FE M-UPS050AD1B User Manual

Manual is about: Uninterruptible Power Supply GX 100 Series (5kVA)

Summary of M-UPS050AD1B

  • Page 1

    Fuji electric co., ltd. User’s manual uninterruptible power supply gx 100 series (5kva) model m-ups050ad1c m-ups050ad1b inr-hg5411 a.

  • Page 2

    For safe use handling of this manual this manual describes important information for using this product safely. Please read this manual carefully before using this product. Use this product, after reading and understanding especially “caution about safety" and "caution for use" in this manual well. ...

  • Page 4

    I introduction an uninterruptible power supply is a device for supplying stable electric power to oa devices, fa devices, and computer devices. This manual describes installation, running, daily management, troubleshooting, and maintenance of an uninterruptible power supply. Use an uninterruptible p...

  • Page 5

    Introduction ii warning indication in this manual, the following warning indications are described so that user or the people around the ups do not suffer damage to the body and property. Warning warning” indicates that death or serious injury may result, if the ups is not used correctly. Caution” i...

  • Page 6

    Iii caution about safety list of important warnings the important warnings described in this manual are as follows. Warning” indicates that death or serious injury may result, if the ups is not used correctly. Electric shock do not remove the cover of the ups. Since there are parts of high voltage i...

  • Page 7

    Caution about safety iv do not ride on the ups and not put the objects on top of the ups. Injury there is the fear of an injury or an overturn. This ups is a heavy load. Pay adequate attention to handling of the ups. Injury damage take out the ups in the level and flat place. Pay adequate attention ...

  • Page 8

    Caution about safety v damage do not use the ups for the uses that may damage the human body or exert an important influence on the society and public. The medical equipment which has an influence on the human life directly the equipment that may damage the human body the socially and publicly impor...

  • Page 9

    Vi caution for use be careful about the following when using the ups. Important “important” indicates precautions for use of the ups. Do not install and store the ups in the following places: in an outdoor location a place exposed to the elements an extremely humid place and a dusty place a place wi...

  • Page 10

    Caution for use vii the allowable voltage between the input electric cable of the ups and the ground is 230 vac. If applying the voltage of more than 230 vac, the filter circuit of the input part may be damaged. The input surge voltage capacity of the ups is 5kv peak (1.2 50µs). However, if the mode...

  • Page 11

    Viii index introduction.......................................................................................................I caution about safety .....................................................................................Iii caution for use..................................................

  • Page 12

    Ix 5.2 caution and measures for the rolling blackouts............................. 24 operation before the rolling blackouts operation after the rolling blackouts 5.3 inspecting the battery (battery check)............................................. 25 confirming the state of the ups using the manu...

  • Page 13

    1 1 unpacking 1.1 opening the packing opening the packing this ups is a heavy load. Pay adequate attention to handling of the ups. Injury damage take out the ups in the level and flat place. Pay adequate attention so that an accident such as an overturn or a drop will not occur. The mass of the ups ...

  • Page 14

    2 2 overview 2.1 name and main function of each part this chapter describes the name and main function of each part of the ups. (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14) (13) (12) (15) (16) (18) (17).

  • Page 15

    2.1 name and main function of each part 3 name main function (1) run it blinks (green) when the ups is connected to an input power source. It lights up (green) while the ups is operating normally. (2) alarm it lights up (orange) when the abnormalities occurred inside the ups. (3) over load it lights...

  • Page 16

    2 overview 4 2.2 operation mode of the ups at the normal operation while the ups is operating normally, the ups operates an ac power supply as an input, and supplies the output of constant voltage to connection device. Simultaneously, the ups charges an internal battery and prepares for the battery ...

  • Page 17

    2.2 operation mode of the ups 5 at the bypass operation (in the event of the abnormalities inside the ups) when the abnormalities occur inside the ups, an output switching circuit switches to a bypass circuit, and continues to supply electric power through the bypass circuit to the connection device...

  • Page 18

    6 3 installation 3.1 installing the ups caution about installation injury do not ride on or put an object on the ups. There is fear of an injury or an overturn. Damage do not put an object (crt display or floppy disk, etc.) vulnerable to magnetism around the ups. There is fear of exerting a bad infl...

  • Page 19

    3.1 installing the ups 7 the following spaces are required for an installation location. The ups takes in air through the vent hole on the front of the ups and exhausts air through the cooling fan on the back of the ups. Therefore, the space of 10cm or more is required in the front and rear of the u...

  • Page 20

    3 installation 8 determining the installation method this ups can be installed laying down. If installing laying the ups down, tilt it only to the right side, seeing from the front. Never tilt the ups to the left side. Fire damage there is fear of a fire or the ups failure owing to a leak of battery...

  • Page 21

    3.1 installing the ups 9 installation method the ups is heavy. Pay enough attention to handling the ups. Injury damage take out the ups in a level and flat place. Pay enough attention to prevent an accident such as an overturn or a drop. The weight of the ups is as follows: m-ups050ad1c : 84kg (with...

