25500444 rev. A0 0118 printed in u.S.A. © copyright 2018 federal signal corporation ultravoice ® remote interface model: uvri-b description, specifications, and installation manual.
Limited warranty this product is subject to and covered by a limited warranty, a copy of which may be found at www.Fedsig.Com/ssg-warranty. A copy of this limited warranty may also be obtained by written request to federal signal corporation, 2645 federal signal drive, university park, il 60484; by ...
3 description, specifications, and installation manual contents safety messages......................................................................................................................................................8 general description ....................................................
4 ultravoice remote interface (uvri-b) wiring guidelines for 120 vac electrical service .....................................................................................34 wiring guidelines for 240 vac electrical service ..............................................................................
5 description, specifications, and installation manual two-way radio controlled system ..................................................................................................................47 fire panel interface ..............................................................................
6 ultravoice remote interface (uvri-b) tables table 1 uvri-b models ..........................................................................................................................................11 table 2 electrical on the control board ......................................................
7 description, specifications, and installation manual table 27 metal stud wall mounting materials .....................................................................................................32 table 28 installer supplied uvri-b electrical installation material list ...........................
8 safety messages ultravoice remote interface (uvri-b) safety messages it is important to follow all instructions shipped with this product. This device is to be installed by trained personnel who are thoroughly familiar with the country electric codes and will follow these guidelines as well as loc...
9 safety messages description, specifications, and installation manual • after installation, service, or maintenance, test the siren system to confirm that it is operating properly. Test the system regularly to confirm that it will be operational in an emergency. • if future service and operating pe...
10 general description ultravoice remote interface (uvri-b) general description introduction the ultravoice remote interface unit (uvri-b) provides remote extension of federal signal indoor and outdoor warning systems. The uvri-b is available with a number of standard and optional features to allow ...
11 general description description, specifications, and installation manual operation is supervised and status information is transferred back to the control station(s) through one or more available communications networks. The uvri-b monitors the audio output level and the remote activation input t...
12 general description ultravoice remote interface (uvri-b) • remote download for voice message downloads using ip interface • remote monitoring of system and speaker circuits • optional cellular, satellite, or broadband ip communications • stackable siren functions enable user pre-defined warning s...
13 general description description, specifications, and installation manual rf frequency program the radio transceiver with the rf frequency(s), channel spacing and power output before placing into service. These settings are pre-set at the factory if the requirements are provided with the order. Se...
14 specifications ultravoice remote interface (uvri-b) user programs the uvri-b has the capacity to store functions for specific alerting configuration. Functions can be used to activate relays for control of external devices and activation of pre-recorded messages. See the commander software manual...
15 specifications description, specifications, and installation manual table 4 serial and i 2 c ports on control board serial port protocol rs232c 115200,n,8,1 i 2 c port protocol philips standard i 2 c table 5 relay outputs on control board quantity 5 contact rating 10 a, 250 vac, 30 vdc, optically...
16 specifications ultravoice remote interface (uvri-b) table 11 tc1 sensing inputs on control board quantity 4 input type optically isolated. To be connected to contact closure through a series 1.00 k Ω resistor and with a 2.2k Ω resistor across the contacts. Senses; active loop; inactive loop; > 36...
17 specifications description, specifications, and installation manual pocsag supports binary frequency shift keying 512 baud numeric messages decode sensitivity 18 db sinad for tone (except with ctcss tones > 200 hz and decode tones and 21 db sinad for msk, eas, pocsag and dtmf with 50 ms/50 ms or ...
18 specifications ultravoice remote interface (uvri-b) jp18 tc1 interface relay outputs (typically used for fire panel interface) 1 tc1-1 (-) request to activate audio 2 tc1-1 (+) 3 tc1-2 (-) request to manage evacuation signals 4 tc1-2 (+) 5 tc1-3 (-) request to manage visible alert signals 6 tc1-3...
19 specifications description, specifications, and installation manual jp34 relay outputs 1 relay # 1 common 2 relay # 1 normally open 3 relay # 1 normally closed 4 relay # 2 common 5 relay # 2 normally open 6 relay # 2 normally closed 7 relay # 3 common 8 relay # 3 normally open 9 relay # 3 normall...
