FFE Fireray 100RU Technical Bulletin

Manual is about: UL/ULC

Summary of Fireray 100RU

  • Page 1

    Features • microprocessor controlled • 50ru range 15 – 160 feet • 100ru range 160 – 330 feet • unique simple alignment • 12vdc or 24vdc operating voltage • selectable alarm thresholds • low current consumption • automatic reset • automatic contamination compensation • low level controller interface ...

  • Page 2

    22318.10.03 15.09.05 1 1. System description. Fireray 50/100ru detector comprises a transmitter and receiver contained within one enclosure. The detector installs to the building fabric between 1 and 2 feet from the ceiling. The transmitter emits an invisible infrared light beam that is reflected vi...

  • Page 3

    22318.10.03 15.09.05 2 3. Detector positioning. An infrared signal is projected out of the transmitter optics (see fig 3) to the reflector placed at the opposite end of the detection zone. The signal is reflected back to the receiver where it is analysed for fire and trouble. It is important that th...

  • Page 4

    22318.10.03 15.09.05 3 4. Installation. 4.1. Pre-installation at ground level. Confirm that all parts have been supplied as listed in the parts list. See page 9. Select the required alarm threshold using switches 3 and 4 (see fig. 4. For switch configuration settings). The factory default setting is...

  • Page 5

    22318.10.03 15.09.05 4 5. Prism targeting mode. Apply power to the detector. There is a 5 seconds pre-charge delay after power is applied to allow the internal circuits to stabilise correctly. After this period the red indicator will flash once to indicate that the model is a 50ru or will flash twic...

  • Page 6

    22318.10.03 15.09.05 5 • flashing amber the detector is receiving a weak signal and is attempting to increase the infrared power output. • off the detector has optimised the infrared power and receiver gain for the current orientation of the detector and prism. This does not mean that the detector t...

  • Page 7

    22318.10.03 15.09.05 6 amber constant amber red red amber neither 6.3. Alignment process flow diagram. Wait until both led’s stop flashing (up to 30 seconds) return to prism targeting mode slowly turn the thumbwheel in the same direction reverse the direction of the thumbwheel exit alignment mode an...

  • Page 8

    22318.10.03 15.09.05 7 6.4. Exiting alignment mode. Do not remove the detector from the wall during this action. Using the mode switch (see fig. 4) select run mode (switch will be in the down position). On exiting alignment mode the detector will perform an internal calibration check, this can take ...

  • Page 9

    22318.10.03 15.09.05 8 7.2. Trouble test. Cover the prism totally with a non-reflective material and confirm that the detector indicates a trouble condition after approximately 10 seconds (the amber led on the detector will illuminate, and the trouble relay opening will indicate this). The trouble c...

  • Page 10

    22318.10.03 15.09.05 9 9. Typical single zone wiring diagram. This diagram is an example for a single fireray being the only device on a zone. The correct operation for fire and trouble should always be checked connected to a typical panel. Relays are shown in normal powered no fault condition. Cont...

  • Page 11

    22318.10.03 15.09.05 10 10. Detector interface assembly configuration settings (not to scale). On 4 3 2 1 x x x x x x x x x dip switch x x x x x x x x x 2 x 1 3 x 4 1 2 3 4 on settings fig. 4. 2-pin port for optional low level controller.

  • Page 12

    22318.10.03 15.09.05 11 11. Technical data. • operating range fireray 50ru 15 to 160 feet • operating range fireray 100ru 160 to 330 feet • lateral coverage 30 feet (either side of the beam) • supply voltage 10.2 to 30 volts dc • quiescent current less than 4ma • alarm/trouble current less than 20ma...