  • Page 22

    3 installation 10 3.2 connecting the cable caution about connecting the cable electric shock connect a grounding wire to a ground terminal. (class d grounding) there is fear of an electric shock. A commercial power ordinarily has electrodes of a grounding side and an un-grounding side apart from a g...

  • Page 23

    3.2connecting the cable 11 preparation before connecting the cable important when connecting the ups to a three-phase power supply system, be sure to connect the grounding phase of the three-phase power supply system to the electrode of a grounding side of the ac input of the ups. If connecting to a...

  • Page 24

    3 installation 12 2. The specifications of the input and output terminal block are as follows. Select the crimp-type terminal which is suitable for specification. Ups side specification connect with terminal marking connection figuration l/r ac input (un-grounding side) n/s ac input (grounding side)...

  • Page 25

    3.3 interface port 13 3.3 interface port the interface port (d-sub 9 pins) is mounted on the back of the ups and can take out the following signals. Use as necessary. Cn1 (no-voltage contact signal interface) pin no. Classification of signal name of signal content 1-4 “open” at operation 1-6 “close”...

  • Page 26

    3 installation 14 cn2 (rs-232c interface) pin no. Classification of signal name of signal content 2-3 “close” at operation input power supply abnormal signal (*1) it is the no-voltage contact signal which is outputted when the abnormalities, such as the power failure, occur at an input power supply....

  • Page 27

    3.4 setting up the output voltage 15 3.4 setting up the output voltage this ups can change the rated output voltage by the switch of voltage setting on the back of the ups. Damage confirm that the voltage set up by the switch of voltage setting is within the range of input voltage of the connection ...

  • Page 28

    3 installation 16 7. Press the run/stop switch on the front of the ups for approximately 1 second. The buzzer will sound if the switch is received. 8. Ac voltage set up is outputted from the output terminal block. The run led (green) on the front of the ups lights up. 9. Turn on the connection devic...

  • Page 29

    17 4 running 4.1 turning on the ups confirm that the voltage set up by the switch of voltage setting is within the range of input voltage of the connection device. Damage there is fear of damaging the connection device. Confirming cable connection 1. Confirm that the ups is connected to an input pow...

  • Page 30

    4 running 18 turning on the ups 2. Press the run/stop switch on the front of the ups for approximately 1 second. The buzzer will sound if the switch is received. 3. Ac voltage is outputted from the output terminal block. The run led (green) on the front of the ups lights up. The battery condition le...

  • Page 31

    4.1 turning on the ups 19 4. The battery check is performed automatically. The battery condition led (orange) on the front of the ups blinks (in the cycles of approximately 1.6 sec.). 5. The battery check is performed for approximately 5 seconds. Then, if the battery is normal, the battery condition...

  • Page 32

    4 running 20 4.2 turning off the ups also when the rolling blackouts are performed, be sure to perform the following operation. (for details, refer to chapter 5.2 “caution and measures for the rolling blackouts”) damage when turning off the input breaker on the back of the ups, confirm that the run ...

  • Page 33

    4.2 turning off the ups 21 3. An output stops. The run led (green) on the front of the ups blinks slowly (in the cycles of approximately 1.6 sec.). If an output does not stop normally: refer to chapter 6 “troubleshooting”. 4. Turn off the input breaker on the back of the ups..

  • Page 34

    22 5 inspection 5.1 care and daily inspection in order to use the ups safely over the long term, perform the following care and daily inspection regularly. Warning electric do not remove the cover of the ups. Shock since there are some portions with high voltage in the inside of the ups, there is fe...

  • Page 35

    5.1 care and daily inspection 23 how to care for the ups 1. Turn off the ups after turning off the connection device, and remove the dust adhering to the vent hole and cooling fan of the ups with a cleaner, etc. 2. Wipe the surface of the ups with a dry and soft cloth. Daily inspection confirm that ...

  • Page 36

    5 inspection 24 5.2 caution and measures for the rolling blackouts important when using a generator temporarily during the rolling blackouts, use a generator satisfying the following specification. If connecting a generator not satisfying the following specification to the input part of the ups, the...

  • Page 37

    5.3 inspecting the battery (battery check) 25 5.3 inspecting the battery (battery check) inspection of the battery is performed using a battery check function. There are two kinds of battery check functions, an automatic check and a manual check. The manual check is not necessary ordinarily since th...

  • Page 38

    5 inspection 26 using the manual check function 2. Press the batt check switch on the front of the ups for approximately 2 seconds. A buzzer sounds and the battery condition led (orange) blinks (in the cycles of approximately 1.6 sec.). A buzzer sounds again approximately 5 seconds later and the bat...

  • Page 39

    5.3 inspecting the battery (battery check) 27 3. As a result of the battery check, the ups will be in the following state. If the battery is fully charged: the run led (green) on the front of the ups lights up, and the ups returns to the normal operation. If the battery is not fully charged: a warni...

  • Page 40

    5 inspection 28 charging the battery 4. Put out the battery condition led (orange) by pressing the reset switch on the front of the ups for approximately 3 seconds, and operate the ups 12 hours or more to charge the battery. When pressing the reset switch, once the battery condition led (orange) on ...

