Eaton xiria series User Manual - page 36
Xiria
36
994.570 G01 06
Options
665417
Scissor type interlock, used in combination with a padlock inserted in the
access hole for the vacuum Interrupter. It prevents switching ON and it
prevents the operation of the change-over switch.
107926
Padlock, used in combination with the scissor type interlock and for
padlocking the earth interlock on the front.
107079
Warning sign, used when a panel is switched ON in earthed position and
any further manual operation is not allowed.
Rear cover, used when the switch room has no rear internal arc exhaust
channel.
E6055889
Adapter WIC1-PC3.
Used to connect the WIC1-1PE protection relay to a computer (laptop) via
a USB connection for setting the protection parameters or retrieving the
data stored in the relay memory. Including connection cables and
software.
E6055901
Tester type WIC1-TU.
Used for on site diagnostic test of the WIC1 protection relay.
E6046006
Phase sequence indicator type Orion 3.0.
Used for voltage test, phase sequence test and interface test of the
voltage detecting unit type WEGA. The WEGA units are used on Xiria
switchgear since December 2009.
E6046005
Phase sequence indicator type Orion Compare.
Simplified version of the Orion 3.0. Used for voltage test and phase
sequence test of the voltage detecting unit type WEGA. These voltage
indication units are used on Xiria switchgear since December 2009.
E6046007
Functional tester for WEGA voltage detecting units. The WEGA units are
used on Xiria switchgear since December 2009.
Summary of xiria series
Page 1
Xiria product family user manual 994.570 g01 06 user manual xiria product family 994.570 g01 06 eaton industries (netherlands) b.V. P.O. Box 23, 7550 aa hengelo, the netherlands tel: +31 74 246 91 11 e-mail: info.Electric@eaton.Com internet: www.Eaton.Eu/electrical service emergency eaton - electric...
Page 2
2 994.570 g01 06 administrative data issue number: g01 06 date of issue: 12-11-2013 translation of: checked by job title: product manager name: a.R.A. Pikkert / b. Ter hedde date: initials:.
Page 3
Xiria 994.570 g01 06 3 contents 1. General ............................................................................................... 5 1.1 explanation of used warnings .............................................................................. 5 1.2 safety relating to medium-voltage install...
Page 4
Xiria 4 994.570 g01 06 4.4 signals ................................................................................................................. 29 4.4.1 voltage detectors .................................................................................................. 29 4.4.2 overcurrent indi...
Page 5
Xiria 994.570 g01 06 5 1. General the user must have authority to perform switching operations, which means being qualified in accordance with locally applicable guidelines, government legislation and in-house company regulations with respect to the operation of medium-voltage installations. Legal a...
Page 6
Xiria 6 994.570 g01 06 1.4 product standards and guidelines used table 1: current product standards used standard title iec62271-1 common specifications for high-voltage switchgear and control gear standards iec62271-100 high-voltage alternating-current circuit-breakers iec62271-102 alternating curr...
Page 7
Xiria 994.570 g01 06 7 current transformer iec 61869-2 type: ctb 90 make: eaton 75/5 a 5 va l1-l2-l3 cl. 0,2 ext. 120% / a va cl. 0,2 ext. 120% / a va cl. 0,2 ext. 120% i p 50 a i k 20 ka t k 3 s current transformer iec 61869-2 type: wic1-w3h1 make: eleq s1 – s2 28,8/0,075 a l1 – l2 – l3 0.1 va cl. ...
Page 8
Xiria 8 994.570 g01 06 busbar system: rated normal current a ----------------------630----------------------------------- rated short-time withstand current ka-s 20-1 20-1 20-1 20-1 20-1 rated short time withstand current alternative ka-s 20-3 20-3 20-3 20-3 20-3 rated peak withstand current ka 50 5...
Page 9
Xiria 994.570 g01 06 9 table 2: explanation oftype plate data in accordance with iec variable description unit system - r. Release - iec iec reference - type type switching device - serial no. Serial number - year of man. Year of manufacturing - w.O.No. Works order number - f r rated frequency hz i ...
Page 10
Xiria 10 994.570 g01 06 2. Xiria system description 2.1 xiria system description the xiria switchgear panels are available for applications up to 24kv. The system is fully metal enclosed and a highly compact and safe unit is achieved using high-quality internal insulation. All live primary component...
Page 11
Xiria 994.570 g01 06 11 2.2 cross-section, single line diagram and list of functions 1 cable connected to the busbar cable connected to earth figure 2-1: panel cross-sections and single line diagrams 1. Viewing window 2. Earth contact change-over switch 3. Busbar contact change-over switch 4. Main b...
Page 12
Xiria 12 994.570 g01 06 2.3 technical specifications, general item explanation specification weight of the heaviest transport unit nett (kg) gross (kg) see delivery note for the exact value 1 panel 320 350 2 panels 350 380 2 panels with plinth 410 440 3 panels 430 460 3 panels with plinth 520 550 4 ...
