6. POWER & CONTROL CONNECTIONS Cont
6.1
Wiring-up the Unit
Electrical terminations should be made onto the screw terminal side of the outdoor unit terminal blocks.
6.2 Wiring
Requirements
Power supply – Connection of isolation power supply to the outdoor unit.
Interconnecting Wiring – Power and signal cables run between outdoor and indoor unit.
Details of the fuse ratings and cable requirements are given in the tables in Section 5 Page 7,
of this manual.
Note: On units with 3-phase power supplies, ensure the 3 phases are connected in the
correct rotation ie L1, L2, L3. If the phase rotation is incorrect, the compressor will fail
to pump and will likely be noisy. If this is the case, two phases will need to be
swapped over to achieve correct rotation.
6.3 Terminations
Details of cable terminations and interconnections are given in Table 6.1.
6.4
Wiring Diagrams
These are fitted to the inside of the access door.
SPECIAL NOTES :
REFER TO KIT INSTRUCTIONS FOR ELECTRICAL CONNECTION OF SITE OPTION KITS!!
DO NOT MEGGER OR FLASH TEST WITH ELECTRONIC PCB’S IN CIRCUIT!!
INDOOR AND OUTDOOR UNITS SHOULD HAVE LOCAL ELECTRICAL ISOLATORS.