Gamewell FCI GF505 Series Installation, Programming, And Operation Manual

Manual is about: Fire alarm control panels

Summary of GF505 Series

  • Page 1

    0 gamewell-fci 12 clintonville road northford, ct 06472 gf505 & gf510 series fire alarm control panels installation, programming & operation manual p/n: 53164 rev. A 03/26/07 ecn 07-129.

  • Page 2

    Precaularge.Pmd 02/26/2007 an automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, do...

  • Page 3: Fcc Warning

    Precaularge.Pmd 02/26/2007 warning - several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and asso- ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables wh...

  • Page 4: Table of Contents

    Table of contents 4 gf505 & gf510 p/n: 53164:a 03/26/07 section 1: product description .........................................................................................................................12 1.1: product features ......................................................................

  • Page 5

    Gf505 & gf510 p/n: 53164:a 03/26/07 5 table of contents 2.8.9: gfann-rly relay module.............................................................................................................50 2.8.9.1 gfann-rly board layout ...........................................................................

  • Page 6

    Table of contents 6 gf505 & gf510 p/n: 53164:a 03/26/07 3.6.1: input zones - enable/disable ............................................................................................................99 3.6.2: history .....................................................................................

  • Page 7

    Gf505 & gf510 p/n: 53164:a 03/26/07 7 table of contents 6.4.2: selecting and locating batteries.......................................................................................................125 appendix a: ademco contact id format ................................................................

  • Page 8

    Notes 8 gf505 & gf510 series pn 53164:a 3/26/2007.

  • Page 9

    Gf505 & gf510 series pn 53164:a 3/26/2007 9 it is imperative that the installer understand the requirements of the authority having jurisdiction (ahj) and be familiar with the standards set forth by the following regulatory agencies: • underwriters laboratories standards • nfpa 72 national fire alar...

  • Page 10

    10 gf505 & gf510 series pn 53164:a 3/26/2007 gf505 series main circuit board d act p ho ne l in e jacks (n on pow er -li m it ed ) resett ab le p o w e r - 24 v d c fi lt e red, power -l imi ted ( 0.500 am ps max imum ) to s m ok e dete c tor s ( idc ). S uper v is ion r equi red. N o nr es et tabl ...

  • Page 11

    Gf505 & gf510 series pn 53164:a 3/26/2007 11 gf510 series main circuit board dact p hone li ne j ac ks (n onpow er -li m it ed) e s e ttab le p o w e r - 24 v d c fi lt e re d , wer -l imi ted ( 0.500 amps m ax im um ) s m ok e dete c to rs ( idc ). U p er v is io n r e qui red. Nr e s ettabl e o r ...

  • Page 12

    Product description product features 12 gf505 & gf510 series pn 53164:a 3/26/2007 section 1 product description the gf505 is a five zone facp (fire alarm control panel) and the gf510 is a ten zone facp. The information in this manual refers to both the gf505 and gf510 unless otherwise specified. The...

  • Page 13

    Specifications product description gf505 & gf510 series pn 53164:a 3/26/2007 13 gfann-80 remote lcd annunciator gfann-i/o led driver gfann-s/pg printer module gfann-rly relay module gfann-led annunciator module • 80-character lcd display (backlit) • real-time clock/calendar with daylight savings tim...

  • Page 14

    Product description specifications 14 gf505 & gf510 series pn 53164:a 3/26/2007 alarm zones 6 - 10 on tb6 (gf510 only) supervised and power-limited circuitry operation: all zones style b (class b) normal operating voltage: nominal 20 vdc alarm current: 15 ma minimum short circuit current: 40 ma max....

  • Page 15

    Controls and indicators product description gf505 & gf510 series pn 53164:a 3/26/2007 15 form-c relays - programmable - tb8 relay 1 (factory default programmed as alarm relay) relay 2 (factory default programmed as fail-safe trouble relay) relay 3 (factory default programmed as supervisory relay) re...

  • Page 16

    Product description controls and indicators 16 gf505 & gf510 series pn 53164:a 3/26/2007 function keys: • acknowledge/step • alarm silence • drill • system reset (lamp test) service/program keys: • keys labeled 1 to 9 • * key • # key • 0 (recall) key • 1st event key • clear key • escape key • mode k...

  • Page 17

    Digital alarm communicator/transmitter product description gf505 & gf510 series pn 53164:a 3/26/2007 17 1.4 digital alarm communicator/transmitter two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled ph1 for primary phone line and ph2 for secondary phone line. ...

