3
REMOTE CONTROL FUNCTION
REMOTE CONTROL FUNCTIONS
-
If the room temperature is lower than the setting temperature, the
heating mode is activated. The motor driven valve is triggered. The
internal fan works at the set speed.
-
If the room temperature is equal to the setting temperature + 0.5°C,
the heating mode is stopped. The motor driven valve and the internal
fan are disconnected.
-
The setting temperature range is 15° - 30°C.The internal fan speed can
be set on Min, Med, Max and Auto.
-
The motor driven valve will be activated/deactivated after a delay time of
30 sec
-
If the water temperature is equal to 38°C, the motor driven valve is
activated and the internal fan is deactivated.
-
If the water temperature is >38°C the motor driven valve is activated. The
internal fan will continue working at the set speed.
-
If the water temperature is >75°C the motor driven valve is deactivated.
The internal fan will continue working at the set speed.
COOLING
-
If the room temperature is higher than the set temperature, the cooling
mode is activated. The motor driven valve is activated. The internal fan
works at the set speed.
-
If the room temperature is equal to the setting temperature -0.5°C, the
cooling mode is stopped. The motor driven valve is deactivated. The
internal fan works at the set speed.
-
The setting temperature range is 15° - 30°C.
-
The internal fan speed can be set on Min, Med, Max and Auto.
-
The motor driven valve will be activated/deactivated after a delay time of
30 sec.
-
If the water temperature is equal to or lower than 2°C, the motor driven
valve is deactivated and the internal fan continues working at the set
speed.
TIMER
-
The switch off timer can be set only when the system is ON.
-
The switch on timer can be set only when the system is OFF.
-
The maximum setting time is 24 hours.
-
Switching the unit on/off will cancel the timer mode.
4
RATED TECHNICAL DATA
- Cooling mode: water temperature 7/12°C, air temperature 27°C dry bulb, 19°C wet bulb
- Heating mode: water temperature 70-60°C, air temperature 20°C
- Sound pressure calculated for 1 meter distance, under the unit
Fan speed
WH10
WH20
WH30
Total cooling capacity
High
kW
2,27
3,06
4,28
Sensible cooling capacity
High
kW
1,72
2,41
3,15
Water flow
l/h
389
524
734
Water pressure drop
kPa
15
13
18
Heating capacity
High
kW
5,34
7,87
9,96
Water flow
l/h
468
685
873
Water pressure drop
kPa
15
18
19
Water connection
"
1/2
1/2
1/2
Drain connection
mm
22
22
22
Water content
dm
3
0,5
1,1
1,8
High
m
3
/h
415
515
750
Med
m
3
/h
360
460
630
Low
m
3
/h
335
420
570
Power supply
V / f / Hz
230 /1 / 50
230 /1 / 50
230 /1 / 50
Current absorption
High
A
0,15
0,17
0,24
Power input
W
34
39
51
High
dB(A)
54
54
60
Med
dB(A)
50
51
55
Low
dB(A)
48
49
51
High
dB(A)
46
46
52
Med
dB(A)
42
43
47
Low
dB(A)
40
41
43
Overall dimension: height
mm
276
320
330
Overall dimension: lenght
mm
870
1020
1160
Overall dimension: depth
mm
183
185
213
Approx. weight
kg
12
15
18
Sound power level
Sound pressure level
Air flow