Goodman ASH Series Service Instructions Manual

Manual is about: Split System Air Conditioners, Split System Heat Pumps with R-22 Refrigerant Blowers, Coils, & Accessories

Summary of ASH Series

  • Page 1

    This manual is to be used by qualified, professionally trained hvac technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person. Split system air conditioners, split system heat ...

  • Page 2

    This manual is for the follow model numbers gsh100903aa gsh140181aa ash130181aa gsh100903ab gsh140181ab ash130181ab gsh100904aa gsh140241aa ash130181ac gsh100904ab gsh140241ab ash130241aa gsh101203aa gsh140241ac ash130241ab gsh101203ab gsh140301aa ash130241ac gsh101204aa gsh140301ab ash130241ad gsh1...

  • Page 3

    This manual contain the following important information model identification air handler/coil identification accessories product design system operation troubleshooting chart servicing table of contents servicing table of contents accessories wiring diagrams wiring for heat pump or air conditioning ...

  • Page 4: Important Information

    Important information pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety proced...

  • Page 5: Warning

    3 the successful development of hermetically sealed refrigera- tion compressors has completely sealed the compressor's moving parts and electric motor inside a common housing, minimizing refrigerant leaks and the hazards sometimes associated with moving belts, pulleys or couplings. Fundamental to th...

  • Page 6: Product Identification

    Product identification 4 model # description gsc13018-241aa goodman® brand split condenser 13 seer condensing units. Initial release. 26" chassis gsc13036-481aa goodman® brand split condenser 13 seer condensing units. Initial release. 29" chassis gsc13036,48*aa goodman® brand split condenser 13 seer...

  • Page 7: Product Identification

    Product identification 5 model # description gsc140**1aa goodman® brand split condenser 14 seer condensing units. Introduces goodman® brand 14 seer ac r-22 models. Gsc140**1ab goodman® brand split condenser 14 seer condensing units. New revisions have screw locations moved in the top panel, base pan...

  • Page 8: Product Identification

    Product identification 6 model # description gsh10***aa goodman® brand split heat pump 10 seer heat pump units. Initial release. Gsh10***ab goodman® brand split heat pump 10 seer heat pump units. Screw locations moved in the top panel, base pans, louvers, and control box covers. . Gsh13***aa goodman...

  • Page 9: Product Identification

    Product identification 7 model # description ash130**1aa amana® brand split heat pump 13 seer heat pump units. Initial release new models of amana® brand deluxe 13 seer r-22 heat pumps. Ash130**1ab amana® brand split heat pump 13 seer heat pump units. New revisions have screw locations moved in the ...

  • Page 10: Product Identification

    Product identification 8 model # description aruf****16aa a single piece r multi-position psc motor unpainted flowrater introduction of new 13 seer air handler models. All models will be suitable for use with r-22 and r-410a aruf364216ab a single piece r multi-position psc motor unpainted flowrater....

  • Page 11: Product Identification

    Product identification 9 model # description aepf****16aa a single piece e multi-position variable-speed painted flowrator. Introducation of new 13 seer air handler models. All models will be suitable for use with r-22 and r-410a aepf****16ba a single piece e multi-position variable-speed painted fl...

  • Page 12: Product Identification

    Product identification 10 model # description mbr****aa-1aa modular blower r multi-position psc motor. Introduces module blower with psc blower motor. Mbe****aa-1aa modular blower e multi-position variable-speed. Introduces module blower with variable speed blower motor. Mbe****aa-1ba modular blower...

  • Page 13: Product Identification

    Product identification 11 c pkf 036 2 a product category: c: split system unit type: e: commercial air conditioner k: air cojditioner p: heat pump revision: a: revision electrical: 1: 208-230v/1ph/60hz 2: 220-240v/1ph/50 hz 3: 208-230v/3ph/60hz 4: 308/415v/3ph/50hz nominal capacity: 018: 1.5 tons 04...

  • Page 14: Product Identification

    Product identification 12 c kf 036 2 a product category: c: split system unit type: e: commercial air conditioner k: air cojditioner p: heat pump revision: a: revision electrical: 1: 208-230v/1ph/60hz 2: 220-240v/1ph/50 hz 3: 208-230v/3ph/60hz 4: 308/415v/3ph/50hz nominal capacity: 018: 1.5 tons 048...

  • Page 15: Product Identification

    Product identification 13 a r u f 3642 1 a a product type a: single piece air handler application c: ceiling mount psc motor d: downflow psc motor e: multi-position variable speed motor r: multi-position psc motor w: wall mount psc motor cabinet finish u: unpainted p: painted n: uncased nominal capa...