  • Page 18

    Product description optional modules and accessories 18 gf505 & gf510 series pn 53164:a 3/26/2007 facp lcd display. Gfann-led annunciator module the gfann-led annunciator module mounts in the dp-51050led/w dress panel and provides three leds for each zone: alarm, trouble and supervisory. Gfann-rly r...

  • Page 19

    Telephone requirements and warnings product description gf505 & gf510 series pn 53164:a 3/26/2007 19 1.7 telephone requirements and warnings 1.7.1 telephone circuitry ringer equivalence number (ren) = 0.0b ac impedance: 10.0 mega ohm complies with fcc part 68 mates with rj31x male connector supervis...

  • Page 20

    Product description telephone requirements and warnings 20 gf505 & gf510 series pn 53164:a 3/26/2007 1.7.3 telephone company rights and warnings the telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or proc...

  • Page 21

    Backbox mounting installation gf505 & gf510 series pn 53164:a 3/26/2007 21 section 2 installation the cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting if off the hinges. The cabinet mounts using two key slots at the top...

  • Page 22

    Installation backbox mounting 22 gf505 & gf510 series pn 53164:a 3/26/2007 9050ud encl .C dr figure 2.2 cabinet dimensions hinge slot for optional dress panel semi-flush mounting hole mounting slots for optional trim ring hinge slot for optional dress panel semi-flush mounting do not recess box more...

  • Page 23

    Backbox mounting installation gf505 & gf510 series pn 53164:a 3/26/2007 23 figure 2.3 backbox and battery box 9050ud ca b.Cdr.

  • Page 24

    Installation operating power 24 gf505 & gf510 series pn 53164:a 3/26/2007 2.2 operating power warning: several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting c...

  • Page 25

    Input circuits installation gf505 & gf510 series pn 53164:a 3/26/2007 25 2.3 input circuits the gf505 has five idcs (initiating device circuits) and the gf510 has ten idcs. Each circuit is compatible with system sensor’s i 3 smoke detectors which generate a maintenance signal when the detector becom...

  • Page 26

    Installation input circuits 26 gf505 & gf510 series pn 53164:a 3/26/2007 combination waterflow/supervisory zone a combination waterflow/supervisory circuit allows an facp to distinguish between an alarm switch (waterflow device) and a supervisory switch (tamper) installed on the same circuit. Any ci...

  • Page 27

    Output circuits installation gf505 & gf510 series pn 53164:a 3/26/2007 27 2.4 output circuits 2.4.1 notification appliance circuits each of the four style y (class b) notification appliance circuits can output a maximum of 3.0 amps of current. Total current drawn from these as well as other dc power...

  • Page 28

    Installation output circuits 28 gf505 & gf510 series pn 53164:a 3/26/2007 2.4.2 special application dc power output connections special application resettable and nonresettable 24 vdc power is available on the gf505/ gf510 control panel. 2.4.3 relays - programmable the gf505/gf510 control panels pro...

  • Page 29

    Output circuits installation gf505 & gf510 series pn 53164:a 3/26/2007 29 2.4.4 remote synchronization output synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critic...

  • Page 30

    Installation power-limited wiring requirements 30 gf505 & gf510 series pn 53164:a 3/26/2007 2.5 power-limited wiring requirements power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from an...

  • Page 31

    Digital communicator installation gf505 & gf510 series pn 53164:a 3/26/2007 31 2.6 digital communicator two independent telephone lines can be connected to the control panel. Telephone line control/ command is made possible via double line seizure as well as usage of an rj31x style interconnection. ...

  • Page 32

    Installation installation of optional modules 32 gf505 & gf510 series pn 53164:a 3/26/2007 2.7 installation of optional modules caution: remove all power (ac and dc) before installing or removing modules or wiring. 2.7.1 cac-5x class a converter module 2.7.1.1 installation the cac-5x module can be u...

  • Page 33

    Installation of optional modules installation gf505 & gf510 series pn 53164:a 3/26/2007 33 2.7.1.2 wiring nacs and idcs for class a wire the style z (class a) notification appliance circuits using tb5 of the gf505/gf510 and tb2 of the cac-5x module. Wire the style d (class a) initiating device circu...

  • Page 34

    Installation installation of optional modules 34 gf505 & gf510 series pn 53164:a 3/26/2007 2.7.2 4xtmf option module the 4xtmf module can be plugged into connectors j4 and j5 on the main circuit board. The following steps must be followed when installing the 4xtmf module: 1. Remove all power (ac and...

  • Page 35

    Installation of optional modules installation gf505 & gf510 series pn 53164:a 3/26/2007 35 2.7.2.1 4xtmf transmitter module installation the 4xtmf provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the r...

