Fantec ECO-TOUCH Operating Instructions
OPERATING INSTRUCTIONS
ECO-TOUCH
TM
PROGRAMMABLE TOUCH SCREEN WALL CONTROL
*Compatible with SHR/VHR (HRV), SER (ERV) and FLEX Series units
The
OPTIONS menu enables you to customize the operation of your
wall controller. To enter the menu, you need to first press anywhere in
the bottom portion of the
OPTIONS screen section. The icon NEXT will
first appear with a 5 second countdown timer. If you wish to continue
and change the available options, press the
NEXT button before the
timer reaches 0 (zero).
Once in the
OPTIONS menu, you will have the possibility to change
the options listed on the right. To change the values of each option,
use the
up or down arrow buttons. To navigate to the next available
option, press the
NEXT button . When doing so, any changes made to
the values of the previous option will be automatically saved and will
then become your own personal operating preferences.
To exit the
OPTIONS menu and return to normal operation, use the
NEXT button to advance to the original 5-second timer. The controller
will resume its operation with your new preferences once the time
has elapsed.
If for any reason you cannot find the 5 second timer, the controller
will automatically exit the
OPTIONS menu after 1 minute of inactivity.
PARAMETERS OPTION
POSSIBLE VALUES
DEFAULT VALUE
Night Preferences
Ventilation mode and fan speed during night
Ventilation Mode /
Fan Speed Level
Air Exchange
Mode & Medium
Speed
Day Preferences
Ventilation mode and fan speed during day
Ventilation Mode /
Fan Speed Level
Air Exchange
Mode & Reduced
Speed
Relative Humidity
Desired indoor relative humidity selection
30 to 80 %
45%
Maintenance Reset
*See Maintenance Section for details.
Reset Timer & Icon
Display
n/a
MAINTENANCE REMINDER
The Maintenance Icon will display every
3 months (90 days) of runtime as a reminder that maintenance to the
ventilation system is recommended. Refer to ventilation system maintenance instructions. In order to reset the
Maintenance timer, enter the
OPTIONS menu and advance to the Maintenance Reset option, which will be indicated
by a blinking Maintenance icon. To reset the Maintenance reminder, hold the
NEXT button for 3 seconds until the
controller returns to its normal operation.
Item #: 422528
Rev Date: 060214
OPERATION INDICATORS
Air Exchange
mode Animation
Recirculation
mode Animation
System stand-by
Fan speed level
and timer
Fan operation
Animation
Icon activation
USE & OPERATION
OPTIONS & PREFERENCES
AUTOMATIC OPERATION (ECO MODE)
Pressing the
ECO mode touch area enables the AUTOMATIC operation of the ventilation
system to optimize its performance. It uses the indoor and outdoor conditions and the user
preferences to automatically select the proper Ventilation Mode and Fan Speed. You can
customize the operation of
ECO mode to meet your individual needs using the OPTIONS &
PREFERENCES menu.
20-40-60 MINUTES TIMER OVERRIDE
You can activate an internal timer to force the ventilation system to run at the maximum
speed by pressing the
MAX button. When MAX mode is activated, the ventilation system
will exchange indoor air with outdoor air for a period of
20, 40 or 60 minutes, which will be
indicated above the Fan speed level indicator. Repeatedly pressing the
MAX button will cycle
through the time periods.
Ventilation Mode
Selection
Ventilation system
exchanges indoor
air for outdoor air.
The indoor air is
circulated within the
house.
The ventilation
system is on
stand-by.
Exchange
Fan Speed
Selection
1
Reduced
20 min/hr
1
Reduced
40 min/hr
Reduced
Medium
Normal
Recirculation
Fan Speed
Selection
2
Reduced
2
Medium
2
Normal
MANUAL OPERATION
There are simply two (2) selections required to
operate your ventilation system –
Ventilation Mode
selection and
Fan Speed selection. These can be
selected either manually, via the manual section of
the touch screen, or automatically by activating the
ECO mode.
To select a specific mode or speed, simply press
the corresponding
Touch Area, indicated in the above
diagram. A blue backlight activates each time a touch
area is pressed.
Reduced
Medium
Normal
1
The unit will ventilate for 20 or 40 minutes, then go into Stand-by for the rest of the
hour.
2
When the
VENT icon flashes and the RECIRC icon is displayed the unit will ventilate for 20
minutes then recirculate for 40 minutes at the selected speed.