  • Page 41

    29 6 troubleshooting 6.1 if a warning beep sounds 1. Confirm the state of led on the front of the ups, and the type of a warning beep. 2. Refer to the “operation mode list”, and deal with it according to directions. If the ups is not connected to an input power supply, connect. For details, refer to...

  • Page 42

    6 troubleshooting 30 6.2 operation mode list when it seems that the abnormalities have occurred inside the ups or the connection device has stopped, confirm the led and a warning beep by the following lists, and deal with the trouble in accordance with the remarks in the "operation mode list". Types...

  • Page 43

    6.2 operation mode list 31 operation mode list symbols of led: ···· lighting ··········not lighting ········ blinking the battery condition led (green) indicates the amount of battery charge according to the sort of lighting as follows: (not lighting)········· 0 to 50% : the battery is not fully cha...

  • Page 44

    6 troubleshooting 32 led no . Run (green) al arm (orange) over load (orange) bypass (orange) battery condition (green/ orange) warning beep operational status remarks 4 lighting lighting (1) bypass operation due to ups failure the ups became the failure state and switched to the bypass operation. Ev...

  • Page 45

    6.2 operation mode list 33 led no . Run (green) al arm (orange) over load (orange) bypass (orange) battery condition (green/ orange) warning beep operational status remarks 9 lighting (b) slow blink (1) output overload during the bypass operation during the bypass operation, the capacity of the conn...

  • Page 46

    6 troubleshooting 34 led no . Run (green) al arm (orange) over load (orange) bypass (orange) battery condition (green/ orange) warning beep operational status remarks 15 lighting lighting (orange) (1) end of battery life the recommendation time of battery replacement has come. Since it is necessary ...

  • Page 47

    35 7 maintenance 7.1 replacing the battery timing of the battery replacement damage replace the battery periodically. If continuing to use the ups that the battery life ended, there is fear of a leak of battery and a smoke. In the following cases, it is the end of battery life. Replace the battery. ...

  • Page 48

    7 maintenance 36 the method of battery replacement electric shock only maintenance personnel must perform the battery replacement. There is fear of an electric shock. Damage replace the battery with one specified by our company and a new one. If using the un-specified battery or mixing an old batter...

  • Page 49

    7.1 replacing the battery 37 disposal and storage of battery pay enough attention to disposal and storage of the battery. When disposing of the used battery, dispose of it separately from a dry cell, etc., sticking the insulating tape on the terminal of battery to prevent a short circuit. This ups u...

  • Page 50

    7 maintenance 38 7.2 replacing the cooling fan timing of the cooling fan replacement important replace the cooling fan periodically. If continuing to use the ups that the fan life ended, there is a possibility that the inside temperature of the ups may get out of the rated specification. In the foll...

  • Page 51

    7.2 replacing the cooling fan 39 the method of cooling fan replacement electric shock injury put neither a stick nor a finger into the cooling fan or the vent hole. There is fear of an electric shock or an injury. Electric shock only maintenance personnel must perform the cooling fan replacement. Th...

  • Page 52

    7 maintenance 40 7.3 when not using the ups (storage) work before storage important do not store the ups in the following places: in an outdoor location a place exposed to the elements an extremely humid place and a dusty place a place with corrosive gas or salinity a place subjected to direct sunli...

  • Page 53

    41 8 appendix 8.1 rated specification model m-ups050ad1c m-ups050ad1b rating capacity 5000va/4000w voltage 100/105/110/115/120v ± 2% frequency 50/60hz (automatic changeover inside the ups) at the normal operation depend on input frequency frequency accuracy at the battery operation within ±0.1% numb...

  • Page 54

    8 appendix 42 model m-ups050ad1c m-ups050ad1b outside dimension w d h 240 700 514mm 240 700 434mm mass 84 ㎏ (without battery: 48 ㎏) 78 ㎏ (without battery: 42 ㎏) standard ul1778 (-u, -uc type) applicable standard vcci class a, in conformity with en62040 (-uc type) input terminal block (l/r, n/s : m6 ...

  • Page 55

    8.2 additional description for ul type 43 8.2 additional description for ul type important safety instructions save these instructions this manual contains important instructions for ups gx100 series models that should be followed during installation and maintenance of the ups and batteries. ‒ inter...

  • Page 56

    8 appendix 44 table 2. Output rating, wire size, torque, external output circuit breaker size output 2pole circuit breaker model vin(v) iin(a) wire size awg type of closed-loop terminal tightening torque (n・m) v a m-ups050ad1c-u m-ups050ad1b-u 100/105 110/115 120 50/47.6 45.5/43.5 417 4 r14-6 3.0 ac...

  • Page 57

    8.2 additional description for ul type 45 danger ■ risk of electric shock do not touch uninsulated battery terminal. Warning ■ risk of electric shock ・ do not remove the cover for any reason. There are no user-serviceable parts inside the ups. Refer servicing to qualified service personnel. Caution ...

  • Page 58

    8 appendix 46 ■ a battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries: a) remove watches, rings, or other metal objects. B) use tools with insulated handles. C) wear rubber gloves and boots. D) do not l...