  • Page 36

    Installation ann-bus devices 36 gf505 & gf510 series pn 53164:a 3/26/2007 2.8 ann-bus devices warning! Disconnect all sources of power (ac and dc) before installing or removing any modules or wiring. A variety of optional devices can be connected to the facp ann-bus communication circuit. Compatible...

  • Page 37

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 37 after calculating the total worst case current draw, table 2.1 specifies the maximum distance the modules can be located from the facp on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wir...

  • Page 38

    Installation ann-bus devices 38 gf505 & gf510 series pn 53164:a 3/26/2007 wiring distance calculation example: suppose a system is configured with the following ann-bus modules: • 2 gfann-80 remote fire annunciators • 1 gfann-s/pg serial/parallel printer interface module • 1 gfann-i/o led driver mod...

  • Page 39

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 39 2.8.1.3 powering ann-bus devices from auxiliary power supply figure 2.19 illustrates the powering of ann-bus devices from an auxiliary power supply such as the hpf24s6/8, when the maximum number of ann-bus devices exceeds the ...

  • Page 40

    Installation ann-bus devices 40 gf505 & gf510 series pn 53164:a 3/26/2007 2.8.3 gfann-80 remote fire annunciator the gfann-80 annunciator is a compact, 80 character, backlit lcd remote fire annunciator which mimics the facp display. It also provides system status indicators for ac power, alarm, trou...

  • Page 41

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 41 2.8.5.3 wiring gfann-80 to facp the following steps can be used as a guide to wire the annunciator. Make certain all power has been removed from the facp prior to annunciator installation. 1. Route wires from hole in backplate...

  • Page 42

    Installation ann-bus devices 42 gf505 & gf510 series pn 53164:a 3/26/2007 the following table shows the gfann-80 connections to the gf505/gf510. Programming following installation and wiring of the gfann-80 lcd annunciator to the facp, the annunciator must be added to the system via facp programming...

  • Page 43

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 43 2.8.6 gfann-s/pg serial/parallel printer interface installation the gfann-s/pg serial/parallel printer interface module allows the ancillary connection of a serial and/or parallel printer to the facp for a real-time log of sys...

  • Page 44

    Installation ann-bus devices 44 gf505 & gf510 series pn 53164:a 3/26/2007 2.8.6.2.1 connecting prn printer remote printers require a primary ac power source. If required for the fire alarm system configuration (for example, a proprietary fire alarm system), a remote printer requires a secondary powe...

  • Page 45

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 45 2.8.7 gfann-i/o led driver module the gfann-i/o is an led driver module that can be used in a wide variety of applications, including as an interface with most customized graphic annunciators. The gfann-i/o can drive up to 40 ...

  • Page 46

    Installation ann-bus devices 46 gf505 & gf510 series pn 53164:a 3/26/2007 2.8.7.3 gfann-i/o connection to facp the gfann-i/o connects to the facp via the ann-bus as illustrated in figure 2.23. After the gfann-i/o is connected to the panel, it must be added to the system via facp programming. Figure ...

  • Page 47

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 47 2.8.7.4 gfann-i/o module led wiring there are four 12-pin connectors on the gfann-i/o module for connecting leds. Each set of 10 leds get their power from pin 11 of the corresponding connector. Internal resistors are sized so ...

  • Page 48

    Installation ann-bus devices 48 gf505 & gf510 series pn 53164:a 3/26/2007 2.8.8 gfann-led annunciator module the gfann-led annunciator module provides led annunciation of general system faults and input zones/points when used with a compatible facp. The gfann-led module provides alarm (red), trouble...

  • Page 49

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 49 2.8.8.4 gfann-led connection to facp figure 2.26 illustrates the gfann-led board wiring connections to the facp. Figure 2.26 gfann-led connection to facp facp gfann-led ann-bus +24 vdc -24 vdc.

  • Page 50

    Installation ann-bus devices 50 gf505 & gf510 series pn 53164:a 3/26/2007 2.8.9 gfann-rly relay module the gfann-rly relay module provides 10 programmable form-c relays when used with a compatible facp. 2.8.9.1 gfann-rly board layout figure 2.27 illustrates the gfann-rly board showing locations of s...

  • Page 51

    Ann-bus devices installation gf505 & gf510 series pn 53164:a 3/26/2007 51 2.8.9.4 gfann-rly connection to facp figure 2.28 illustrates the gfann-rly board wiring connections to the facp. Figure 2.28 gfann-rly connection to facp facp gfann-rly ann-bus +24 vdc -24 vdc.

