FCI ADP-R Installation And Maintenance Instructions

Summary of ADP-R

  • Page 1

    Fc200-12-00 8 i56-2214-004r © 2004 fci fcc statement this device complies with part 15 of the fcc rules. Operation is subject to the following two conditions: (1) this device may not cause harmful inter- ference, and (2) this device must accept any interference received, including interference that ...

  • Page 2

    [9.3.2] photo detector boards 1. Remove the screen by gently grasping on each side and pulling straight off. 2. Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen and blow out any remaining debris. Replacement screens (p/n s08-39-01) are avai...

  • Page 3

    Fc200-12-00 6 i56-2214-004r figure 11. System wiring diagram for adp-r duct smoke detector with rts451/rts451key figure 10. Wiring diagram for adp-r duct detector with optional ra400z 5 7 ra400z 5 = alarm signal 7 = aux. Power (–) alarm signal aux. Power (–) test + test – alarm signal not used not u...

  • Page 4

    [9.1.5] filter replacement the filters do not substantially affect smoke performance even when up to 90% of the filter is clogged. Quarterly visual inspection usually suf- fices to determine whether the filters should be replaced because only a high percentage of contamination affects performance. I...