Echelon HC1B Installation And Start-up Instructions Manual

Summary of HC1B

  • Page 1

    Note: read the entire instruction manual before starting the installation. Safety considerations improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a ...

  • Page 2

    Procedure 2—install on a solid, level mounting pad if conditions or local codes require the unit be attached to pad, tiedown bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in fig. 2 to determine base pan size and knockout hole location. ...

  • Page 3

    Procedure 5—make piping connections outdoor units may be connected to indoor sections using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft, consult long-line application guideline which is available at your loca...

  • Page 4

    Procedure 6—make electrical connections warning: to avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed. Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit r...

  • Page 5

    Use no. 18 awg color-coded, insulated (35°c minimum) wires. If thermostat is located more than 100 ft from unit (as measured along the control voltage wires), use no. 16 awg color-coded wires to avoid excessive voltage drop. Use furnace transformer, fan coil transformer, or accessory transformer for...

  • Page 6

    6. Set room thermostat at heat or cool and fan switch at on or auto, as desired. Operate unit for 15 minutes. Check system refrigerant charge. (see procedure 9—checking charge.) warning: relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury...

  • Page 7

    Inspection and, if required, cleaning of indoor and outdoor coils. Inspection of the indoor coil drain pan, plus the primary and secondary drain lines. If supplied, the auxiliary drain pan and line should be inspected at this time. Service should include cleaning if required. A check of all electric...

  • Page 8

    Fig. 8—typical circuit connections a91327 a91326 w 2 c l g y e o r c w 2 l g y e o r w 3 c w 2 l g y/y 2 e o r thermostat subbase indoor splice connection outdoor splice connection defrost board thermostat subbase indoor terminal board outdoor splice connection defrost board factory wiring field wir...