Economite RE32 Installation And Service Instructions Manual

Summary of RE32

  • Page 1

    Midco international inc. 4140 west victoria street, chicago, illinois 60646 / (773) 604-8700 fax: (773) 604-4070 / http://www.Midco-intl.Com the economite model re32 intermittent spark ignition conversion burner is adaptable to most gas utilization equipment, including gravity and forced circulation...

  • Page 2: Installation

    Around door frames, to prevent leakage into or out of the combustion chamber. ■ the access or firing door should open easily to relieve pressure. If positive latches exist, they should be modified to permit easy opening; a spring loaded door holder is recommended. ■ on all boilers, make certain the ...

  • Page 3

    Warning: burner cabinet must be mounted in orientation shown in figures 2 and 3. Any other mountings may cause dangerous condition, and will void burner warranty and agency approvals.Non-standard arrangements may be available for some models; consult factory for details if required. ■ before permane...

  • Page 4

    -4- v electrical installation wiring and grounding of the burner must conform to local codes, or, in their absence in the united states to national electric code , ansi/nfpa no. 70-1 latest edition; in canada, to canadian electrical code part 1, csa standard c22.1 . ■ use 14 gage copper wire for lin...

  • Page 5

    Vii main gas spud standard burners are approved for use with natural or propane gas and should be used only with the gas specified on the rating plate. ■ as shipped, the installed natural gas spud has a #8 (.199) drill orifice size (propane a #25 [.149]), for an input capacity range of approximately...

  • Page 6: Service

    Part 2 service danger: be sure the manual main shut-off valve combination valve and burner power switch are turned off before removing any parts for service. -6- 11. 12. 13. 14. 15. = btu/hr = 180,000 btu/hr = 180 mbh control to off or thermostat below room temperature for at least 60 seconds. If bu...

  • Page 7

    Manifold gas pressure of 2.0" w.C. If pressure adjustment is required for setting capacity, remove regulator cap for access to slotted adjustment screw. Turning of adjustment screw counterclockwise reduces pressure; clockwise increases pressure. Do not adjust past point where no change in pressure i...

  • Page 8

    -8- trouble chart make sure the thermostat and operating controls are calling for heat. Defective wiring or loose connections can simulate the component defects outlined below. Check associated wiring before replacing a component. Electrical and flame checks must be made in the order listed. Shut of...