  • Page 52

    Programming user programming 52 gf505 & gf510 series pn 53164:a 3/26/2007 section 3 programming 3.1 user programming the gf505/gf510 facp is completely field programmable using the panel keypad and requires no special software skills. While programming the facp, the fire protection capabilities of t...

  • Page 53

    Initial power-up programming gf505 & gf510 series pn 53164:a 3/26/2007 53 user programming levels there are two user programming levels: • user master program level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc. • user maintena...

  • Page 54

    Programming programming and passwords 54 gf505 & gf510 series pn 53164:a 3/26/2007 to access user programming mode, press the enter or mode key. The lcd will display the following: to enter the user programming mode, press 2. The display will read as follows: entering the master level password (defa...

  • Page 55

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 55 3.5 master programming level when the master program level password is entered, the control panel will enter user programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the sy...

  • Page 56

    Programming master programming level 56 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.1 input zones the input zones option allows the user to initially program or change the programming for the five input zones (circuits) on the gf505 or the ten input zones (circuits) on the gf510. Pressing 1, while...

  • Page 57

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 57 enable/disable zone to enable or disable the zone, press the 1 key while viewing the edit input zone screen #2. Each press of the key will toggle the screen between enabled yes and enabled no. If enabled no is selected...

  • Page 58

    Programming master programming level 58 gf505 & gf510 series pn 53164:a 3/26/2007 pressing the down arrow key will display additional zone types as indicated in the following table. While viewing any zone type screen, select the type of zone being programmed by pressing the corresponding keyboard nu...

  • Page 59

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 59 pas/pre-signal delay pressing 1 while viewing edit input zone screen #3 will display the following screen: pre-signal the pre-signal option programs the zone to delay panel activation for a preprogrammed time delay of ...

  • Page 60

    Programming master programming level 60 gf505 & gf510 series pn 53164:a 3/26/2007 pressing 1 while viewing the noun/adjective screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the adjective screens. Press the number correspond...

  • Page 61

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 61 pressing 2 while viewing the noun/adjective screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the noun screens. Press the number corresponding t...

  • Page 62

    Programming master programming level 62 gf505 & gf510 series pn 53164:a 3/26/2007 description the description selection allows the programmer to enter additional information about the detector currently being programmed. This information will be displayed as part of the device label on the display. ...

  • Page 63

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 63 as an example, the user could quickly enter ‘flr_3_room_305’ as follows: 1. The cursor is on the first letter of the adjective field. Press the zero key twice to display flr_3 2. With the cursor on the first letter of ...

  • Page 64

    Programming master programming level 64 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.2.1 enabled pressing 1 while viewing nac screen #1 will cause the display to change to enabled no. This will prevent the selected main circuit board nac from activating its devices. Each press of the 1 key will cau...

  • Page 65

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 65 the programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding selections are: • steady - a continuous output with no coding • march time - 120 ppm (p...

  • Page 66

    Programming master programming level 66 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.2.2.2.1 maximum number of strobes for synchronization the maximum current draw for a notification appliance circuit cannot exceed 3.0 amps for models with the flps-7 power supply (refer to the ac power section unde...

  • Page 67

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 67 3.5.2.4 auto silence the auto silence feature, when enabled, automatically silences all main circuit board silenceable notification appliances after a programmed length of time. To enable this feature and program the t...

  • Page 68

    Programming master programming level 68 gf505 & gf510 series pn 53164:a 3/26/2007 to program relay 1, 2 or 3, press the number corresponding to the selected relay. The following screens will appear for each relay to be programmed: while viewing the selected screen, press the number corresponding to ...

  • Page 69

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 69 3.5.4 system setup system setup allows the programmer to configure the following control panel features: • timers: this option allows the programmer to set the pas (positive alarm sequence) time delay, pre-signal time ...

  • Page 70

    Programming master programming level 70 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.4.1 timers timer delays for pas, pre-signal and waterflow activation can be programmed by pressing 1 while viewing system setup screen #1. The following screen will be displayed: 3.5.4.1.1 pas (positive alarm seque...

  • Page 71

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 71 a flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be stored in the ...

  • Page 72

    Programming master programming level 72 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.4.2 banner the top line of the display, which appears when the control panel is in normal mode, can be changed by using the banner option. Pressing 2 while viewing system setup screen #1 will cause the following to...

  • Page 73

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 73 3.5.4.3 time-date the control panel time and date can be changed by pressing 3 while viewing the system setup screen #1. The following screen will be displayed: 3.5.4.3.1 time to change the time, press 1 while viewing ...

  • Page 74

    Programming master programming level 74 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.4.3.2 date to change the date, press 2 while viewing the time-date screen. The following screen will be displayed: a flashing cursor is located toward the top left of the display. Below the cursor is the current da...