  • Page 16: Product Identification

    Product identification 14 this nomenclature is to be used after july 2006 all airhandlers use direct drive motors. Power supply is ac 208-230v, 60 hz, 1 phase. A w u f 3642 1 6 a a product type: a: air handler cabinet finish: u: unpainted p: paited n: uncased expansion device: f: flowrater t: txv (e...

  • Page 17: Product Identification

    Product identification 15 model mfg. # mbr0800 mbr0800 mbr1200 mbr1200 mbr1600 mbr1600 mbr2000 mbr2000 mbe1200 mbe1200 mbe1600 mbe1600 mbe2000 mbe2000 mb r 8 00 a a 1 design series: mb: modular blower motor type: r: constant speed e: variable speed airflow delivered 08: 800 cfm 12: 1200 cfm 16: 1600...

  • Page 18: Accessories

    Accessories 16 *installed on indoor coil. Model description g/vsh13018 g/vsh13024 g/vsh13030 g/vsh13036 g/vsh13042 g/vsh13048 g/vsh13060 afe18-60a all fuel kit x x x x x x x ot18-60a outdoor thermostat x x x x x x x fsk01a* freeze protection kit x x x x x x x asc01 anti short cycle kit x x x x x x x...

  • Page 19: Accessories

    17 accessories model description cpkf24 cpkf36 cpkf42 cpkf48 cpkf60 cpkf61 afe18-60a all fuel kit x x x x x x ot18-60a outdoor thermostat x x x x x x fsk01a* freeze protection kit x x x x x x asc01 anti short cycle kit x x x x x x tx2n2* txv kit --- --- --- --- --- --- tx3n2* txv kit x x --- --- ---...

  • Page 20: Accessories

    Accessories 18 suction line bulb 1/4 flare connection expansion valve evaporator coil remove before installing expansion valve seal supplied w/ kit seal supplied w/ kit bulb to be located at 10 or 2 o'clock for applications requiring a field installed access fitting tailpiece 3/8"- sweat 7/8" nut di...

  • Page 21: Accessories

    19 accessories fsk01a freeze thermostat kit t2 t1 l2 l1 black 1 thermostat wire short cycle protector yellow 1 black 1 y1 y2 r1 r2 y c unit terminal board contactor asc01a anti-short -cycle control kit install line thermostat here install line thermostat here wire nut wire nut y y b la ck bl ac k wi...

  • Page 22: Accessories

    Accessories 20 coil accessories coil model tx2n2 txv kit tx3n2 txv kit tx5n2 txv kit fsk01a freeze protection kit ca*f030b4* --- x --- x ca*f036b4* --- x --- x ca*f042c4* --- --- x x ca*f048c4* --- --- x x ca*f057d4* --- --- x x ca*f060d4* --- --- x x chpf030a4* --- x --- x chpf036b4* --- x --- x ch...

  • Page 23: Product Design

    Product design 21 this section gives a basic description of cooling unit opera- tion, its various components and their basic operation. Ensure your system is properly sized for heat gain and loss according to methods of the air conditioning contractors association (acca) or equivalent. Condensing un...

  • Page 24: Product Design

    Product design 22 the coils are designed for upflow, counterflow or horizontal application, using two-speed direct drive motors on the cacf/capf/chpx models and bpm (brushless permanent magnet) or ecm motors on the mbe models. The aruf is a multi-position air handler (upflow/horizontal or downflow) ...

  • Page 25: System Operation

    System operation 23 cooling the refrigerant used in the system is r-22. It is a clear, colorless, non-toxic, non-irritating, and non-explosive liquid. The chemical formula is chclf 2 . The boiling point, at atmospheric pressure is -41.4°f. A few of the important principles that make the refrigeratio...

  • Page 26: System Operation

    System operation 24 cooling cycle heating cycle indoor coil accumulator bi-flow filter dryer outdoor coil thermostatic expansion valve check valve reversing valve (de-energized) indoor coil accumulator bi-flow filter dryer outdoor coil thermostatic expansion valve check valve reversing valve (energi...

  • Page 27: System Operation

    System operation 25 restrictor orifice assembly in cooling operation restrictor orifice assembly in heating operation in the cooling mode, the orifice is pushed into its seat, forcing refrigerant to flow through the metered hole in the center of the orifice. In the heating mode, the orifice moves ba...

