure 1-1. Typical powerware 9315 ups system 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 2-1. Cabinet as shipped, ...

  • Page 5

    1−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 1 introduction this manual describes how to install your powerware ® 9315 uninterruptible power supply (ups) system. It contains instructions for installing the ups and each optional componen...

  • Page 6

    Introduction 1−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 1.1 using this manual the system you are installing dictates which parts of this manual you should read. Everyone should read chapters 1 through 3: a chapter 1 discusses installation con...

  • Page 7

    Introduction 1−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 1.3 for more information refer to the powerware 9315 ups (200–300 kva) operation manual for more information about the operation and communication capabilities of the ups system: a descr...

  • Page 8

    Introduction 1−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com this page intentionally left blank..

  • Page 9

    2−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 2 getting started each cabinet of your ups system is shipped on a separate pallet. Use a forklift or pallet jack to move the packaged cabinets to the installation site, or as close as possibl...

  • Page 10

    Getting started 2−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 2.1 preparing your site for your ups system to operate at peak efficiency, the installation site should meet the environmental specifications outlined in the powerware 9315 ups (200–3...

  • Page 11

    Getting started 2−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 2.4 inspecting and unpacking each cabinet the first task in preparing for installation is inspecting and unpacking each cabinet. Cabinets arrive covered with protective packaging mate...

  • Page 12

    Getting started 2−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com this page intentionally left blank..

  • Page 13

    3−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 3 installing the ups w a r n i n g installation should be performed by qualified personnel. Refer to the following while installing the ups: a dimensions in this manual are in millimeters and...

  • Page 14

    Installing the ups 3−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com see figure 3-1 before installing the ups cabinet. The ups cabinet base is equipped with forklift slots to accommodate lifting and moving the equipment. The forklift slots are locat...

  • Page 15

    Installing the ups 3−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 2 1 1 2 1 ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓÓ ÓÓ...

  • Page 16

    Installing the ups 3−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 3.2 prepare for installing optional cabinets or accessories if you are installing optional cabinets or accessories, such as a power distribution module cabinet, an input transforme...

  • Page 17

    Installing the ups 3−5 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ...

  • Page 18

    Installing the ups 3−6 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 3.3 completing the installation checklist the final step in installing the ups system is completing the following installation checklist. This checklist ensures that you have compl...

  • Page 19

    Installing the ups 3−7 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com installation checklist - all packing materials and restraints have been removed from each cabinet. - each cabinet in the ups system is placed in its installed location. - a ground ...

  • Page 20

    Installing the ups 3−8 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com notes _________________________________________________________________________ _________________________________________________________________________ __________________________...

  • Page 21

    4−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 4 installing battery cabinets this chapter describes installing the ups manufacturer’s battery cabinets. If you are installing battery cabinets and remote disconnects provided by powerware, r...

  • Page 22

    Installing battery cabinets 4−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com w a r n i n g a do not dispose of battery or batteries in a fire. The battery may explode. A do not open or mutilate the battery or batteries. Released electrolyte is harm...

  • Page 23

    Installing battery cabinets 4−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 4.2 recycling the used battery or ups contact your local recycling or hazardous waste center for information on proper disposal of the used battery or ups. W a r n i n g a...

  • Page 24

    Installing battery cabinets 4−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com this page intentionally left blank..

  • Page 25

    5−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 5 installing input and output transformers before installing optional input and output transformers, be sure you have prepared the ups according to the instructions in chapter 3, installing t...

  • Page 26

    Installing input and output transformers 5−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com top view customer input area front view figure 5-2. Input transformer cabinet (208/480v).

  • Page 27

    Installing input and output transformers 5−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com top view customer input area (top) front view figure 5-3. Output transformer cabinet (480/208v).

  • Page 28

    Installing input and output transformers 5−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com to prepare the input and output transformer cabinets for wiring to the ups: 1. Install the ups into final operating position. 2. Install the cabinets into fin...

  • Page 29

    Installing input and output transformers 5−5 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com table 5-2. Rectifier input transformer connection points (dual feed) connection point in transformer cabinet connection point in ups phase input output ∅ a e2...

  • Page 30

    Installing input and output transformers 5−6 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com e23 ac output to ups ÓÓÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓÓÓ ac input to transformer e24 e25 e26 e27 e28 in in in out out out a ∅ b ∅ c ∅ a ∅ b ∅ c ∅ front figure 5-4. Instal...

  • Page 31

    Installing input and output transformers 5−7 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com ac output to ups ac input to transformer e23 e24 e25 e26 e27 e28 e22 e29 input neutral output neutral front figure 5-5. Installing a 208/480 vac input transfo...

  • Page 32

    Installing input and output transformers 5−8 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com ac output to ups ac input to transformer e23 e24 e25 e26 e27 e28 neutral ground front figure 5-6. Installing a 480/208 vac output transformer cabinet.

