Falcon SG1KRM-1TU Owner's Operating Manual

Manual is about: Falcon Power Supply User Manual

Summary of SG1KRM-1TU

  • Page 1

    Owner's operating manual rackmount sg series ups plus ® uninterruptible power supply models: sg1krm-1tu, sg1krm-2tu sg2krm-1tu, sg2krm-2tu sg3krm-1tu, sg3krm-2tu detailed sg series product specifications are available in pdf format at www.Falconups.Com ® 2007 falcon ® electric inc. All rights reserv...

  • Page 2

    Sg ups features. . . . . . . 1 sg series online ups block diagram. . . . . 1 important safety instructions (read first) . . . . 2 chapter 1. Sg series ups overview . . . . . 3 true regenerative online design . . . . 3 input power factor correction . . . . 3 microprocessor control . . . . . 3 snmp/ht...

  • Page 3

    Sg series ups features sg series on-line ups system block diagram true double conversion on-line design input power factor correction wide input voltage window pure sinewave output precision output voltage regulation superior brownout, surge and transient protection internal system bypass eliminates...

  • Page 4: Save These Instructions

    Important safety instructions save these instructions this manual contains important instructions which must be followed during the installation, operation and maintenance of this ups and its batteries. Please read all instructions before operating this equipment and save this manual for future refe...

  • Page 5

    Chapter chapter 1 1 sg series ups - overview true regenerative on-line design as new and innovative technologies have become the backbone of today's businesses, maximum system availability is critical and downtime is more expensive than ever. Increasingly, businesses need a ups that not only protect...

  • Page 6

    Chapter chapter 2 2 sg rackmount installation instructions 1. Verify the following is included in the ups shipping carton: * ups * software diskette(s) & manual *power cord * owners manual * ups/computer cable * box containing mounting brackets, handles & mounting hardware * sg2krm-1tu, sg2krm-2tu, ...

  • Page 7

    C. Install a suitable shelf capable of supporting the weight of the ups and batteries into the equipment rack. Install the shelf so the ups and battery bank (if required) will sit directly on the surface of the shelf. Lift the ups onto its rack shelf, slide it into the rack until the ups front panel...

  • Page 8

    5. For all 1kva & (-2) 2-3kva models, connect the power cord to the ups inlet located on the ups rear panel. On (-1) 2 & 3kva models the line cord is permanently attached to the ups. 6. Connect the power cord(s) for the equipment to be protected to the ups output receptacles. 7. For all 2 & 3kva mod...

  • Page 9

    7 8. If unattended computer shutdown and monitoring are desired, connect the green ups/computer cable to the db-9 connector located on the ups rear panel. Then install the shutdown and monitoring software provided with the ups. For your reference, unix shutdown and monitoring software is available f...

  • Page 10

    8 optional slide mounting kit (sgrmkit) an slide mounting kit option is available from falcon electric. The part number for the kit is sgrmkit and may be installed on any rackmount ups and battery bank referenced in this manual. As all 2-3kva models consist of seperate ups and battery bank modules, ...

  • Page 11

    Battery option model sg1krm-1t sgbr2s7-1ku sgbr2s7-1ku sgbr2s7-1ku sgbr2s7-1ku batteries 7ah x 3 7ah x 6 (7ah x 6 ) x 2 (7ah x 6 ) x 3 (7ah x 6 ) x 4 batteries in ups batteries & ups in same case 7ah x 3 7ah x 3 7ah x 3 7ah x 3 # of battery cases ups 1 2 3 4 run time @ 100w 54 min. 220 min. 400 min....

  • Page 12

    10 chapter chapter 3 3 operation 1 2 3 4 5 6 7 8 9 10 11 ups front panel indicator and function keys 1. Load level indicator leds *the first or bottom led is lit when the output load is greater than 25% of the rated output of the ups. *the second led is lit when the output load is greater than 50% o...

  • Page 13

    5. Bypass indicator led when this led is lit the ups bypass is active. Should the alarm led be lit at the same time, the ups detected an internal failure and the ups must be serviced. 6. Inverter indicator led when this led is lit, the ups inverter is operating and powering the connected load. 7. Gr...

  • Page 14

    Audible alarms audible alarm signals are divided into two different levels of alarm status. Category one alarms represent normal or correctable operational alarms. Category two alarms are sounded in the event of abnormal operation. 1. Category one alarms: a. Two short beeps followed by three short b...

  • Page 15

    13 chapter chapter 4 4 front & rear panel details sg1krm-1tu typical rear panel overview sg1krm-2tu typical rear panel overview power cord inlet (120vac only) input fuse (15a) cooling fan output voltage select switch rs-232 port battery fuse (30a) output receptacles (4) 5-15r extended battery connec...

  • Page 16

    Sg2krm-1tu & sg3krm-1tu typical rear panel overview 14 sg2krm-2tu & sg3krm-2tu typical rear panel overview output circuit breaker (lower 2 receptacles) cooling fan rs-232 port output receptacles (4) 5-15r power cord (120vac only) output voltage select switch output circuit breaker (upper 2 receptacl...

  • Page 17

    Chapter chapter 5 5 communications interfaces rs-232 interface 15 pin # function explanation i/o 9 rs 232 rx input 6 rs 232 tx output 7 ground location: the rs-232 interface is standard on all sg series ups models. The port is located on the ups rear panel, via a db-9 female connector. Supported pro...

  • Page 18

    16 dry contact & opto coupler interface board options jp1 jp2 jp3 j1 j2 j3 db-9 typical falcon dry contact relay board pin description 1 low battery ( when ups reaches low battery, contact activates) (j1, 1-2 short = n.O) (j1, 2-3 short = n.C) 2 jp2 shorted = low battery common & all other shorted j...

  • Page 19

    17 pin assignment for the falcon ua88373 opto-coupler option board (no-bypass signal) pin description 1 not used 2 utility loss (n.O.) (closes upon utility loss) 3 utility loss (n.C.) (opens upon utility loss) 4 common for pins 2, 3 & 5 5 low battery (n.O.) (closes at low battery) 6 remote shutdown ...

  • Page 20

    Chapter chapter 6 6 maintenance & technical support 1. Care & maintenance falcon ® sg series upss are designed to be maintenance-free. They can be cleaned with a damp cloth or non-abrasive cleanser, providing the ups is turned off and the input plug is disconnected from the utility source. On a regu...

  • Page 21

    The following precautions should be observed by a qualified technician when working with batteries. 1. Remove watches, rings, or other metal objects. 2. Use tools with insulated handles. 3. Wear rubber gloves and boots. 4. Do not lay tools or metal parts on top of batteries. 4. Storing the ups and b...

  • Page 22

    6. Technical support your falcon ® electric sg series ups is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service. Falcon electric inc. Irwindale, ca. 91706 service 800.842.6940 voice 626.962.7770 fax 626.962.7720 ...

  • Page 23

    21 general provisions falcon® electric inc., hereby warrants product shipped under this agreement to be free from defective workmanship for a period of two years following date of shipment. This limited new product warranty agreement only applies to covered repairs to the product occurring within th...

  • Page 24: Sg Series

    Sg series tm ups plus ® 1kva to 3kva 22 model number sg1krm -1tu sg1krm -2tu sg2krm -1tu sg2krm-2tu sg3krm-1tu sg3krm-2tu nominal va 1000 2000 3000 electrical input nominal ac voltage 120v 230v 120v 230v 120v 230v ac voltage range 87-140v 170-275v 87-140v 170-275v 87-140v 170-275v current-amps 6.9 3...