  • Page 2: Table Of Contents

    0 table of contents important safety introduction………………….……..1 features of line-interactive ups………………..……3 overview s1000, 1500, 2000 va. ………..…………6 product specification…………………….…………...9 installation & operation instructions………….……...11 audible/visual indicators………………………..……14 software application…...

  • Page 3: Introduction

    1 introduction important safety instructions……………. Battery management should be performed or supervised by personnel knowledgeable of batteries and with required precautions. Keep unauthorized personnel away from batteries. When replacing batteries, replace with the same type of batteries. Ups is de...

  • Page 4: Introduction

    2 introduction important safety instructions……………. ρ i f your ups shows obvious signs of having been damaged during transport, immediately return the unit in its original box, with your receipt to your dealer for replacement. ρ keep your ups away from wet or moist places. ρ do not leave your ups in ...

  • Page 5: Introduction

    3 introduction features of line-interactive ups………… thank you for purchasing s series line-interactive ups. This series ups is an advanced line-interactive uninterruptible power system which produces power in pure sine wave form to your equipment; unlike the traditional off-line ups, this series req...

  • Page 6: Introduction

    4 introduction features of line-interactive ups * automatic voltage regulation function - avr provides voltage range by input ± 22% and output ± 5% regulation, which depend on two boosts and two bucks design. * dc start function- allow you to power on the ups inverter (battery) operation, even in ab...

  • Page 7: Introduction

    5 introduction features of line-interactive ups * real time warning for failed battery (lcd model) - the battery self-test function of the ups will check battery status every 20 minutes (no need to push the button by user). The “battery replacement” symbol on lcd panel will show up when battery fail...

  • Page 8: Overview S

    6 overview s 1000, 1500, 2000va led type front panel 1. Leds of battery voltage level and load level 2. Led of operation status 3. Control button led indication: please refer to “audible / visual indicator” section. 80 % 100 % load level 2 high 40 % 20 % 40 % 60 % 80 % 100 % 60 % normal backup low b...

  • Page 9: Lcd Type Front Panel

    7 lcd type front panel 1. Main control button 2. Lcd screen 3. Selection button for mode & value note: lcd available models: all of s series sine-wave line interactive ups could be equipped with lcd display. These models include standard tower series, long-run tower series, standard rack mount serie...

  • Page 10: Rear Panel

    8 rear panel 1. Fuse 2. Inlet of ac power 3. Outlet(s) (nema/iec). 4. Rs-232 communication port it provides rs-232 serial signal and contact closure signals. 5. Network jack- rj45 these two modular jacks provide surge protection to modem or 10 base-t signals. 6. Battery connector when use external b...

  • Page 11: Product Specification

    9 product specification item description model s1000 s1500 s2000 rating 1000va 1500va 2000va wattage 600w 900w 1200w input voltage 100 / 110 / 115 / 120 or 200 / 220 / 230 / 240 vac ±22% nominal frequency 50 / 60hz ± 5% auto sensing phase single output voltage 100 / 110 / 115 / 120 or 200 / 220 / 23...

  • Page 12: Product Specification

    10 product specification item description model s1000 s1500 s2000 communications & management interface port rs-232 control panel led status display on ac power, on battery, overload audible alarm on battery, low battery, overload software upsilon2000 os support windows 95, 98, 2000, me, nt4.0, xp p...

  • Page 13

    11 installation & operation instructions to install the ups, please follow the installation steps below and charge the ups overnight before use. 1. Check the power ratings on the back of your ups to make sure the input voltage matches with your local power specifications. 2. Plug the female end of t...

  • Page 14

    12 installation & operation instructions 7. Perform the power failure test pull out the ac power cord from the wall receptacle to test the operation of ups on battery backup function. Make sure that your computer and other devices are running normally. 8. Turn off the ups before you turn off the ups...

  • Page 15: Green Power Mode Setting

    13 installation & operation instructions 11. Pushing the button for 4 seconds, the ups will turn off the power on the outlets. But, the ups will keep charging if ac power is normal. To stop the charging, please pull out the power cord to shut down the ups completely. 12. During a blackout, push the ...

  • Page 16: Audible/visual Indicators

    14 audible/visual indicators under the following power conditions (status), the led and lcd type indicator, and the audible alarm will respond as follows: led indicator table conditions led indicator audible alarm status description status description idle mode utility good green flashing off none u...

  • Page 17: Lcd Indicator Table (1)

    15 lcd indicator table (1) item symbol indication description 1. Over load the loading exceeds the rating of ups. 2. Load level the higher the loading is, the more bars will illuminate. 3. Ups is loaded when “green mode” is enabled, this symbol will display if the loading is over 30w (approximately)...

  • Page 18: Lcd Indicator Table (2)

    16 lcd indicator table (2) item symbol indication description 9. Silence mode the audible alarm has been silenced. To reset the alarm in back-up mode, push the control button (not available during low battery level or abnormal condition). 10. Ups fault the ups has failed and must be repaired. Contac...

  • Page 19: Software Application

    17 software application ups software introduction introduction the s series ups with software driver provides the functions of ac failure detection, ups battery low detection and system shutdown. Upsilon software is an advanced intelligent ups management utility, which can communicate with s series ...

  • Page 20: Software Application

    18 software application operating system supported novell netware/ windows 95/98/nt/2000/me/xp freebsd linux please install the upsilon 2000 step by step as follow: 1. Turn off the computer. 2. Connect the ups output to the computer input power socket. 3. Connect the special rs232 cable or special u...

  • Page 21: Limited Warranty

    19 limited warranty please register your fenton product on http://www.Fentonups.Com. Fenton ups provides the owner of this fenton product with the following warranties and equipment protection policy. One years ups warranty: fenton ups warrants to the original purchaser of this fenton product that t...

  • Page 22

    20 when you return a ups product or battery under this warranty, you must first obtain an rma number by calling fenton ups. Fenton ups reserves the right to request that you submit a letter describing the circumstances under which the problem occurred and that you submit any other supporting evidenc...

  • Page 23

    21 this protection guarantee is not an insurance policy. This guarantee is not a substitute of insurance coverage policy provided by your insurance carrier and equipment warranty. First, you need to make the claim for recovery, including but not limited to a claim under any applicable insurance, oth...

  • Page 24: Troubleshooting

    22 troubleshooting trouble shooting guide table problem possible cause action to take ups no reaction while ac is connected 1. Power cord plug is loose 2. Fuse on rear panel blown (inside the drawer of inlet) 3. Dead wall socket 1. Check the power cord plug 2. Replace fuse 3. Check wall socket with ...

  • Page 25: Location.

    23 if there is any question, please contact us at the following location. U.S.A. Metapo, inc. 2380 qume drive, suite d san jose, ca 95131 usa tel: +408-943-9308 fax: +408-943-9309 website: www.Metapo.Com www.Fentonups.Com email: support@metapo.Com appendix as for software application, you’re suggest...