20 specifications ultravoice remote interface (uvri-b) audio output (jp10) 600 ohm (jp8) ethernet audio input (jp9) i 2 c (jp19) local mic (j1) figure 2 uvri-b boards (lines a, b, c for control board to amplifier connection) input level audio output (jp9) i 2 c (jp5) 20 amp (f1) uv amplifier board a...
21 specifications description, specifications, and installation manual figure 3 control board with configuration jumpers, controls, and indicators d92 d105 d107 jp45 d118 d89 jp1 r19 r18 r59 r21 jp2 jp3 r17 jp11 jp12 jp16 jp17 jp20 jp15 d51 d54 d53 d52 d56 d55 r103 jp40 j2 j1 jp10 jp9 jp8 r3 jp4 jp5...
22 specifications ultravoice remote interface (uvri-b) table 14 connectors on the amplifier board (see figure 2) jp2 speaker output 1 – to control board jp34 1 and 4 2 – to speaker common jp3 line c balanced audio line input 1 and 2 – 1.33 to 10/25 v rms audio output (jp6) on the control board jp4 a...
23 specifications description, specifications, and installation manual jp20 siren audio channel select jumper: 1-2 signal 0, a 2-3 signal 1, b jp27 options connector: 1 microcontroller input 2 ground jp40 options jumper - future use jp44 short to enable sounder/piezo table 16 configuration jumpers o...
24 specifications ultravoice remote interface (uvri-b) indicators table 18 indicators on the control board (see figure 3) d9 tc interface gnd fault d10 tc interface line fault d11 tc interface tc2-4 / spare #6 input d15 tc interface tc2-1 / spare #3 input d16 tc interface tc2-2 / spare #4 input d17 ...
25 specifications description, specifications, and installation manual pot settings table 20 pot settings on the control board r69 output level for 10 v/25 v and 8 Ω, 0.7 w audio outputs, (default = turn clockwise 20 turns or all of the way up.) r103 digital voice gain, (default = turn clockwise 20 ...
26 installation ultravoice remote interface (uvri-b) configuring for information on configuring, see the commander software manual and the informer-ip setup, program, and user manual. Installation electrocution or severe personal injury can occur when making electrical connections, drilling holes, o...
27 installation description, specifications, and installation manual you can use several methods to activate the uvri-b. Use the manual activation buttons and a hand-held microphone to activate the uvri-b locally. Use landline control through normally open contact switches. Make connections directly...
28 installation ultravoice remote interface (uvri-b) figure 5 uvri-b cabinet dimensional - front and side view 1.82 1.50 20.36 20.00 6.62 16.00 3.34 1.74 2.50 16.30 6x 1/2" conduit knockouts.
29 installation description, specifications, and installation manual figure 6 uvri-b cabinet dimensional - back view 11.00 17.88 2x .31 2x r.25 .44 2x r.16.
30 installation ultravoice remote interface (uvri-b) figure 7 uvri-b drawing of system.
31 installation description, specifications, and installation manual general mounting guidelines use good installation methods and follow local ordinances for mounting cabinet. These general installation instructions are pertinent to all installations. Specific mounting methods and required installa...
32 installation ultravoice remote interface (uvri-b) 4. Proceed to following section. Note : if wall is not straight, use shims to insure enclosure maintains square and structural integrity. Hollow block wall mounting guidelines table 25 hollow block wall mounting materials material description purp...
33 installation description, specifications, and installation manual 1. Locate the wall studs for attaching the mounting backboard to the wall. 2. Mark the wall stud location on the mounting backboard and drill pilot holes for the #14 metal stud screws. Place three screws in each stud evenly spaced ...
34 installation ultravoice remote interface (uvri-b) electrical connections install the siren electrical system in compliance with local electrical codes and nec recommendations. Federal signal recommends that all user-installed conduit connections enter from the bottom of the uvri-b cabinet using t...
