3.04 Top Outlet: Two Pipe Flue System
3.04.1 Two pipe connection
Two separate ducts Ø80 for air intake and flue
gas discharge can be directly connected to the
boiler. Fit separate air intake plate.
Connect flue duct to central hole Ø80 and air duct to left or right air intake hole Ø80. Leave blanking plate "2" in remaining
air intake. A wide number of accessories for two pipe systems are available from Ferroli (ref. to page 18). Before installing
your system please check via calculation table (3.04.2) you are not exceeding the maximum permissible length for the
appliance.
Notes on two pipe system installation:
When using the two pipe system the flue discharge pipe must have a 25mm air gap when passing through combustible
materials. Where the flue discharge pipe passes through the airing space of an airing cupboard it must be protected by a
non combustible guard or expanded metal giving an annular air gap of at least 25mm. Where the flue discharge pipe passes
through a wall containing cavity insulation, a non combustible sleeve must be fitted. Additionally a gap of 25mm between
the sleeve and the insulation should be provided by cutting back the insulation or packing loose fill bead insulation with
mineral fibre. Where the flue pipe is run through an unheated roof space it should be insulated with non combustible
insulating material to prevent condensation. The flue pipe should be supported at intervals of not more than 1.8m and the
support should be preferably below a joint.
3.04.2 Two pipe flue system
• Calculating maximum permissible flue length.
The calculation method is based on a standard reference parameter (1 metre of horizontal air flue 80 diameter 80) for the
maximum length permissible for all the pipes + fittings flow resistance coefficient. In other words, for all components and
pipes in the different installation configurations (vertical or horizontal, air or flue, etc.) and for all the fittings, a flow
resistance (reduction) equivalent to
x
metre of horizontal air induction pipe is indicated. For every boiler model a maximum
pipe length is provided, expressed in
n
metres of horizontal air pipe. In this way, to calculate the length of a proposed 2
pipe air-flue system, add the flow resistance (reduction) in equivalent metres-air. For every component and fitting present
in the system, and to check that the total is less than the maximum length the permissible for the boiler model.
IMPORTANT: the pipes and fittings flow resistance (reduction) have been summarised on the following pages. The flow
resistance values written refer only to Ferroli pipes and fittings.
CALCULATION ROUTINE
1.
Utilise the pipes and fittings flows resistance tables on the following pages and calculate the total flow resistance in
metres-air, by adding the flow resistances of the components in the whole air-flue system, based on their position
(vertical or horizontal, air inlet or flue outlet).
Please note that the same fitting, identified by a one code (i.e. 1 pipe diameter 80, code KWMA83A), can offer
different flow resistances if positioned as air inlet or flue outlet, if placed vertically or horizontally.
The flow resistance of the special two pipe flue-air adapters do not have to be included in the calculation as they
are already included in the maximum length calculation.
2.
For the restrictors, please refer to cap. 3.02 to determinate the correct diaphragm.
3.
Check that the total flow resistance calculated is less or equal to 48 metre, the maximum permissible for Falcon.
Ø80
Ø80
AIR
FLUE
1
2
Insert blanking plate 2
in remaining air intake
Remove
blanking
plate