Eaton PSG120E Installation Instructions - page 2
IL00912002E
TECHNICAL DATA FOR PSG120E
Input (AC)
Nominal input voltage
100-240 VAC
Voltage range
85-264 VAC (DC input range 120-375 VDC)
Frequency
47-63 Hz (0 Hz @ DC input)
Nominal current
1.4 A @ 115 VAC, 0.8 A @ 230 VAC
Inrush current limitation. I
2
t (+25 °C) typ.
< 80 A @ 115 VAC
Mains buffering at nominal load (typ.)
> 35 ms @ 115 VAC, > 70 ms @ 230 VAC
Turn-on time
< 1 sec.
Internal fuse
T 3.15 AH / 250 V
Recommended backup fuse
6 A, 10 A or 16 A
Power circuit-breaker characteristic
B
Leakage current
< 1 mA
Output (DC)
Nominal output voltage UN / tolerance
24 VDC ± 2 %
Adjustment range of the voltage
22-28 VDC
Nominal current
5 A
Derating above +50 °C
2.5 % / K.
Startup with capacitive loads
Max. 10,000 µF
Max. power dissipation idling / nominal load approx.
22.5 W
Efficiency (at 400V AC and nominal values)
> 84 % typical
Residual ripple/ peak switching (20 MHz) (at nominal values)
< 50 mV / < 240 mVpp
Parallel operation
With oring diode
General Data
Type of housing
Aluminium (Al5052)
Signals
Green LED DC OK
MTBF
> 800,000 hrs.
Dimensions (L x W x H)
121 mm x 50 mm x 118. 2 mm
Weight
0.54 kg
Connection method
Screw connection
Stripping length
7 mm or use suitable lug to crimp
Operating temperature
-20 °C to +75°C (> 50°C derating)
Storage temperature
-25 °C to +85 °C
Humidity at +25 °C, no condensation
< 95 % RH
Vibration (operating)
10 to 150 Hz, 0.35 mm acc. 50 m / s², single
amplitude (5 G max.) for 90 min. in each X, Y & Z
directions, in acc. with IEC 68-2-6
Pollution degree
2
Climatic class
3K3 according to EN 60721
Certification and Standards
Electrical equipments of machines
IEC60204-1 (over voltage category III)
Electronic equipment for use in electrical power installations
EN 50178 / IEC62103
Safety entry low voltage
PELV (EN 60204), SELV (EN 60950)
Electrical safety (of information technology equipment)
EN60950-1 (GS-mark),
UL/C-UL recognized to UL60950-1, CSA C22.2 No.60950-1, CB
scheme to IEC60950-1,
cCSAus to UL60950-1 and CSA C22.2 No.60950-1
(file no.181564)
Industrial control equipment
UL / C-UL listed to UL508 and CSA C22.2 No.107.1-01
CSA to CSA C22.2 No.107.1-01 (file no.181564)
Protection against electric shock
DIN 57100-410
CE
In conformance with EMC directive 2004/108/EC and low
voltage directive 2006/95/EC
ITE
EN55022, EN61000-3-2, EN61000-3-3, EN55024
Industrial
EN55011
Limitation of mains harmonic currents
EN61000-3-2
RoHS Compliant
Yes
Safety and Protection
Transient surge voltage protection
VARISTOR
Current limitation at short-circuits approx.
I
surge
= 150 % of Po
max
typically
Surge voltage protection against internal surge voltages
Yes
Isolation voltage:
Input / output (type test/routine test)
Input / PE (type test/routine test)
Output / PE (type test/routine test)
4 kVAC / 3 kVAC
1.5 kVAC / 1.5 kVAC
1.5 kVAC / 500 VAC
Protection degree
IPX0
Safety class
Class I with PE connection
Shock (in all directions)
30 G (300 m/s²) in all directions according to IEC 68-2-27