  • Page 33

    6−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 6 installing a power distribution module the pdm cabinet has one or two panels, each containing up to 42 poles for breaker switches. This arrangement provides flexibility for the needs of you...

  • Page 34

    Installing a power distribution module 6−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com this page intentionally left blank..

  • Page 35

    7−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 7 installing a remote emergency power−off the remote epo control arrives as shown in figure 7-1. For enclosure dimensions, side views, and knockout patterns, see drawing 164201037−10 on page ...

  • Page 36

    Installing a remote emergency power−off 7−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 1 tb2 2 remote epo switch twisted wires (2) figure 7-2. Remote epo note remote epo switch rating is 24 vdc, 1a minimum if supplied by user. Note this switch mu...

  • Page 37

    8−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 8 installing a remote battery disconnect the remote battery disconnect is crated separately for shipping. The enclosure is designed to be wall-mounted on a surface that can support the weight...

  • Page 38

    Installing a remote battery disconnect 8−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com a for specific ratings and wiring requirements, see table t on page a−18. A the material and labor for external wiring requirements is to be supplied by others....

  • Page 39

    9−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 9 installing a remote monitor panel as an option, you can install an rmp to monitor the operation of the ups system from virtually any location within your facility, up to 152.4m (500 ft) fro...

  • Page 40

    Installing a remote monitor panel 9−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com surface mount (for hanging) flush mount wires must be twisted figure 9-1. Remote monitor panel.

  • Page 41

    Installing a remote monitor panel 9−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com before installing an rmp, be sure you have prepared the ups according to the instructions in chapter 3. To install an rmp: 1. Securely mount the rmp(s). 2. Install w...

  • Page 42

    Installing a remote monitor panel 9−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com tb1 tb2 ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ db−9 co...

  • Page 43

    Installing a remote monitor panel 9−5 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 6. To test the indicator lamps, press the horn silence button and hold it for 3 seconds. All lamps should illuminate, and the horn sounds continuously until you rele...

  • Page 44

    Installing a remote monitor panel 9−6 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com this page intentionally left blank..

  • Page 45

    10−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 10 installing a relay interface module the optional rim uses relay contact closures to indicate the operating status and alarm condition of the ups system. The module uses an rs−232 serial i...

  • Page 46

    Installing a relay interface module 10−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com connect to port 1 (db−9) on communication panel fuse terminal block (tb3) figure 10-2. Terminal block bracket tb1 tb2 ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓ...

  • Page 47

    Installing a relay interface module 10−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 4. Connect rim wiring to the terminal block using the terminations shown in table 10-1. 5. Contact your eaton service representative for verification and testing ...

  • Page 48

    Installing a relay interface module 10−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com this page intentionally left blank..

  • Page 49

    11−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com chapter 11 installing a supervisory contact module the optional scm as shown in figure 11-1 provides contacts for monitoring ups status. A maximum of two monitoring accessories (remote monitor panel...

  • Page 50

    Installing a supervisory contact module 11−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com connect to port 1 (db−9) on communication panel fuse terminal block (tb3) figure 11-2. Terminal block bracket tb1 tb2 ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓ...

  • Page 51

    Installing a supervisory contact module 11−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 6. Repeat steps 1 through 5 for each scm you are installing. 7. If you are installing an rmp or rim in addition to an scm, proceed to chapter 9 or 10, respect...

  • Page 52

    Installing a supervisory contact module 11−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com system normal no redundancy on generator bypass not available on battery ups alarm on bypass shutdown imminent figure 11-4. Supervisory contact module tb2 not...

  • Page 53

    A−1 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com appendix a 12− customer information the information in this appendix will help you plan for and install your ups system. This appendix contains the following drawings: a 164201037−1 installation note...

  • Page 54

    Description: date: drawing no: installation notes sheet: revision: e 164201037−1 note: callout letters and map to drawing #164201037−3 , , , 113004 400v = 380/400/415 volt 1 of 17 customer information a−2 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Co...

  • Page 55

    2 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 note: callout letters and map to drawing #164201037−3 , , , e , e customer information a−3 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com table b. Input/o...

  • Page 56

    3 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 note: callout letters and map to drawing #164201037−3 , , , e f g , , , e a b c f d g customer information a−4 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware....

  • Page 57

    4 of 17 description: date: drawing no: installation notes sheet: revision: f 164201037−1 note: callout letters and map to drawing #164201037−3 , , , 051506 400v = 380/400/415 volt customer information a−5 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Co...

  • Page 58

    5 of 17 description: date: drawing no: installation notes sheet: revision: f 164201037−1 051506 note: callout letters and map to drawing #164201037−3 , , , e , e customer information a−6 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com table e. Input/o...

