Fetco CBS-2041e User Manual - page 11
11
Address Description
Range
Default Comment
60
and
61
Left Brew Valve
Flow Rate
Right Brew Valve
Flow Rate
0.30 – 0.50
If #59 is GAL
or
1.13 – 1.89
If #59 is LTR
0.40
1.51
62
and
63
Left Bypass Valve
Flow Rate
Right Bypass
Valve Flow Rate
0.28 – 0.38
If #59 is GAL
or
1.05 – 1.44
If #59 is LTR
0.33
1.24
Use this to compensate for minor discrepancies in
actual volume versus programmed volume. Set
lower to increase volume, higher to decrease
volume. The following formula can be used to
determine the correct setting:
ACTUAL VOLUME
PROGRAMMED VOLUME
X
CURRENT
SETTING
=
NEW
SETTING
64
Keypad Test
0 - 1
0
Tests function of control panel switches.
0 - Skip keypad test
1 - Keypad test active
Starting at the top, press each button. Display will
read the name of the switch being pressed.
Brew switches are named S1, S2, S3, etc.
The hot water switch must be pressed last, as this
will exit the test.
65
Relay Test
0 - 1
0
0 - Skip relay test. Loop back to #50
1 – Relay test active. Go to #90
Press to save the settings and exit Diagnostic mode.
Press again to exit Programming mode and return to Operating mode.
Relay Test
Tests the individual relays which control various components.
Use either batch button to actuate the relays.
To begin, you must first press the blinking Control Panel Power Switch.
Address Description
Comment
90
Left or Single Brew Valve
91
Right Brew Valve
92
Left or Single Bypass Valve
93
Right Bypass Valve
94
Hot Water Faucet
95 Fill
Valve
96
Heater
To protect the heaters, this test will work only if the tank is full.
97
Left or Single Brew Basket Lock
98
Right Brew Basket Lock
Press to exit Relay Test.
Press again to exit Diagnostic mode.
Press again to exit Programming mode and return to Operating mode.
Warning: During these
tests, hot water may
be dispensed from
the va lve being tested.