Faber CADRA NOVA Installation Manual And User's Manual

Other manuals for CADRA NOVA: Installation Manual And User's Manual, User Manual
Manual is about: Room-sealed built-in gas-fireplace

Summary of CADRA NOVA

  • Page 1

    Installation guide and user manual room-sealed built-in gas-fireplace 40 010 527 02 37 silence feeling whisper spectra nova cadra nova misty saturnus 8 nl-8448 cc heerenveen postbus 219 nl-8440 ae heerenveen t. +31(0)513 656500 f. +31(0)513 656501 “log burner technology”.

  • Page 2

    1 contents 1. Introduction 2 2. Safety instructions 3 3. Installation requirements 5 3.1 builders opening and surround 5 3.2 requirements outlet and exhaust 8 4. Installation-instructions 17 4.1 gas connection 17 4.2 preparation of the appliance 17 4.3 fitting the firebox 24 4.4 placing of the wood ...

  • Page 3

    Uk/irl 2 uk/irl 3 1. Introduction note: these instructions should be read carefully and retained for future reference. Please leave these instructions with the user. This guide is concerning the following types of appliances: widescreen interior: types silence and feeling roundscreen interior: type ...

  • Page 4

    Uk/irl 5 uk/irl 4 building regulations and standards issued as relevant by the department of the environment or the scottish development department. In the republic of ireland installation should be carried out in accordance with is813, icp3, is327, building regulations, codes of practice, the manuf...

  • Page 5

    L m f i c b a j e d g k h builders opening (mm) feeling silence whisper spectra cadra misty nova nova a opening width* 960 960 780 780 680 710 b opening height* 649 649 705 698 798 890 c opening depth* 385 385 430 430 430 370 shelf dimensions (combustible) d min. Height shelf from top frame 350 350 ...

  • Page 6

    Uk/irl 9 uk/irl 8 3.2 flue requirements the appliance is of the type c11/c31. The appliance will need to be supplied with the approved flue pipes and terminal, it is not possible to supply your own. The minimum effective height of the flue system must be 0.5 or 1 meter, depending on the appliance. T...

  • Page 7

    Uk/irl 0 1 2 3 4 5 6 0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x 1 30 0 0 0 0 0 0/x* 2 30 30 0 0 0 0 0 3 45 45 30 0 0 0 0 4 45 45 30 0 0 0 0 5 50 50 45 45 30 0 0 6 50 50 45 45 30 0 0 7 60 60 60 50 50 45 8 60 60 60 60 50 9 65 65 60 60 10 65 65 65 11 65 65 12 65 horizontal extension e ff...

  • Page 8

    Uk/irl 13 3.2 flue requirements (continuing) 3.2.1 terminal position verify if the required terminal position meets the local installation regulations regarding disturbance, good functioning and ventilation. (also see: safety requirements). Note: the terminal must be located so that the outlet is no...

  • Page 9

    Table 6 uk/irl 15 uk/irl 14 dimension terminal position balanced flue room sealed (kw input 7.5 kw expressed in net)natural draught a direct below an opening, airbrick, 300 mm opening windows, etc. B above an opening, airbrick, 300 mm opening window ect. C horizontally to an opening, airbrick, 300 m...

  • Page 10

    Uk/irl 17 uk/irl 16 4. Instructions for installation 4.1 gas connection 1. Installation pipes should be in accordance with bs 6891. Pipe work from the meter to the appliance must be of adequate size. 2. The complete installation including the meter must be tested for soundness and purged as describe...

  • Page 11

    Uk/irl 19 uk/irl 18 4.2 preparing the appliances widescreen and whisper (continuing) 4. Take the box with the log set out of the combustion chamber. 5. Place the right flue restrictor in the combustion chamber. To determine the right flue restrictor, see chapter 3. C c c c c c c c c c fig. 8 fig. 9 ...

  • Page 12

    Uk/irl 21 4.3 preparing the appliance misty (continuing) 4. Take the box with the log set out of the combustion chamber. 5. Place the right flue restrictor in the combustion chamber. To determine the right flue restrictor, see chapter 3. Fig. 12 uk/irl 20 4.3 preparing the appliance misty 1. Remove ...

  • Page 13

    Uk/irl 23 uk/irl 22 4.4 preparing the appliances spectra nova/cadra nova (continuing) 4. Take the box with the log set out of the combustion chamber. 5. Place the right flue restrictor in the combustion chamber. To determine the right flue restrictor, see chapter 3. Fig. 15 4.4 preparing the applian...

  • Page 14

    Uk/irl 25 uk/irl 24 4.5 fitting the firebox (continuing) 8. Spread, the bags of embers (imitation ashes) provide with the appliance over the burner tray. Attention! No embers on the grid end between the logs and the burner tray. 9. Before placing the glass; check the glass sealing rope is in good co...

