5.0 INSTALLATION
5.1 RECOMMENDATIONS FOR INSTALLATION
Before installing the appliance, ensure that::
1) the place of installation has sufficient space for carrying out installation
as well as routine and extraordinary maintenance work (see fig. 4).
2) There are no obstructions for air intake and delivery.
3) The water connections are of the sizes, in the position and spaced apart
as required by the appliance (see Dimension).
4) The system pressure does not exceed 8 bar for the water versions..
5) The electricity supply corresponds to the data on the appliance rating
plate and that there is a afety switch readily accessible to the user to cut
off the power supply whenever necessary.
6) The safety switch is in the OFF position so that there is no voltage on the
appliance supply line.
Fig. 07
Vertical version
Horizontal version
Before installing the appliance, remove the housing (if present). Raise
the flaps covering the control panel and the water connections. Remove
the two screws fixing the housing to the fan coil load-bearing structure.
Gipping the rear of the housing, remove it as shown in the fig. 5 (N.B.:
be careful of the lugs on the front part of the load-bearing structure,
as shown in fig. 10). Put the cabinet in the packing box to prevent it
from being soiled or damaged (fig. 6)
Offer the appliance up to the required point of installation and mark, through
the fixing holes, the points on the wall where the holes should be driller for
the 4 screw anchors, as shown in fig. 7.
5.2 FAN COIL INSTALLATION
Remove the appliance from the point of installation, drill the holes
where merked on the wall (see fig. 8) and insert the screw anchors.
Place the appliance against the wall and fix it by tightening the screws
into the anchors see (fig. 9). Carry out the water and electrical
connections as described in the relevant paragraphs. To replace the
housing,
Take the cabinet from the packing box. Standing in front of the fancoil,
lift cabi net, hold ing it by the sides, and tilt it (fig. 10).
6.0 WATER CONNECTIONS
6.1 CONNECTION TO THE WATER MAINS
CAUTION!
Always use a wrench and nose key for connection of the coil to
the pipes (fig. 12). If the valve is installed, suitably insulate the
valve body with insulating material (fig. 13).
Connect the water inlet and outlet pipes, observing the indications
given on the side of the appliance. Correctly insulate the water supply
pipes to prevent dripping during the cooling mode of operation. An
shutoff valve should be inserted on the water supply pipe and balancing
valve on the outlet pipe. The valve body and balancing valve should
also be properly insulated to prevent dripping. It is the installer's
responsibility to insulate properly and the manufacturer cannot be
held liable for any insulation work.
N. B.: It is always advisable to install the solenoid valve. In the heating
mode of operation the valve reduces consumption because upon
reaching the set temperature the circulation of water is stopped to
avoid wasting energy (the fan coil would otherwise continue to heat
like a radiator, even with the motor at a standstill). In the cooling mode
of operation the valve stops the circulation of water when the set
temperature is reached, this stopiing the internal exchanger
Insert the lugs A into the relative slots B (fig. 11). Pivot the cabinet on
its base until it is aligned with the wall. Raise the flaps covering the
control panel and water connections and tighten the two fixing screws
(fig. 5).