  • Page 59

    6 of 17 description: date: drawing no: installation notes sheet: revision: f 164201037−1 051506 note: callout letters and map to drawing #164201037−3 , , , e f g , , , e a b c f d g customer information a−7 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware....

  • Page 60

    7 of 17 description: date: drawing no: installation notes sheet: revision: c 164201037−1 121598 note: customer ground, size 2/0, can be run in any conduit listed in table g and table h. Customer information a−8 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerw...

  • Page 61

    8 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 note: customer ground, size 2/0, can be run in any conduit listed in table g. Customer information a−9 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com tabl...

  • Page 62

    9 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 customer information a−10 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 1. In the ups system, each battery cabinet, pdm cabinet, and the input transforme...

  • Page 63

    10 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 customer information a−11 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 1. Table j lists the maximum rating for input circuit breakers. Table j. Maximum...

  • Page 64

    11 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 customer information a−12 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 8. Output overcurrent protection and output disconnect switch are to be provided...

  • Page 65

    12 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 customer information a−13 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 1. Your ups equipment’s operating environment must meet the size and weight requ...

  • Page 66

    13 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 tb1 bldg alarm 1 bldg alarm 4 bldg alarm 5 1 2 3 4 5 6 7 8 9 15 10 11 14 13 12 tb2 bldg alarm 2 bldg alarm 3 bldg alarm 6 1 2 3 4 5 6 7 8 9 15 10 11 14 13 12 rs232 rs485 on bypass battery contactor close...

  • Page 67

    14 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 customer information a−15 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com table o. Communications panel inputs and outputs tb1 pin # name description 1 bl...

  • Page 68

    15 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 customer information a−16 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 1. Use class 1 wiring methods (as defined by the nec) for control wiring. Instal...

  • Page 69

    16 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 customer information a−17 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com 3. The remote epo feature opens all breakers and contactors in the ups cabinet a...

  • Page 70

    17 of 17 description: date: drawing no: installation notes sheet: revision: e 164201037−1 113004 note: for other than powerware battery cabinets that use uv trip coils, connect to tb4 pin 3 instead of tb4 pin 2. 24v s.T. Rtn uv rtn dc aux dc aux rtn dc aux dc aux rtn not used not used not used tb 4 ...

  • Page 71

    Description: date: drawing no: typical ups system sheet: revision: a 164201037−2 1 of 1 020497 note: the input transformer cabinet may be installed on either the left or the right side of the ups cabinet. Battery cabinet cabinet ups (optional) input cabinet output transformer (optional) pdm cabinet ...

  • Page 72

    Customer information a−20 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com table u. Ups system oneline configurations oneline drawing 164201037−7 powerware 9315 vin / vout input transformer output transformer sheet 1 225 480/208 n/a n/a sheet 1 225, 30...

  • Page 73

    1 of 4 ups cabinet battery critical load cabinet (optional) rectifier input filter cb1 to ground ac output to e4−5 to additional battery cabinet (optional) static switch bypass contactor (k4) e9−12 on inverter" on bypass" monitoring rs−232 rs−485 remote epo generator interface ac input to ups rectif...

  • Page 74

    2 of 4 ups cabinet battery critical load cabinet (optional) rectifier input filter cb1 to ground ac output to e4−5 to additional battery cabinet (optional) static switch bypass contactor (k4) e9−12 on inverter" on bypass" monitoring rs−232 rs−485 remote epo generator interface ac input to ups rectif...

  • Page 75

    3 of 4 description: date: drawing no: sheet: revision: f oneline drawings of ups system 082806 note 2: see table u to determine when an input transformer is required. Note 1: a bypass neutral feeder must be supplied when the output neutral is used. If no bypass neu- tral is supplied, the output neut...

  • Page 76

    4 of 4 description: date: drawing no: sheet: revision: f oneline drawings of ups system 082806 note 2: see table u to determine when an input transformer is required. Note 1: a bypass neutral feeder must be supplied when the output neutral is used. If no bypass neu- tral is supplied, the output neut...

  • Page 77

    Tb1 tb2 ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓÓÓ ÓÓ...

  • Page 78

    Dimensions are in millimeters (inches) description: date: drawing no: sheet: revision: a 164201037−6 ups cabinet 1 of 2 020497 1866.1 (73.5) 733 (28.9) 484.4 (19.1) 333 (13.1) 1653.8 (65.1) customer information a−26 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.P...

  • Page 79

    Dimensions are in millimeters (inches) description: date: drawing no: sheet: revision: a 164201037−6 ups cabinet 2 of 2 020497 top bottom view view ups cabinet ups cabinet 52.9 (2.1) 35.7 (1.4) 720.7 (28.4) 568.3 (22.4) 301.6 (11.9) 21 (0.8) 50.3 (2) 29.9 (1.2) 240 (9.4) 39.3 (1.5) 756 (29.8) 454 (1...