  • Page 75

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 75 pressing 3 while viewing daylight savings screen #1 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will begin. In the first sub-screen, pressing 1 wil...

  • Page 76

    Programming master programming level 76 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.5.1 ann-bus pressing 1 while viewing the option modules screen will cause the control panel to display the following screens. A variety of ann-bus option modules can be installed in the facp. These devices communic...

  • Page 77

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 77 in the technical information screen, pressing 1 for type will display the following screens: press the number corresponding to the module type, if any, that is installed with the selected address. This will enable the ...

  • Page 78

    Programming master programming level 78 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.5.1.4 ann-s/pg options screen the printer option allows the user to configure the optional printer. Pressing 1 while viewing the ann-bus screen #2 will display the following screens: pressing 1 for port while viewi...

  • Page 79

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 79 3.5.5.1.5 gfann-i/o led zone assignments the information displayed by leds on every gfann-i/o module is not programmable and will therefore be as indicated in the following table. Led zone (any address) 1 ac fault 2 ge...

  • Page 80

    Programming master programming level 80 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.5.1.6 ann-80 options screen pressing 2 while ann-bus screen #2 will display the following screen: the piezo enable option allows the programmer to select whether the piezo sounder on any installed gfann-80 module w...

  • Page 81

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 81 3.5.5.2 ann-rly options screen pressing 1 for ann-rly options while viewing ann-bus screen #3 will cause the following screen to be displayed: the gfann-rly module provides ten form-c relays which can be programmed for...

  • Page 82

    Programming master programming level 82 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.5.3 onboard dact the onboard dact (digital alarm communicator/transmitter) provides communication to a central station. Pressing 2 while viewing the option module screen will cause the following screens to be displ...

  • Page 83

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 83 3.5.5.3.2 secondary phone press 2 while viewing onboard dact screen to program the type of secondary phone line being connected to the dact. The following screen will be displayed: press 1 to select touchtone dialing, ...

  • Page 84

    Programming master programming level 84 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.5.3.3.3 central station primary and secondary phone numbers pressing 1 for primary or 2 for secondary, while viewing central station screen #2, will display the following screens. Note that the following informatio...

  • Page 85

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 85 test time interval pressing 1 while viewing primary/secondary screen #1 will cause the following screens to be displayed: the test report sent to the central station phone number may be sent once every 6, 8, 12 or 24 h...

  • Page 86

    Programming master programming level 86 gf505 & gf510 series pn 53164:a 3/26/2007 24 hour test time pressing 3 while viewing primary/secondary screen #1 will cause the following screen to be displayed: use the 24 hour test time screen to program the time that the dact will transmit the 24 hour test ...

  • Page 87

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 87 communication format pressing 1 while viewing primary/secondary screen #3 will cause the following screen to be displayed: the communication format is determined by the type of receiver that the dact is transmitting to...

  • Page 88

    Programming master programming level 88 gf505 & gf510 series pn 53164:a 3/26/2007 the following table lists the zone alarm types that can be programmed for zones 1 through 10 and the corresponding event codes for ademco contact id and sia dcs formats. Note that table 3.3 on page 89, table 3.4 on pag...

  • Page 89

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 89 ademco contact id format - primary central station phone number the information shown in table 3.3 is automatically programmed for the primary central station phone number event codes when ademco contact id format is s...

  • Page 90

    Programming master programming level 90 gf505 & gf510 series pn 53164:a 3/26/2007 ademco contact id format - secondary central station phone number the information shown in table 3.4 is automatically programmed for the secondary central station phone number event codes when ademco contact id format ...

  • Page 91

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 91 sia-dcs format - primary central station phone number the information shown in table 3.5 is automatically programmed for the primary central station phone number event codes when sia-dcs format is selected. To disable ...

  • Page 92

    Programming master programming level 92 gf505 & gf510 series pn 53164:a 3/26/2007 primary # zone 4 dirty ft4 fj4 primary # zone 5 dirty ft5 fj5 primary # zone 6 dirty ft6 fj6 primary # zone 7 dirty ft7 fj7 primary # zone 8 dirty ft8 fj8 primary # zone 9 dirty ft9 fj9 primary # zone 10 dirty ft10 fj1...

  • Page 93

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 93 sia-dcs format - secondary central station phone number the information shown in table 3.6 is automatically programmed for the secondary central station phone number event codes when sia-dcs format is selected. To disa...

