3.0 INSTALLATION DETAILS
3.1 Gas Safety (Installation & Use) Regulations: 1994
In the interest of safety, it is the law that all gas appliances are installed by a competent person in
accordance with the above Regulations, Building Regulations/Building Standards Scotland, Codes of
Practice, current I.E.E. Regulations and the byelaws of the Local Water Undertaking. Failure to
comply with the Regulations may lead to prosecution; it is in your interest and that of safety to ensure
that the law is complied with.
Important - If the water heater is to be fitted in a timber framed buiding it should be fitted in
accordance with the British Gas publication; Guide for Gas Installation in Timber Frame Housing:
Reference DM2. If in doubt advice must be sought from the Local Gas Region of British Gas Plc.
3.2 Location of the water heater
The installation of the TALENT must be on a suitable non-combustible load bearing wall which will
provide an adequate fixing for the boiler mounting bolts. The location should be in an area where the
water pipes will not be subjected to frost conditions. In siting the water heater the following limitations
must be observed:
The water heater may be installed in any room or internal space, although particular attention
is drawn to the requirements of the current, i.e. wiring regulations and in Scotland the electrical
provisions of the building regulations applicable in Scotland, with respect to the installation of the
water heater in a room or internal space containing a bath or shower.
Where a room sealed appliance is installed in a room containing a bath or shower any electrical
switch or appliance control utilising mains electricity, should be so situated that it cannot be touched
by a person using the bath or shower.
3.3 Terminal Position
POSITION
MINIMUM SPACING (fig. 3)
mm
A Directly below an openable window, air vent, or any other ventilation opening ........ 300
B Below gutters, soil pipes or drainpipes ......................................................................... 75
C Below Eaves ............................................................................................................... 100
D Below a Balcony ........................................................................................................ 100
E From vertical drainpipes or soilpipes ............................................................................ 75
F From internal or external corners ............................................................................... 100
G Above adjacent ground or balcony level .................................................................... 100
H From a surface facing the terminal ............................................................................. 600
I
Facing another terminal .......................................................................................... 1.200
J
From opening (door/window) in carport into dwelling ............................................ 1.200
K Vertically from a terminal on the same wall ............................................................ 1.500
L Horizontally from a terminal on the same wall........................................................... 300
N Below carport ............................................................................................................ 600
A Quinnel Barrat and Quinnel guard (part. No. C2) should be screwed to the wall centrally over the
terminal, when the distance is less than 2 m from the outside floor.
3.4 Air Supply
The room in which the boiler is installed does not require a purpose provided vent.