  • Page 15

    Uk/irl 27 uk/irl uk/irl 5. Installation of the flue 5.1 connections with use of concentric duct material - build the system starting from the appliance on. - make a hole of ø 153 mm for the wall or roof mounted terminal. - make sure you place the pipes in the right direction, the narrow end towards ...

  • Page 16

    Uk/irl 29 uk/irl 28 uk/irl uk/irl 5.2 connection onto an existing chimney (continuing) 5. Fixing the chimney sealing plate (d) and place the 150 mm grommet into the hole of the sealing plate. 6. Fix the sealing plate air tight into the builders opening (use the isolation rope from the chimney connec...

  • Page 17

    Uk/irl 31 uk/irl 30 uk/irl uk/irl 3. Connect the wires to the gas valve (see fig. 22). 4. Check that there are batteries in the transmitter. See "replacing batteries", see chapter 10.4.4. 5. Set the on/off switch on the receiver to "on". Setting the right transmission code the receiver has to learn ...

  • Page 18

    Uk/irl 33 uk/irl 32 uk/irl uk/irl 6.3 functional balanced flue check 1. Set the appliance on max. Input. 2. Verify the flame picture, this means no flames against the window, the flame have to come besides the logs, if not check the log layout. 3. Check if the flames are yellow after 10 minutes of o...

  • Page 19

    Uk/irl 35 uk/irl 34 8. Servicing to ensure safe, efficient operation of the appliance, it is necessary to carry out routine servicing at regular intervals. It is recommended, that the fire is inspected/serviced by a competent person at least once a year. Important turn off the gas supply before comm...

  • Page 20

    Uk/irl 37 uk/irl 36 8.1.4 burner tray assembly 1. Remove the front, glass, log set, grid and burner tray cover. 2. Break the gas supply at the control valve. 3. Unscrew the burner assembly and take them out of the combustion chamber. A. Pilot assembly b. Burner c. Fixation plate d. Injector e. Gas c...

  • Page 21

    Uk/irl 39 uk/irl 38 uk/irl uk/irl 8.1.7 combustion test a bs7967 combustion analysis check should be carried out using an analyser to bs7927 positioned in the flue outlet. A ratio of co/co2 should be less than 0.01 within 30 minutes. (100ppm co per 1% co2). A reading of co in the room centre should ...

  • Page 22

    Whisper feeling silence misty spectra cadra nova nova description company company company company company company part part part part part part surround antracite a9271453 a9270053 a9267753 aa9272853 a9274149 a9274249 glass 04508200 04508300 04508300 04509000 4509500 04509300 glass below x x x x 045...

  • Page 23

    Country uk/irl uk/irl category ii 2h3+ ii 2h3+ model type c11 0f c31 c11 0f c31 heat input hi kw 7.5 7.5 efficiency class 2 2 nox class 4 4 type of gas g20 g30 inlet pressure mbar 20 30/37 gas rate 15 °c / 1013 mbar m3/h 800 231 kg/h 540 g reference burner pressure mbar 13 25 injector size mm 3x 1.5...

  • Page 24

    Uk/irl 45 uk/irl 44 uk/irl uk/irl uk/irl user guide 8.3 technical data roundscreen misty country uk/irl uk/irl category ii 2h3+ ii 2h3+ model type c11 0f c31 c11 0f c31 heat input hi kw 8,5 8,5 efficiency class 2 2 nox class 4 4 type of gas g20 g30 inlet pressure mbar 20 30 / 37 gas rate 15 °c / 101...

  • Page 25

    Uk/irl 47 uk/irl 46 important a suitable fireguard conforming to bs6539 and bs6778 should be used with this appliance to protect children, the elderly or infirm. Care should also be taken with pets. In your own interest and that of safety, all gas appliances must be installed by competent persons. I...

  • Page 26

    Uk/irl 49 uk/irl 48 knob a the { is the off position preventing any gas from passing through the control valve to either the pilot burner or to the main burner. By pressing the knob in it is possible to turn it anticlockwise. The first function is to turn on the gas to the pilot- this occurs just be...

  • Page 27

    Uk/irl 51 uk/irl 50 10.4.1 to light 1. Push in and turn the control knob (a) from { anticlockwise to the setting (small flame). You will hear a ignition click. Check that the pilot is lit (if not repeat). 2. Continue to hold in the control knob for a further ten seconds to ensure that the pilot flam...

  • Page 28

    Uk/irl 53 uk/irl 52 10.4.3 setting the right transmission code he receiver has to learn the code from the transmitter, which is already done at the factory. However the code disappears if the receiver is disconnected from the mains for a longer period, 1. Set the on/off switch on the receiver to "on...

  • Page 29

    Uk/irl 55 uk/irl 54 uk/irl uk/irl uk/irl uk/irl 12. Disposal of the packaging and the appliance the appliance packaging is recyclable. The packaging could include the following materials: - cardboard; - cfc-free foam (soft); - wood; - plastic; - paper. These materials should be disposed responsibly ...