Federal Signal Corporation PS1000 Installation And Maintenance Manual

Manual is about: Power Supply/Charger

Summary of PS1000

  • Page 1

    2562563a rev. A 1212 printed in u.S.A. Installation and maintenance manual model ps1000 power supply/charger.

  • Page 2

    Warranty – seller warrants all goods for five years on parts and 2-1/2 years on labor, under the following conditions and exceptions: seller warrants that all goods of seller's manufacture will conform to any descriptions thereof for specifications which are expressly made a part of this sales contr...

  • Page 3: Contents

    1 contents safety messages to installation and service personnel of federal signal products ..................2 product specifications.......................................................................................................................3 installing and maintaining the model ps1000 ....

  • Page 4: Of Federal Signal Products

    2 safety messages to installation and service personnel of federal signal products peoples lives depend on your proper installation of our products. It is important to follow all instructions shipped with the products. The selection of the mounting location for the device, its controls and routing o...

  • Page 5: Product Specifications

    3 product specifications themodelps1000isapowersupply/chargerthatconvertsanacinputtoa24vdcregulatingoutput.Itis intended for indoor use only. Input ◆ ps1000: 115vac/60hz,4.4a ◆ ps1000-240: 230vac/50-60hz,2.2a output ◆ 24vdc ◆ 8asupplycurrentinanon-alarmconditionwith10asupplycurrentduringthealarmforf...

  • Page 6

    4 standby specifications (total current) output 15 min. Of standby, 5 min. Of alarm 4 hr. Of standby, 5 min. Of alarm 24 hr. Of standby, 5 min. Of alarm 60 hr. Of standby, 5 min. Of alarm 24 vdc, 12 ah battery standby = 8 a alarm = 10 a standby = 1.5 a alarm = 10 a standby = 200 ma alarm = 10 a stan...

  • Page 7

    5 installing and maintaining the model ps1000 installingthemodelps1000requiresmountingtheenclosureandwiringtheps1000.Tocalculatebattery capacity,alarmduration,andothervariables,use“table3battery-sizecalculationworksheet”onpage8. For access control applications, standby batteries are optional. When s...

  • Page 8

    6 connectthepowerdistributionmoduletoterminalsmarked – dc + . Connecttheappropriatesignalingnotificationdevicestotheterminalsmarked ac fail and bat fail (supervisoryrelayoutputs. Whenthemodelps1000isusedinfirealarm,burglaralarm,oraccesscontrolapplications,the ac fail relaymustbeusedtoprovideavisuali...

  • Page 9

    7 -- dc + bat fail no c nc no c nc + bat --- dc ac fail l g ac 10a 250v 15a 250v input 1 2 green lead n wire strap from enclosure door replace fuse cover before energizing power distribution module(s) 115 vac power mains non-power limited class i battery and ac supervision circuit (power limited) no...

  • Page 10

    8 table 3 battery-size calculation worksheet a. Model ps1000 internal current consumption (standby) 0.05a b. Load current consumption (standby) (standby) a c. Standby time required (hours) h d. Battery capacity required for standby (a + b) * c ah e. Model ps1000 internal power consumption (alarm) 0....

  • Page 11: Maintaining The Model Ps1000

    9 maintaining the model ps1000 shock and fire hazards—de-energize the model ps1000 before servicing it. For continued protection against the risk of electric shock and fire hazard, replace the fuses with fuses of the same type and rating. Input fuse: 10 a, 250 v battery fuse: 15 a, 32 v output volta...

  • Page 12

    10 © 2012 federal signal corporation obtaining service, parts, and support federal signal will service your product, provide technical assistance support. Please call the phone numbers listedbelow.Forinstructionmanuals,pleasegotohttp://www.Federalsignal-indust.Com repair service productsreturnedforr...