35 installation description, specifications, and installation manual wiring guidelines for 240 vac electrical service review the following wiring guidelines: 1. Install a dedicated 15 a breaker in an existing breaker panel or install a new breaker panel if necessary for the uvri-b. 2. Install condui...
36 installation ultravoice remote interface (uvri-b) the battery supply wires are attached to the battery at the factory and the unit is shipped with the battery supply wires disconnected from the control board at jp36. Wait until all other wiring connections are made and refer to the turning on the...
37 installing the antenna description, specifications, and installation manual 600 ohm i/o connections (jp8 on the uvri-b control board) control connections use terminal block jp8 on the uvri-b control board for making connections to 600 ohm balanced audio equipment such as a direct connection to an...
38 installing the antenna ultravoice remote interface (uvri-b) installing the antenna determine type of antenna to be installed if a wireless rf system is used: • cabinet mounted magnetic base • remote mounted magnetic base • yagi external antenna type • omni external antenna type installing the cab...
39 installing the antenna description, specifications, and installation manual note a : proper trimming and adjustment is critical to the voltage standing wave ratio, known as vswr. (high reflected power levels decrease forward power. The life of the radio and transmit capabilities are dependent upo...
40 installing the antenna ultravoice remote interface (uvri-b) 2. Apply rf power to the antenna at the transmit frequency to be used at that antenna, and check for the low vswr while performing each of the following steps. A. Loosen the setscrew with the allen key provided and make a slight adjustme...
41 installing the antenna description, specifications, and installation manual installing the omni fiberglass antenna models note : no tuning is required for this model. “figure 9 omni antenna installation example” on page 42. To install the omni antenna, do the following: 1. Install antenna, (using...
42 installing the antenna ultravoice remote interface (uvri-b) figure 9 omni antenna installation example figure 10 antenna grounding.
43 pre-operational system configuration and testing description, specifications, and installation manual pre-operational system configuration and testing the following procedures should be performed by a properly trained technician to ensure the equipment is operating properly. Visual inspection to ...
44 pre-operational system configuration and testing ultravoice remote interface (uvri-b) equipment required 1. Service monitor 2. Oscilloscope setup connect the radio to the service monitor. Receive audio adjustment to receive audio adjustment: 1. Using service monitor, modulate the correct rf signa...
45 operations description, specifications, and installation manual operations manual activation if configured, use the manual activation switches to activate siren functions. Buttons are located on the control board. Figure 11 uvri-b activation buttons table 29 manual activation buttons on control b...
46 operations ultravoice remote interface (uvri-b) relay output the uvri-b provides five high-powered relays for control of external hardware. Sensor inputs terminal block jp24 is located on the left edge of the uvri-b control board. Use sensor inputs to detect and notify conditions occurring at an ...
47 applications description, specifications, and installation manual audio a and b. Quiet test the federal signal commander system can manually or automatically activate quiet test for verification of system operation. Quiet test uses a 20 khz tone to test tone generators and optional amplifiers. To...
48 maintenance ultravoice remote interface (uvri-b) maintenance service and maintenance should be performed by qualified personnel familiar with the uvri-b, associated controls, and power sources being used and in conjunction with the authorities having jurisdiction. The sound output of speakers is ...
49 troubleshooting description, specifications, and installation manual checking the battery to check the battery: 1. Remove ac power and measure the dc voltage across the dc input connector on the control board. If the battery has been charging for at least 24 hours, this voltage should be above 12...
50 replacement parts ultravoice remote interface (uvri-b) replacement parts the uvri-b has the following replacement parts. Table 32 replacement part numbers description part number control board q20000253 amplifier board q20000324 f1 148142a, 20 amp auto fuse littlefuse 287020 bussman # gdc-5a 1481...
51 appendix a uvri-b field service data sheet description, specifications, and installation manual appendix a uvri-b field service data sheet customer: project number: date: contact person: phone second phone radio shop: contact: phone: siren type: s/n: voltage: controller type: antenna: omni yagi c...
2645 federal signal drive university park, illinois 60484-3617 www.Fedsig.Com customer support 800-548-7229 • +1 708 534-3400 technical support 800-524-3021 • +1 708 534-3400