  • Page 94

    Programming master programming level 94 gf505 & gf510 series pn 53164:a 3/26/2007 secondary # zone 2 dirty ft2 fj2 secondary # zone 3 dirty ft3 fj3 secondary # zone 4 dirty ft4 fj4 secondary # zone 5 dirty ft5 fj5 secondary # zone 6 dirty ft6 fj6 secondary # zone 7 dirty ft7 fj7 secondary # zone 8 d...

  • Page 95

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 95 3.5.6 history the history option allows an authorized user to view or erase events which have occurred in the control panel. Pressing 3 while viewing programming screen #2 will display the history options as shown in t...

  • Page 96

    Programming master programming level 96 gf505 & gf510 series pn 53164:a 3/26/2007 3.5.7 walktest walktest allows an individual to test the fire alarm system without the necessity to reset the control panel after each device activation. Pressing 1 while viewing the programming screen #3 will cause th...

  • Page 97

    Master programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 97 3.5.8 clear program pressing 2 while viewing programming screen #3, will select the clear program option. The control panel will provide a warning to the user by prompting with the following display: pressing 1 will ca...

  • Page 98

    Programming maintenance programming level 98 gf505 & gf510 series pn 53164:a 3/26/2007 3.6 maintenance programming level to access maintenance programming mode, press the enter key. The lcd will display the following: to enter the maintenance programming mode, press 2. The display will read as follo...

  • Page 99

    Maintenance programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 99 3.6.1 input zones - enable/disable the zone setup option allows the user to enable or disable desired zones. Pressing 1 for zone setup, while viewing maintenance screen #1 will cause the following screens to be di...

  • Page 100

    Programming maintenance programming level 100 gf505 & gf510 series pn 53164:a 3/26/2007 pressing 1 while viewing the history screen will cause the following screen to be displayed: to view all the events which have occurred in the control panel since the history file was last erased, press 1 while v...

  • Page 101

    Maintenance programming level programming gf505 & gf510 series pn 53164:a 3/26/2007 101 3.6.4 time-date to program the time and date into the control panel, press 1 while viewing maintenance screen #2. The following display will appear: to change the time, press 1 to display the following screen: a ...

  • Page 102

    Operating instructions panel control buttons 102 gf505 & gf510 series pn 53164:a 3/26/2007 section 4 operating instructions 4.1 panel control buttons 4.1.1 acknowledge/step the first press of the acknowledge/step key silences the piezo sounder, changes flashing leds to steady and also changes the st...

  • Page 103

    Led indicators operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 103 4.2 led indicators the five led indicators, which are located on the front panel, operate as follows: ac power this is a green led which illuminates if ac power is applied to the facp. A loss of ac power will turn of...

  • Page 104

    Operating instructions trouble operation 104 gf505 & gf510 series pn 53164:a 3/26/2007 4.4 trouble operation with no alarms in the system, the detection of a trouble will cause the following: • the piezo to pulse 1 second on and 1 second off • the system trouble led to flash one second on and one se...

  • Page 105

    Alarm operation operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 105 pressing the acknowledge/step or alarm silence key will cause the pulsing piezo to silence and the system trouble led to change from flashing to on steady. This block acknowledgment occurs regardless of the number o...

  • Page 106

    Operating instructions supervisory operation 106 gf505 & gf510 series pn 53164:a 3/26/2007 • fourth line in display: time; the current time in this example is 10:00a which represents 10:00 am date; the current month, day and year in this example is 09 for september, 08 for the 8th day of the month a...

  • Page 107

    Process monitor operation operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 107 4.7 process monitor operation process monitor operation will initiate the following events: • the piezo sounder pulses ¼ second on and ¼ second off • the lcd displays a process monitor message along with t...

  • Page 108

    Operating instructions disable/enable operation 108 gf505 & gf510 series pn 53164:a 3/26/2007 4.10 disable/enable operation input zones which are disabled do not cause an alarm or any zone activation. Disabled nacs are held in the off state. All disabled zones/nacs are treated as if they were in tro...

  • Page 109

    Presignal operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 109 4.15 presignal presignal option programs an initiating device to delay the activation of nacs while allowing visual verification by a person. Once a detector triggers an alarm, the onboard piezo sounds immediately, but th...

  • Page 110

    Operating instructions special system timers 110 gf505 & gf510 series pn 53164:a 3/26/2007 4.17 special system timers 4.17.1 silence inhibit timer this option, if selected, prevents the alarm silence key from functioning for 60 seconds following an alarm. A new alarm during the initial 60 second per...

  • Page 111

    Walktest operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 111 4.17.5 alarm verification (none or one minute) if alarm verification is selected, a smoke detector activation will cause the facp to reset the detector by removing power for 6 seconds. Power is reapplied and a 17 second re...