  • Page 28: System Operation

    System operation 26 indoor coil outdoor coil thermostatic expansion valve cooling cycle - condensing unit in the cooling mode, the orifice is pushed into its seat, forcing refrigerant to flow through the metered hole in the center of the orifice..

  • Page 29: System Operation

    System operation 27 afe18-60a control board description the afe18 control is designed for use in heat pump applica- tions where the indoor coil is located above/downstream of a gas or fossil fuel furnace. It will operate with single and two stage heat pumps and single and two stage furnaces. The afe...

  • Page 30: Troubleshooting Chart

    28 troubleshooting chart complaint system operating pressures possible cause dots in analysis guide indicate "possible cause" sym pt om s ystem will not star t compr e ssor will not star t - fan r uns c o mp. And c ond. F an w ill not star t e v apor ator fan w ill not star t c ondenser fan w ill no...

  • Page 31: Servicing

    Servicing 29 table of contents high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. S-1 checking voltage .......................................... 30 s-2 checking wir...

  • Page 32: Servicing

    Servicing 30 s-1 checking voltage 1. Remove outer case, control panel cover, etc., from unit being tested. With power on: warning line voltage now present. 2. Using a voltmeter, measure the voltage across terminals l1 and l2 of the contactor for the condensing unit or at the field connections for th...

  • Page 33: Servicing

    Servicing 31 4. Check the continuity of the thermostat and wiring. Repair or replace as necessary. Resistance heaters 1. Set room thermostat to a higher setting than room temperature so both stages call for heat. 2. With voltmeter, check for 24 volts at each heater relay. Note: bba/bbc heater relays...

  • Page 34: Servicing

    Servicing 32 s-4 checking transformer and control circuit a step-down transformer (208/240 volt primary to 24 volt sec- ondary) is provided with each indoor unit. This allows ample capacity for use with resistance heaters. The outdoor sec- tions do not contain a transformer. Warning disconnect all p...

  • Page 35: Servicing

    Servicing 33 s-7 checking contactor and/or relays warning high voltage! Disconnect all power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. The compressor contactor and other relay holding coils are wired i...

  • Page 36: Servicing

    Servicing 34 s-10 copeland comfort alert™ diagnostics applies to asc13 & ash13 comfort alert™ is self-contained with no required external sensors and is designed to install directly into the electrical box of any residential condensing unit that has a copeland scroll™ compressor inside. Once attache...

  • Page 37: Servicing

    Servicing 35 status led status led description status led troubleshooting information green “power” module has power supply voltage is present at module terminals red “trip” thermostat demand signal 1. Compressor protector is open y1 is present, but the 2. Outdoor unit power disconnect is open compr...

  • Page 38: Servicing

    Servicing 36 start relay c o m h e r m f a n run capacitor contactor t2 t1 l1 l2 start capacitor red 10 violet 20 yellow 12 orange 5 hard start kit wiring s-15a resistance check 1. Discharge capacitor and remove wire leads. Warning discharge capacitor through a 20 to 30 ohm resistor before handling....

  • Page 39: Servicing

    Servicing 37 b. Shorted - indicator swings to zero and stops there - replace. C. Open - no reading - replace. (start capacitor would read resistor resistance.) s-15b capacitance check using a hookup as shown below, take the amperage and voltage readings and use them in the formula: voltmeter capacit...

  • Page 40: Servicing

    Servicing 38 1 2 3 4 5 lines 1 and 2 will be connected for 12ovac power connector applications only gnd ac line connection ac line connection } 11 1 9 2 3 4 5 6 7 8 16 15 14 13 12 10 out - out + adjust +/- g (fan) y1 y/y2 cool em ht/w2 delay 24 vac (r) common2 heat w/w1 bk/pwm (speed) common1 o (rev...

  • Page 41: Servicing

    Servicing 39 - c o nn ec to rs a re or ien ted " d ow n " (o r a s re c o m m end ed b y e q u ipm ent m a nu fa c ture r) .- a rr a n g e har ne s s e s w it h " d ri p lo op " u n d e r m o to r. - is co n d ens a te d ra in p lu gg e d? - ch ec k f or l ow a ir fl ow (t oo m u c h l a ten t ca p ...

  • Page 42: Servicing

    Servicing 40 chart continued from previous page - c onn ec to rs ar e o ri ent ed " d o w n" ( or as r e c o m m e nde d b y e qui p m e n t m anu fa c tu rer ).- a rr a n g e h a rn es s e s w it h " d ri p l oop " u nde r m o to r. - is co n d en s a te d ra in p lu gg e d? - ch ec k f or low a ir...

