Connect the cable to the indoor unit
1. Indoor/Outdoor connection cable should be H07RN-F type.
2. Remove the panel and Screw, then remove the window cover.
3. Connect cables according to their marks to terminals.
4. Wrap those cables not connected with terminals with insulation tapes, so
that they will not touch any electrical components.
10mm
40mm
Terminal block of indoor unit
To outdoor unit
To outdoor unit
Cord clamp
L N S
L N S
Connect the cable to the outdoor unit
1. Remove the electric parts cover from the outdoor unit.
2. Connect the connective cables to the terminals as identified with their respective
matched numbers on the terminal block of indoor and outdoor units.
3. To prevent the ingress of water, from a loop of the connective cable as illustrated
in the installation diagram of indoor and outdoor units.
4. Insulate unused cords (conductors) with PVC-tape.Process them so they do not
touch any electrical or metal parts.
Cover
Screw
40mm
L
S
N
10mm
12
Electrical work
Fig.20
Fig.21
Window cover
Panel
Wire connector of outdoor unit
Wire -holding board
12000Btu/h
12000Btu/h
NOTE: The supply voltage must be consistent with the rate voltage of the air conditioner.
L
S
N
or
Model
Power supply
Input Rated Amp
(Switch/Fuse)
13A
16A
220-240V~ 50Hz
12000Btu/h
12000Btu/h
Minimum norminal cross-sectional
area of conductors:
Rated current
of appliance
(A)
>3 and <6
>6 and <10
>10 and <16
>16 and <25
Nominal cross-sectional
area
2
(mm )
0.75
1
1.5
2.5