  • Page 112

    Operating instructions read status 112 gf505 & gf510 series pn 53164:a 3/26/2007 4.19 read status read status functions do not require a password. The control panel will continue to provide fire protection while in read status mode. This mode can be entered while the control panel is in alarm or tro...

  • Page 113

    Read status operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 113 4.19.1 input zones pressing 1 while viewing read status screen #1 will cause the following screens to be displayed: pressing the down arrow key will allow the selection of zones 4-5 for the gf505 and zones 4-10 for the ...

  • Page 114

    Operating instructions read status 114 gf505 & gf510 series pn 53164:a 3/26/2007 the resulting screens will display the following information: • enable/disable status • coding selection (temporal, steady, etc.) • silenceable/nonsilenceable • auto silence enable/disable and time delay (in minutes) • ...

  • Page 115

    Read status operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 115 4.19.5 timers pressing 2 while read status screen #2 will display the following screen: these screens allow the operator to view the various timer settings. 4.19.6 daylight savings pressing 3 while read status screen #2...

  • Page 116

    Operating instructions read status 116 gf505 & gf510 series pn 53164:a 3/26/2007 4.19.7 history pressing 1 while viewing read status screen #3 will display the following screens: the operator can view all events which have been stored in the history file, only alarms or other events, such as trouble...

  • Page 117

    Read status operating instructions gf505 & gf510 series pn 53164:a 3/26/2007 117 4.19.9 ann-bus pressing 3 while viewing read status screen #3 will display the settings for the ann-bus options as shown in the following screens: ann-bus screen #1 indicates whether the ann-bus is enabled (yes/no). Pre...

  • Page 118

    Operating instructions read status 118 gf505 & gf510 series pn 53164:a 3/26/2007 4.19.10 central station pressing 2 while viewing read status screen #4 will display the following screens: central station screen #1 indicates whether the central station reporting is enabled or disabled, if the reports...

  • Page 119

    Read status central station communications gf505 & gf510 series pn 53164:a 3/26/2007 119 section 5 central station communications the control panel transmits zone and system status reports to central stations via the public switched telephone network. Two supervised telephone line connections are ma...

  • Page 120

    Central station communications transmittal priorities 120 gf505 & gf510 series pn 53164:a 3/26/2007 5.1 transmittal priorities the integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in descending order: 1. Alarms (highest priority level) pul...

  • Page 121

    Transmittal priorities central station communications gf505 & gf510 series pn 53164:a 3/26/2007 121 the table below shows ul listed receivers which are compatible with the gf505/gf510. 1. With 685-8 line card with rev. 4.4d software 2. With 124077v2.00 or later receiver and 126047 line card rev. M o...

  • Page 122

    Power supply calculations overview 122 gf505 & gf510 series pn 53164:a 3/26/2007 section 6 power supply calculations 6.1 overview this section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the follow...

  • Page 123

    Calculating the system current draw power supply calculations gf505 & gf510 series pn 53164:a 3/26/2007 123 6.3 calculating the system current draw 6.3.1 overview the control panel must be able to power all internal and external devices continuously during the non-fire alarm condition. To calculate ...

  • Page 124

    Power supply calculations calculating the system current draw 124 gf505 & gf510 series pn 53164:a 3/26/2007 table 6-3 contains three columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from c...

  • Page 125

    Calculating the battery size power supply calculations gf505 & gf510 series pn 53164:a 3/26/2007 125 6.4 calculating the battery size use table 6-4 to calculate the total standby and alarm load in ampere hours (ah). This total load determines the battery size (in ah), required to support the control...

  • Page 126: Ademco Contact Id Format

    Ademco contact id format event code descriptions transmission format between dact and receiver 126 gf505 & gf510 series pn 53164:a 3/26/2007 appendix a ademco contact id format event code descriptions this appendix describes the various event codes and their messages which are available for the adem...

  • Page 127

    Ademco contact id typical printout ademco contact id format event code descriptions gf505 & gf510 series pn 53164:a 3/26/2007 127 event message medical alarms - 100 100 medical emerg - personal emergency - # 101 pendant transmitter emerg - personal emergency - # 102 fail to report in emerg - fail to...

  • Page 128

    Ademco contact id format event code descriptions ademco contact id typical printout 128 gf505 & gf510 series pn 53164:a 3/26/2007 event message 24 hour non-burglary - 150 and 160 150 24-hour non-burg alarm - 24-hr. Non-burg - # 151 gas detected alarm - gas detected - # 152 refrigeration alarm - refr...

