GAI-Tronics 709-901 User Manual - Installation
P
UB
.42004-699L2D
M
ODEL
709-901
S
MART
S
ERIES
H
ANDSET
/S
PEAKER
A
MPLIFIER
P
AGE
5 of 14
f:\standard ioms - current release\42004 instr. manuals\42004-699l2d.doc
10/13
Installation
CAUTION
Do not install this equipment in hazardous areas other than in an approved
enclosure, or areas other than those indicated on the approval listing in the “Specifications” section
of this manual. Such installation may cause a safety hazard and consequent injury or property
damage.
WARNING
Do not disconnect equipment while energized.
The Model 709-901 SmartSeries Handset/Speaker Amplifier assembly plugs directly into the following
GAI-Tronics SmartSeries hazardous area enclosures listed below. Use extra care not to damage the
protruding latch wings of connector J2 located on the bottom edge of the amplifier during installation.
707-001-UL/EX; -EX-F07045
UL Listed SmartSeries Amplifier Enclosures
708-001-UL/EX; -EX-F07048
UL Listed SmartSeries Single Party Enclosures
7085-001-UL/EX; -EX-F07044
UL Listed SmartSeries Multi-Party Enclosures
7085-004-UL/EX; -EX-F07049
UL Listed SmartSeries Multi-Party Enclosures with Alternate Page*
7085-005-UL/EX; -EX-F07050
UL Listed SmartSeries Multi-Party Enclosures with RTU Control*
Models 707-001-UL/EX and -EX-F07045
Ensure that the connectors mate securely and then tighten the four screws in the corners of the front panel.
Tighten to 10 to 12 in-lb. or 1.13 to 1.36 N-m.
Models 708-001-UL/EX, -EX-F07048, 7085-001-UL/EX, -EX-F07044, 7085-004-
UL/EX and -EX-F07049
1. When installing the amplifier in these enclosures, connect the 2-point plug cable from the push-to-
page operator to the 2-point receptacle on the bottom of the amplifier chassis.
2. Connect the 6-point plug cable from the hookswitch and handset to the 6-point receptacle on the
bottom of the amplifier chassis.
3. Ensure that the connectors mate securely and then tighten the four screws in the corners of the front
panel. Tighten to 10 to 12 in-lb. or 1.13 to 1.36 n-m.