Page 13
Xiria 994.570 g01 06 13 3. Installing the unit 3.1 environmental requirements 3.1.1 transport, assembly and storage conditions if the temperature and humidity conditions specified in the order cannot be guaranteed during the transport, assembly and storage of the unit, preventive measures must be ta...
Page 14
Xiria 14 994.570 g01 06 3.2.1 lifting w arning the person in charge of lifting the xiria unit must hold a certificate issued by the relevant authorities to certify that he/she is authorised to carry out these operations. After installation the lifting equipment (1) must not be removed. 3.2.2 travell...
Page 15
Xiria 994.570 g01 06 15 3.2.3 preparation prior to installation the location of the unit is required to meet the conditions stated in par. 3.1.2. 1. Remove the packaging and check the contents. 2. Remove the doors of the left- and right-hand panels, see figure 3-4. T ip the door can only be removed ...
Page 16
Xiria 16 994.570 g01 06 3.2.4 setting up the unit the xiria system has been designed in accordance with the recommendations set out in iec 62271-200 which theoretically prevents internal faults from occurring. Moreover, when set up correctly, a xiria unit will comply with this iec standard for setti...
Page 17
Xiria 994.570 g01 06 17 table 4: short-circuit capacity in relation to cable cones used cone type en 50181 i [a] maximum short-circuit current plug type cable type load-break switch c 630 3.6-24kv 20ka-3s bolted t-plug m16 cu/al xlpe cu/al xlpe circuit- breaker a 200 3.6-24kv 20ka-0,4s plug type l p...
Page 18
Xiria 18 994.570 g01 06 assembly steps if current transformers are installed around the primary cable the same steps should be followed as described at the standard assembly. For easy connection of the primary cables the current transformers in the cable compartment can be removed and remounted. For...
Page 19
Xiria 994.570 g01 06 19 3.3.3 replacing the cable connection cone damaged cable connection cones can be easily replaced by our service department. A different type of cone can also be fitted in the circuit-breaker panel at a later stage. Two types are available, a and c in accordance with en 50181. ...
Page 20
Xiria 20 994.570 g01 06 3.4 connection of station earthing the xiria unit can be connected either to the left or to the right of the station earthing. An earth bar, to which the earth screens of the power cables and the system earth can be connected, is located at the rear of every cable connection ...
Page 21
Xiria 994.570 g01 06 21 procedure (xiria e with top-unit) 1. Open top-unit with key. 2. The secondary compartment is now accessible, see figure 3-15. Procedure (xiria metering panel) 1. Open integrated low voltage compartment, see figure 3-16. 2. The secondary compartment is now accessible. Figure 3...
Page 22
Xiria 22 994.570 g01 06 4. Operation 4.1 details of control panel the xiria unit is equipped with two types of control panel, one for the load-break switch panel and one for the circuit- breaker panel. Figure 4-1 provides a summary of the control units on the control panels. 1. Earthed position inte...
Page 23
Xiria 994.570 g01 06 23 3. Remove the handle and check that the position indicator (9) of the change-over switch indicates the busbar position. 4. Turn the selector anti-clockwise until the switch control point (5) is revealed. 5. Place the operating handle with the arrow pointing up in the switch c...
Page 24
Xiria 24 994.570 g01 06 4.2.2 switch cable earthing on/off in the operating position, the cable is connected to the main busbar of the unit; the switch is on and the change- over switch is in the busbar position. Initial position: in the neutral position (see figure 4-5): the switch is off, see swit...
Page 25
Xiria 994.570 g01 06 25 5. When the arrows and dots are not visible then check the operation of the voltage detection using the voltage detection tester (18) see figure 4-9: a. Insert the tester plugs in the contact sockets “earth” and l1. Test the detector by pressing the tester button. The tested ...
Page 26
Xiria 26 994.570 g01 06 procedure 1. Switch on the integrated cable earthing in accordance with the instructions in section 4.2.2. 2. To open the cable connection compartment: check, using the single line diagram and position indicators, whether the cable on the panel to be opened is earthed; open t...
Page 27
Xiria 994.570 g01 06 27 4.3 interlocks the xiria unit is equipped as standard with built-in interlocks to prevent accidental switching operations. These interlocks are mechanical interlocks. L ife hazard undesirable switching operations could result in the following: • danger to personnel (operating...
Page 28
Xiria 28 994.570 g01 06 4.3.3 interlock for circuit-breaker/load-break switch opening button the interlock on the opening button is to prevent the switch from being unintentionally opened. Once this interlock is in place, the flap in front of the opening button can no longer be lifted. The switch ca...
Page 29
Xiria 994.570 g01 06 29 4.4 signals the xiria unit features voltage detectors on the cable side and can be fitted with overcurrent indicators and trip indicators as options. 4.4.1 voltage detectors the xiria unit features voltage detectors in the control panel (12) conform iec 61243-5 with lrm inter...
