Ecologix TP30 Installation Instructions Manual

Manual is about: hot water air handler

Summary of TP30

  • Page 1

    Tp-m11 installation instructions thermal-pac & thermal-duct hot water air handler ecologix heating technologies inc. 221 holiday inn dr. Cambridge, ontario n3c 3t2 phone: 519-658-4330 fax: 519-658-9384 info@ecologix.Ca www.Ecologix.Ca.

  • Page 2

    Tp-m11 table of contents important notes for the installer ..............................................................................................................3 typical plumbing connections .......................................................................................................

  • Page 3

    Tp-m11 3 important notes for the installer ) a quick check list ! Are the water connections to the water heater oriented in a way to avoid trapping air in the heating circuit? (see diagram on next page) ! Is the purge valve installed on the return line from the air handler upstream from the isolatio...

  • Page 4: Typical Plumbing Connections

    Tp-m11 4 typical plumbing connections if the water heater has side connections, use them for the air handler.

  • Page 5: Electrical Wiring Diagram

    Tp-m11 5 electrical wiring diagram air handler electrical wiring schematic air handler electrical wiring layout -- xelk103 air handler electrical wiring schematic air handler electrical wiring layout -- xelk124 with cycle timer.

  • Page 6

    Tp-m11 6 for tp75, tdhv-48 and tdhv-60 air handler electrical wiring schematic air handler electrical wiring layout -- xelk113 air handler electrical wiring schematic air handler electrical wiring layout -- xelk134.

  • Page 7

    Tp-m11 7 physical properties cabinet dimensions supply air return air water inlet shipping model type a b c d x e f x g and outlet weight tp30, tdhv-12, tdhv-18 20” 14” 24” 12”x16” 12”x16” 1/2” 80 lb. Tp45 to tp75, tdhv-24 to tdhv-60 22” 22” 31.5” 20”x20” 20”x20” 3/4” 110 lb. Unit specifications: th...

  • Page 8

    Tp-m11 8 unit specifications: thermal-duct tm air handlers model tdhv- 12 tdhv- 18 tdhv- 24 tdhv- 30 tdhv- 36 tdhv- 42 tdhv- 48 tdhv- 60 number of 3” outlets 1 8 12 15 18 22 26 30 36 cooling capacity (tons) 1.0 1.5 2.0 2.5 3.0 3.5 4.0 5.0 *heating capacity (mbh) 130f water 15 21 35 41 46 49 52 57 *h...

  • Page 9: Introduction

    Tp-m11 9 introduction thermal-pac™ and thermal-duct™ air handlers are designed for use with hydronic (boiler) systems or in combination space and water heating systems (combo systems). Combo heating systems use the home’s water heater to provide both the space heating and domestic hot water, elimina...

  • Page 10: Product Description

    Tp-m11 10 cooling, the normal heating or cooling speed will over-ride the continuous fan setting. Once the thermostat is satisfied, continuous fan speed will resume. Product description ecologix air handlers are certified by: entela inc. 81 kelfield st., unit 7 toronto, ontario m9w 5a3 ph: 416-241-8...

  • Page 11

    Tp-m11 11 all ecologix air systems come supplied with spring loaded, vertical lift check valves. These check-valves have been tested and proven to resist thermal siphoning for installations where the air handler elevation does not exceed the distance above the water heater shown in the table below. ...

  • Page 12

    Tp-m11 12 2) select a water heater with an output that is at least 120% of the heat loss duct layout make sure a proper duct design has been completed for the dwelling using hrai, ashrae or other approved design method. Supply air plenum provide a supply air plenum that is the same dimensions as the...

  • Page 13: Installation

    Tp-m11 13 installation the installer must adhere strictly to all local and national code requirements pertaining to the installation of this equipment. Detailed instructions are shipped with all accessory items and should be followed in detail. Air handler mounting the ecologix air handler can be in...

  • Page 14: Electrical

    Tp-m11 14 locate outlets at least 6 inches from outside walls or window coverings. Return ductwork return air plenum should be the same cross sectional area as the air handler return air opening. In vertical installations, a conventional return air drop and elbow is acceptable. It is recommended tha...

  • Page 15: Start-Up Procedures

    Tp-m11 15 thermostats will need 250 ohm, 10 watt resistors on each of the w and y terminals. Heat anticipator setting for optimum comfort the anticipator setting should be set to provide approximately 4 cycles per hour typical heat anticipator setting 0.25 amps thermostat wire from the thermostat is...

  • Page 16: Service and Maintenance

    Tp-m11 16 one minute. If noise is still present after one minute, repeat step 3 to purge air as necessary. 6.Check pipes for heating to make sure there is flow. Service and maintenance filter the ecologix air handler is provided with a disposable pleated filter. This filter should be inspected month...

  • Page 17

    Tp-m11 17 pump does not run in areas where hard water is present the pump may “stick” and fail to run. Often, closing the isolation valve on the return leg and opening the drain port so that water flows through the pump can free this. For grundfos pumps, remove the screw-on cover from the face of th...

  • Page 18

    Tp-m11 18 thermal-pac air handler parts & accessory list part no. Description tp30 tdhv -18 tp60 tdhv -24 tdhv -30 tp65 tdhv -36 tdhv -42 tp75 tdhv -48 tdhv -60 uc12163 hot water coil -- 12”x16” s uc18203 hot water coil – 20”x18” s s s gups15-58ruc pump- grundfos c/w check s s s s gup15-42buc5 pump-...

  • Page 19: Product Warranty

    Tp-m11 19 product warranty 221 holiday inn drive, phone: 519-658-4330 www.Ecologix.Ca cambridge, on, n3c 3t2 fax: 519-658-9384 info@ecologix.Ca this product is warranted by ecologix heating technologies inc to be free from defects in materials and workmanship that affect product performance under no...