Fantech SER 1504 Installation Manual - Start Up Procedure
12
fantech
Start up procedure
The Switch on the side of the unit is used to toggle between STANDBY, REDUCED speed and NORMAL speed modes.
Place the unit in NORMAL speed to perform the balancing.
Airflow balancing
IF THE UNIT'S AIR FLOWS ARE NOT PROPERLY BALANCED...
• THE UNIT'S EFFICIENCY MAY BE REDUCED.
• THE UNIT'S CORE MAY BECOME DAMAGED.
• NORMAL OPERATION OF THE UNIT COULD CAUSE THE PRESSURIZATION OR DEPRESSURIZATION OF YOUR HOME,
WHICH CAN LEAD TO AIR LEAKS OR BACKDRAFTING OF ANY COMBUSTION APPLIANCES.
The balancing procedure consists of measuring the supply air flow and the return air flow to ensure that they are equal. A difference of up to 10%
is considered acceptable. In the cases where the air flow is not exactly the same, it is recommended to have a higher return air flow to ensure
that the temperature of the supply air flow coming from outside is as close to room temperature as possible.
•
For optimal performance, ERV unit should be re-balanced after a major renovation or after the
installation of extra grilles or registers.
2 Install the drain hose,
making a “P” trap
1 Install the drain nipple.
Installing drain line
Through normal operation and during its defrost mode, the ERV may produce some condensation. This water should flow into a nearby drain, or be taken
away by a condensate pump. The ERV and all condensate lines must be installed in a space where the temperature is maintained above the freezing
point. A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the unit.
Secure the condensate line to the drain connection using a tie wrap or other appropriate method.