PEciFicAtions
SS-GMVC95
www.goodmanmfg.com
5
Dipswitch
Number
Function
Instructions
1
Electric Heat Mode
Select the taps allowed in the tables (Dipswitch 1/2/ 7/8) below.
2
Electric Heat Mode
3
N/A
N/A
4
Thermostat Mode
ON = The system operates with single-stage units using a single-stage cooling or heat pump
thermostat. (factory default)
OFF = The system operates with two-stage units with either a conventional two-stage cooling/
heat pump thermostat or with an encoded two-stage thermostat for cooling operation.
The encoded thermostats can be used with two-stage condensing units in retrofit applications where
there aren’t enough existing wires available for connections to the indoor thermostat and outdoor
units.
5
Cooling/Heat Pump Mode
Find the airflow for your application in the tables (Dipswitch 5/6/ 7/8) below. Set up the motor based
on the outdoor unit capacity tons.
6
Cooling/Heat Pump Mode
7
Trim CFM Adjust Mode
Increase or decrease your selected airflow to fit your requirement.
ON-OFF = Increases selected Cool/Heat Pump airflow by 10%.
OFF-ON = Decreases selected Cool/Heat Pump airflow by 15%
Note: Other settings have no effect on the set airflow.
8
Trim CFM Adjust Mode
AEPF d
iPswitcHEs
(
cont
.)
Dipswitch 1/2/ 7/8
Dipswitch 5/6/ 7/8
AEPF1830
AEPF1830
Heating
Element (kW)
Switch Position
Emergency
Backup
HP w/
Backup
Outdoor Unit
(Tons)
Switch Position
Indoor CFM
1
2
7
8
5
6
7
8
Cool
HP
Up to 10
Off
Off
Off
Off
1,100
1,210
2.5
Off
Off
Off
Off
1,100
1,100
Up to 10
On
Off
Off
Off
890
935
2
On
Off
Off
Off
800
800
5
Off
On
Off
Off
700
770
1.5
Off
On
Off
Off
600
600
AEPF3036/4260
AEPF3036/4260
Heating
Element (kW)
Switch Position
Emergency
Backup
HP w/
Backup
Outdoor Unit
(Tons)
Switch Position
Indoor CFM
1
2
7
8
5
6
7
8
Cool
HP
Up to 20
Off
Off
Off
Off
2,050
2,150
5
Off
Off
Off
Off
1,800
1,800
Up to 20
On
Off
Off
Off
1,750
1,835
4
On
Off
Off
Off
1,580
1,580
Up to 15
Off
On
Off
Off
1,600
1,680
3.5
Off
On
Off
Off
1,480
1,480
Up to 10
On
On
Off
Off
1,200
1,260
3
On
On
Off
Off
1,200
1,200
Up to 10
On
On
Off
On
1,020
1,070
2.5
On
On
Off
On
1,020
1,020
AEPF3137
AEPF3137
Heating
Element (kW)
Switch Position
Emergency
Backup
HP w/
Backup
Outdoor Unit
(Tons)
Switch Position
Indoor CFM
1
2
7
8
5
6
7
8
Cool
HP
Up to 15
Off
On
Off
Off
1,600
1,680
3.5
Off
On
Off
Off
1,480
1,480
Up to 10
On
On
Off
Off
1,200
1,260
3
On
On
Off
Off
1,200
1,200
Up to 10
On
On
Off
On
1,020
1,070
2.5
On
On
Off
On
1,020
1,020
Note: When applying a humidistat (normally closed), refer to the installation and operating instructions.
The humidistat can adjust the cooling airflow to 85%.