Ferrups 0800-2000 User Manual

Other manuals for 0800-2000: Installation Manual
Manual is about: 2 kVA-7.6 kVA 50 and 60 Hz UPS

Summary of 0800-2000

  • Page 1

    User manual ferrups 0800-2000 - 0800-7500

  • Page 2

    Ferrups ® user manual 0800-2000 through 0800-7500 2 kva-7.5 kva 50 and 60 hz uninterruptible power systems important safety instructions. Save these instructions. This manual contains important instructions for your ups. See the checkups cd also for the ferrups safety information manual. Se cd-romme...

  • Page 3

    2 best power offices best power p.O. Box 280 necedah, wi 54646 u.S.A. Telephone: 1-608-565-7200 toll-free: 1-800-356-5794 (u.S.A. And canada) fax: 1-608-565-2221 international fax: 1-608-565-7675 worldwide service p.O. Box 11 necedah, wi 54646 u.S.A. Telephone: 1-608-565-2100 toll-free: 1-800-356-57...

  • Page 4

    3 contents 100 introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 200 ups features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 5

    4 200 ups features the drawings below will help you identify the features on your ups and separate battery cabinets. Back panel of standard units* back panel with optional internal bypass battery cabinet back panel ups display * only one ferrups model is shown; sizes vary. The unit shown is a soft-w...

  • Page 6

    5 300 starting the ups note: if you plan to store your ups, the storage temperature must be between –20° and +40° celsius (–4° and +104° fahrenheit). If the ups does not have internal batteries, you can store it at –20° to +60° c (–4° to +140° f). The batteries must be recharged every 90-120 days. T...

  • Page 7

    6 3 models with permanently attached power cords (shown): plug in the ups. If the plug on the ups’ power cord does not match your outlet (receptacle), an electrician must install the proper outlet. Models with power cords that must be plugged in: do not use the cord that came with your ups to plug i...

  • Page 8

    7 if your ups has output receptacles/outlets on the back panel (shown) or on an attached internal bypass switch, plug the equipment you want to protect into the ups’ receptacles. If you used the cord from your own equipment to plug in the ups (see step 2 ), use the cord provided with the ferrups to ...

  • Page 9

    8 b. Press the t button twice until the display shows “3 system status info.” c. Press ¿ once. The display will now show “3 1 unit time.” d. Press ¿. A cursor will appear in the time shown. E. Notice that the bottom line of the display has changed to “ esc” to show you that you can now use the botto...

  • Page 10

    400 using the ferrups’ front panel lights the ferrups display includes three lights that show you the status of ferrups operation. The red alarm light means the ups has detected a problem. When this happens, the display shows an alarm message, and the ups beeps the morse code for the alarm. See sect...

  • Page 11

    To scroll down through menus or menu items in the same level: press the t button on the right side of the display. To scroll up through menus or menu items in the same level: press the s button. You can also look at the bottom line of the display, which includes the words “top” and “esc.” the button...

  • Page 12

    11 1 enter password 3 system status info 5 system config enter password 3 1 unit time 3 2 unit date 3 3 unit year 3 4 ac input volts 3 5 ac output volts 3 6 ac input current 3 7 ac output current 3 8 va out 3 9 watts out 3 10 % full load 3 11 power factor 3 12 output frequency 3 13 battery volts 3 1...

  • Page 13: 503 Entering A Password

    12 503 entering a password before you can change the setting of some ferrups parameters or menu items, you must enter a password. To do this, follow the steps below. The user password is 0377. 1. If the display is not already showing the menus, press the bottom right button (below the word “menu” on...

  • Page 14: 505 Parameters

    3. Move the cursor to the first digit you want to change, and use the s and t buttons to increase or decrease the number. Repeat this step for each digit that needs to be changed. 4. When you have finished, press ¿ to save the new setting. If you decide not to change the setting, press the bottom ri...

  • Page 15

    14 menu 2: system status (continued) menu 3: system status info by pressing ¿ while displaying this parameter, you can start a user test alarm to make sure the ferrups alarms properly or to test alarm contacts at the db9 communication port. By pressing ¿ again, you can stop the user test alarm. This...

  • Page 16

    15 menu 3: system status info (continued) menu 4: system id item and sample display password to change range explanation 3 10 % full load pctfload 90 % no change allowed. Not applicable. Percent of full load. The percentage of the ferrups’ total capacity that your equipment is using. 3 16 eeprom sta...

  • Page 17

    16 506 reading the ferrups logs your ferrups makes an entry in its logs every time it sounds an alarm or runs on inverter (battery power). This information can help diagnose power problems. You can display both the alarm and inverter logs at the unit’s display panel; both logs are in menu 6. Inverte...

  • Page 18

    These are the inverter codes: alarm log the alarm log is in menu 6, submenu 3. If you have already displayed inverter log entries, press the bottom right button to display “6 2 inverter log,” and press t once to scroll down to the alarm log. Then press ¿. If not, follow the steps below to display th...

  • Page 19

    18 alarm message morse code what it means how to react a low battery vbatt 40.0 v lowbatv 41.0 v minbattv 38.34 • — (a) the ups has shut down because the battery voltage is too low for the ups to continue operating on battery power. The battery charge is low because the ups was running on battery po...

  • Page 20: 701 Communication Options

    19 alarm message morse code what it means how to react k circuit breaker warning shutdown — • — (k) your equipment is drawing more current (amps) than the ups is designed to provide. (see your model’s output current rating.) the unit will shut down; the time until shutdown depends on the amount of o...

  • Page 21: 702 Db9 Port Pin Functions

    20 optional interface kits: for computer systems that already have ups monitoring software, best power offers interface cable kits for connecting the ferrups to your computer system. The kit includes the cable, adapters, and instructions. Optional internal bestlink™ snmp/web adapter: using simple ne...

  • Page 22: 801 Regular Maintenance

    21 1. A. Press the bottom right button (below “menu” on the display) to switch from the normal display to the menus. The display will show the top menu, “1 enter password.” b. Press t four times (until the display shows “5 system config”). C. Press ¿. The display will show “5 1 system config.” d. Pr...

  • Page 23

    22 900 specifications * size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the u.S. And canada. ** at 0.7 leading or distortion power factor. Size output protection according to all applicable local or national codes. *...

  • Page 24

    23 ac output with nominal input power and loads (protected equipment) voltage regulation: ±3% load regulation. Total voltage regulation under any line, load, or battery condition to within –8.3% and +5% of nominal. Input voltage range: at low voltages: 85-135 vac. At high voltages: 165-275 vac. Over...

  • Page 25

    24 protection dc input: dc fuse and battery charger overvoltage limit network. Output protection: the ferroresonant transformer inherently limits current and provides overload protection. Ferrups has high ac and low ac output voltage alarms, as well as an overload alarm. If the ac output voltage fal...

  • Page 26

    25 incompatible or defective. Replacement or repair will be made at best power’s worldwide service, highway 80, necedah, wisconsin 54646, u.S.A. Such repair or replacement shall be at best power’s expense. This warranty does not cover any taxes which may be due in connection with replacement or repa...

  • Page 27

    26 this warranty does not include any taxes which may be due in connection with replacement or repair nor any installation, transportation or postage costs. These expenses will be paid by purchaser. Replacement or repair will be made at best power’s worldwide service, highway 80, necedah, wisconsin ...

  • Page 28

    27 1100 notices 2-3 kva soft-wired (plug-in) and 50 hz models: this device complies with part 15 of the fcc rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference that may cause undesired opera...