  • Page 80

    ÓÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓÓ door swing 624.8 (24.60) x 90 degrees 952.50 (37.50) cable top 838.51 (33.01) 374.95 (14.75) 117.48 (4.63) top view bottom view front front 25.4 (1.00) 914.4 (36.00) minimum clearance for subassembly removal 1853.87 (73.00) dimensions are in millimeters (inches) description: da...

  • Page 81

    Top view dimensions are in millimeters (inches) description: date: drawing no: sheet: revision: c 2 of 3 121598 front view transformer cabinets input isolation transformer cabinet (208/480) side view 449.5 (17.7) 282 (11.1) 91 (3.6) 1021 (40.2) 1211.4 (47.7) 1203 (47.4) 1870 (73.6) 26 (1) 200 (7.9) ...

  • Page 82

    Top view dimensions are in millimeters (inches) description: date: drawing no: sheet: revision: c 3 of 3 121598 front view transformer cabinets side view 449.5 (17.7) 282 (11.1) 91 (3.6) 1021 (40.2) 1211.4 (47.7) 1203 (47.4) 1870 (73.6) 26 (1) 200 (7.9) 200 (7.9) 200 (7.9) 1200 (47.2) 713.4 (28.1) 2...

  • Page 83

    Description: date: drawing no: sheet: revision: d 164201037−8 1 of 1 041500 42-pole panelboard with main breaker 225a 600v square d type nqom442m225ig−nl branches−qo plug-on and qob bolt-on circuit breaker. 15−70a, 1-pole; 15−100a 2- and 3-pole; 125a, 2-pole. Grounding stud grounding stud ∅a e1 ∅b e...

  • Page 84

    Description: date: drawing no: sheet: revision: d 1 of 1 041500 maintenance bypass module Á Á Á mbp mis bib1 bib2 breaker annunciation critical load connections neutral connections optional ups bypass input connections utility input, if bib breaker installed ups/ptc output connection utility input, ...

  • Page 85

    114.3 (4.50) 115.8 (4.56) 11.9 (0.47) 95.3 (3.75) square 88.9 (3.50) knockout pattern typ. 5 sides to ups to other equipment dimensions are in millimeters (inches) description: date: drawing no: sheet: revision: d 164201037−10 remote emergency power off 1 of 1 041500 customer information a−33 eaton ...

  • Page 86

    Max. Wire size: no. 14 awg min. Wire size: no. 18 awg wires must conduit and wiring supplied by customer. Max. Distance between remote monitor and ups not to exceed 500 feet. 41.1 (1.62) 25.4 (1.00) 190.5 (7.50) 88.9 (3.50) 215.9 (8.50) 100.1 (3.94) 74.7 (2.94) 171.5 (6.75) knockouts provided on fiv...

  • Page 87

    19.0 (.750) 28.6 (1.12) 41.1 (1.62) existing internal flush mount surface mount continues at ups max wire size no. 14 awg. Min wire size no. 18 awg. Relay interface module 88.9 (3.50) 190.5 (7.50) 215.9 (8.5) 196.8 (7.75) for hanging wiring conduit and wiring supplied by customer. Maximum distance b...

  • Page 88

    15−pin d−sub connectors 25.4 (1.00) knockouts provided on five surfaces 285.7 (11.25) 273.1 (10.75) 215.9 (8.50) 171.5 (6.75) 74.6 (2.94) 100.0 (3.94) dimensions are in millimeters (inches) description: date: drawing no: sheet: revision: d 164201037−12 relay interface module 2 of 2 041500 customer i...

  • Page 89

    Max. Wire size: no. 14 awg min. Wire size: no. 18 awg wires must conduit and wiring supplied by customer. Max. Distance between remote monitor and ups not to exceed 500 feet. 41.1 (1.62) 25.4 (1.00) 190.5 (7.50) 88.9 (3.50) (7.75) 215.9 (8.50) 100.1 (3.94) 74.7 (2.94) 171.5 (6.75) knockouts provided...

  • Page 90

    Description: date: drawing no: sheet: revision: a 164201037−14 battery disconnect switch 1 of 2 010198 enclosure has no knockouts. Knockouts to be determined at time of installation. Enclosure for k1200 breakers weight 75 lbs (34 kg) customer information a−38 eaton powerware ® 9315 ups (200–300 kva)...

  • Page 91

    Description: date: drawing no: sheet: revision: a 164201037−14 battery disconnect switch 2 of 2 010198 type k1200 breaker outline customer information a−39 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com.

  • Page 92

    Customer information a−40 eaton powerware ® 9315 ups (200–300 kva) installation manual s 164201037 rev g www.Powerware.Com this page intentionally left blank..

  • Page 94

    *164201037g* 164201037 g.