Page 30
Xiria 30 994.570 g01 06 4.5 short-form instructions in these short-form instructions the following procedures are described: from closed service position to closed and locked earthed position. From closed and locked earthed position to closed service position. Figure 4-20: short-form instructions.
Page 31
Xiria 994.570 g01 06 31 5. Remote signalling and remote control t ip for correct connection and operating voltages see the circuit diagrams delivered with the unit. Remote signalling and electric remote control are available as options for xiria switchgear units. N ote remote control is suitable for...
Page 32
Xiria 32 994.570 g01 06 5.3.2 24 v dc remote closing (option) the panels concerned are provided with: auxiliary contacts as described under remote signalling; a controller; a trip coil; a closing motor; a closing pushbutton on the frontside of the panel. If the supply voltage 24 v dc, then an option...
Page 33
Xiria 994.570 g01 06 33 6. Inspection and maintenance 6.1 introduction the xiria unit is theoretically a maintenance-free system. No specific components need to be maintained. All primary, live components are maintenance-free and are housed in a sealed gas-tight enclosure. All other components have ...
Page 34
Xiria 34 994.570 g01 06 6.2.3 inspection of the moisture absorbing agent check the operation of the moisture absorbing agent in the unit with a colour indicator. This is located behind the centre viewing window of the right-hand panel (see figure 6-1). The indicator should be pale blue in colour. Un...
Page 35
Xiria 994.570 g01 06 35 7. Accessories and options 7.1 supplied accessories accessories 668251 operating handle 135 mm for on-off switching of the circuit-breaker and the load break switch and for busbar-earth position selection of the change- over switch. 668270 operating handle 510 mm needed for o...
Page 36
Xiria 36 994.570 g01 06 options 665417 scissor type interlock, used in combination with a padlock inserted in the access hole for the vacuum interrupter. It prevents switching on and it prevents the operation of the change-over switch. 107926 padlock, used in combination with the scissor type interl...
Page 37
Xiria 994.570 g01 06 37 options e6042323 short circuit indicator type sigma. It detects short-circuit currents in medium-voltage distribution networks. It consists of a display unit accommodated in a plug-in housing for panel mounting and three current transformers for short circuit sensing. 668002 ...
Page 38
Xiria 38 994.570 g01 06 options e569882 protection relay make woodward seg type wic1-2pe setting via dip switches on the front. E569884 protection relay make woodward seg type wic1-3pe setting via hex switches on the front. E6056904 protection relay make woodward seg type wib1-2pe setting via dip sw...
Page 39
Xiria 994.570 g01 06 39 appendix 1 – floor plans.
Page 40
Xiria 40 994.570 g01 06.
Page 41
Xiria 994.570 g01 06 41.
Page 42
Xiria 42 994.570 g01 06.
Page 43
Xiria 994.570 g01 06 43.
Page 44
Xiria 44 994.570 g01 06.
Page 45
Xiria 994.570 g01 06 45 appendix 2 – voltage detecting system (wega).
Page 46
Xiria 46 994.570 g01 06.
Page 47
Xiria 994.570 g01 06 47.
Page 48
Xiria 48 994.570 g01 06 appendix 3 – orion 3.0
Page 49
Xiria 994.570 g01 06 49 appendix 4 – short circuit indicator.
Page 50
Xiria 50 994.570 g01 06 appendix 5 – tariff metering 12kv a5.1 the system a5.1 standard system description the xiria system with tariff metering type ma consists of a three- or four panel switchboard with a circuit-breaker in the right panel. This circuit-breaker is provided with built-in cable side...
Page 51
Xiria 994.570 g01 06 51 a5.1.3 design specification of a switchboard with tariff metering with cable side current- and voltage transformers in the right panel: choke coil and resistor for the anti- ferro resonance filter (l20-r20) current transformers for metering phase l1, l2 and l3 (t1-t2-t3) curr...
Page 52
Xiria 52 994.570 g01 06 voltage transformers: the voltage transformers are mounted inside the switchgear at the rear. They are connected with preassembled internal primary cables to the circuit- breaker in the most right panel (number 3). Also the choke coil and the resistor for the anti ferro reson...
Page 53
Xiria 994.570 g01 06 53 a5.1.4 connection of the primary main cables and the voltage transformers: due to the limited mounting space inside the cable compartment the primary cables and the voltage transformers are connected with connectors make tyco type rsti 58. The connectors and cables for the vo...
Page 54
Xiria 54 994.570 g01 06 a5.1.6 allocation of the secondary connections for metering: the switchboard is provided with a secondary front compartment. Two thumb screws (a) are used to secure the cover in closed position. When opened the cover turns to the front and the secondary components can be acce...
Page 55
Xiria 994.570 g01 06 55.
Page 56
Xiria 56 994.570 g01 06.