  • Page 129

    Ademco contact id typical printout ademco contact id format event code descriptions gf505 & gf510 series pn 53164:a 3/26/2007 129 event message communication troubles - 350 and 360 350 communication trouble - communication trouble 351 telco 1 fault trouble - phone line #1 352 telco 2 fault trouble -...

  • Page 130

    Ademco contact id format event code descriptions ademco contact id typical printout 130 gf505 & gf510 series pn 53164:a 3/26/2007 event message sounder/relay disables - 520 520 sounder/relay disable disable - sounder/relay - # 521 bell 1 disable disable - bell/siren - #1 522 bell 2 disable disable -...

  • Page 131

    Ademco contact id typical printout nfpa standard-specific requirements gf505 & gf510 series pn 53164:a 3/26/2007 131 appendix b nfpa standard-specific requirements the gf505/gf510 has been designed for use in commercial, industrial and institutional applications and meets the requirements for servic...

  • Page 132

    Nfpa standard-specific requirements ademco contact id typical printout 132 gf505 & gf510 series pn 53164:a 3/26/2007 the following figure illustrates an example of central station/remote station reporting using a 411ud. The relay contacts from the gf505/gf510 may be used to trip any dialer ul listed...

  • Page 133

    Ademco contact id typical printout nfpa standard-specific requirements gf505 & gf510 series pn 53164:a 3/26/2007 133 notes: 1. Reference the 411ud manual for additional information 2. Program the 411ud for slave operation 3. The gf505/gf510 must be programmed for ac loss reporting delay this prevent...

  • Page 134: Fire

    Nfpa standard-specific requirements ademco contact id typical printout 134 gf505 & gf510 series pn 53164:a 3/26/2007 nfpa 72 auxiliary fire alarm system all connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or trouble co...

  • Page 135

    Ademco contact id typical printout nfpa standard-specific requirements gf505 & gf510 series pn 53164:a 3/26/2007 135 nfpa 72 remote station protective signaling system notes: 1. Cut jumper jp30 on the gf505/gf510 main circuit board to supervise placement of the 4xtmf module. 2. Refer to "4xtmf trans...

  • Page 136

    Nfpa standard-specific requirements ademco contact id typical printout 136 gf505 & gf510 series pn 53164:a 3/26/2007 nfpa 72 proprietary protective signaling systems figure b.4 proprietary protective signaling system form-c relay contact programmed to activate on supervisory condition. Form-c troubl...

  • Page 137

    Central station/remote station transmitter: connection to facp dry contacts nfpa standard-specific gf505 & gf510 series pn 53164:a 3/26/2007 137 b.1 central station/remote station transmitter: connection to facp dry contacts the dry contacts of the facp programmable relays can be used to trip a ul-8...

  • Page 138: Facp With Keltron

    Facp with keltron central station/remote station transmitter: connection to facp dry contacts 138 gf505 & gf510 series pn 53164:a 3/26/2007 appendix c facp with keltron the following figure illustrates the connections between the facp and keltron receiver/ transmitter. Caution! For reasons of wiring...

  • Page 139

    Gf505 & gf510 pn 53164:a 03/26/07 139 index numerics 10 zone main circuit board11 24 hour test time86 4xtmf135 installation34, 35 operation35 see also transmitter module17 see also transmitter module35 specifications35 4xtmf option module placement supervision34 5 zone main circuit board10 a ac loss...

  • Page 140

    140 gf505 & gf510 pn 53164:a 03/26/07 index edit detector screens56 enable/disable zone57 end-of-line resistor idc14, 25, 26 nac14, 27 enter key54 erase history95 event code classification127 event codes87 exiting programming52, 53 read status52, 53 f fail-safe trouble relay28 features12 form-c see ...

  • Page 141

    Gf505 & gf510 pn 53164:a 03/26/07 141 index nfpa 72 auxiliary fire alarm system131, 134 nfpa 72 central station service (protected premises unit) or remote station service131 nfpa 72 proprietary fire alarm system131 nfpa 72 proprietary protective signaling systems136 nfpa 72 remote station protectiv...

  • Page 142

    142 gf505 & gf510 pn 53164:a 03/26/07 index synchronized signals66 sounder13, 16 strobes13, 66 style b14, 25 see also class b12 style d17, 25, 33 style y14 see also class b12 style z17, 33 subscreen53 supervision 4xtmf option module placement34 supervisory12, 106 supervisory piezo pulse rate16 super...

  • Page 143: Limited Warranty

    Limited warranty honeywell international inc. Warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obliga...

  • Page 144

    12 clintonville rd., northford, ct 06472-1653 p/n 53164 rev a 3/22/07 ©2007 by honeywell international inc. All rights reserved. Unauthorized use of this document is strictly prohibited..