Falcon SSG500VA-1 Owner's Operating Manual - page 9
OM48017A
2001 Falcon
Electric Inc. All rights reserved.
All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice. 2001- 10-18
Falcon and the Falcon Electric logo are registered trademarks of Falcon Electric Inc.
MD40024-c
SPECIFICATION
MODEL
SSG500VA-1
RATED POWER
@ p.f. = 0.7
500VA
Voltage
120Vac, +10%, -30%
(Without battery discharge)
Current
8A
INPUT
Frequency
45Hz - 65Hz
(45-400Hz optional)
Voltage
120Vac
±
3%
Current
4.2A (RMS),
11A Repetitive Peak
Frequency (Sync)
(Internal)
50/60 Hz
±
0.1%
50/60 Hz
±
0.5Hz
Harmonic Distortion
Linear <4% Typical
Dynamic Response
±
4% for 100% Step Load
Change ,05 ms Recovery Time
Overload (UPS)
110% Continuous;
200% for 0.5 seconds;
Sustained excessive overload
causes safe shutdown without
equipment damage
Output Protection
Short circuit & overload
Excessive battery discharge
OUTPUT
Efficiency
85% (Typical)
DC Voltage
48Vdc
Type
12V, 7AH Sealed Lead Acid
Backup
time.
Full Load
Half Load
4 min.
10 min.
BATTERY
Recharge Time
8 Hours to 90%
Visual Indicators
Utility Present
Inverter On
Summary Alarm
Audible Alarms
Low Battery, Utility Interrupt,
Inverter Failure, Over Temp.
FEATURES
Computer Interface
(DB-9) Utility Interrupt
Low Battery
Audible Noise
43-46dBA at five feet
Operating Temperature
32
°
F (0
°
C to 40
°
C)
Humidity
10% to 90%
ENVIRONMENT
Altitude
Sea Level to 7,000 Feet
Cooling
Low Velocity Forced Air
Input
8' Cord with NEMA Type
5-15P
Output
Four NEMA Type 5-15R
Weight
22 lbs. (10kg)
MECHANICAL
Dimensions (H x W x D)
2.8 x 13.4 x 15.0 Inches
7 x 34 x 38 cm
APPROVALS
Agency
UL Listed, CSA, FCC Class A
FALCON
Electric Inc., 5106 Azusa Canyon Rd., Irwindale, California 91706, 877-2-FALCON {877 232-5266}, Fax 626-962-7720, Email:
sales@falconups.com
SSG500VA SERIES
REAR VIEW