  • Page 43: Servicing

    Servicing 41 dipswitch functions the mbe air handler motor has an electronic control that contains an eight (8) position dip switch. The function of these dipswitches are shown in table 1. D ipsw itch n um ber function 1 2 3 n /a 4 indoor therm ostat 5 6 7 8 cooling & heat pum p cfm cfm trim adjust ...

  • Page 44: Servicing

    Servicing 42 humidity control when using a humidstat (normally closed), cut jumper pj6 on the control board. The humidstat will only affect cooling airflow by adjusting the airflow to 85%. Two stage heating when using staged electric heat, cut jumper pj4 on the control board. S-16e checking ge x13 t...

  • Page 45: Servicing

    Servicing 43 1. Remove the leads from the compressor terminals. See warnings s-17 before removing compressor terminal cover. 2. Using an ohmmeter, test continuity between terminals s- r, c-r, and c-s, on single phase units or terminals t2, t2 and t3, on 3 phase units. S r c comp ohmmeter testing com...

  • Page 46: Servicing

    Servicing 44 a. If the compressor starts and continues to run, the cause for failure is somewhere else in the system. B. If the compressor fails to start - replace. Copeland compressor 03 a 12345 l yea r m onth ser ial num ber plant s-18 testing crankcase heater (optional item) the crankcase heater ...

  • Page 47: Servicing

    Servicing 45 s-40 ar*f & mbr electronic blowers time delay relay the mbr contains an electronic blower time delay relay board, b1370735. This board provides on/off time delays for the blower motor in cooling and heat pump heating demands when “g” is energized. During a cooling or heat pump heating d...

  • Page 48: Servicing

    Servicing 46 4.0 heating operation on heat pump units, when the room thermostat set to the heating mode, the reversing valve is not energized. As long as the thermostat is set for heating, the reversing valve will be in the de-energized position for heating except during a defrost cycle. Some instal...

  • Page 49: Servicing

    Servicing 47 aep* & mbe with single stage condensers when used with a single stage condenser, dip switch #4 must be set to the on position on the vstb inside the mbe. The “y” output from the indoor thermostat must be connected to the yellow wire labeled “y/y2” inside the wire bundle marked “thermost...

  • Page 50: Servicing

    Servicing 48 rate programmed in the motor. 4.0 heating operation on heat pump units, when the room thermostat is set to the heating mode, the reversing valve is not energized. As long as the thermostat is set for heating, the reversing valve will be in the de-energized position for heating except du...

  • Page 51: Servicing

    Servicing 49 lation. Other components such as a heating/cooling thermostat and outdoor thermostats are available to complete the installation. The system cfm can be determined by measuring the static pressure external to the unit. The installation manual supplied with the blower coil, or the blower ...

  • Page 52: Servicing

    Servicing 50 1. Remove the wiring from the control terminals. 2. Using an ohmmeter, test for continuity across the nor- mally closed contacts. No reading indicates the control is open - replace if necessary. If found open - replace - do not wire around. S-61b checking heater fuse link (optional elec...

  • Page 53: Servicing

    Servicing 51 to avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig. Warning pressure test the system using dry nitrogen and soapy water to locate leaks. If...

  • Page 54: Servicing

    Servicing 52 caution use refrigerant certified to ahri standards. Used refrigerant may cause compressor damage and will void the warranty. Most portable machines cannot clean used refrigerant to meet ahri standards. Caution operating the compressor with the suction valve closed will void the warrant...

  • Page 55: Servicing

    Servicing 53 note: the compressor may run backwards (noisy opera- tion) for 1 or 2 seconds at shutdown. This is normal and does not harm the compressor. 1. Install gauges and verify that the suction pressure drops while the discharge pressure increases. 2. Listen for normal compressor sound levels. ...

  • Page 56: Servicing

    Servicing 54 cooling heating thermostatic expansion valves some txv valves contain an internal check valve thus eliminating the need for an external check valve and bypass loop. The three forces which govern the operation of the valve are: (1) the pressure created in the power assembly by the feeler...

  • Page 57: Servicing

    Servicing 55 temp. °f. Gauge pressure (psig) freon-22 temp. °f. Gauge pressure (psig) freon-22 -40 -38 -36 -34 0.61 1.42 2.27 3.15 60 62 64 65 102.5 106.3 110.2 114.2 -32 -30 -28 -26 4.07 5.02 6.01 7.03 68 70 72 74 118.3 122.5 126.8 131.2 -24 -22 -20 -18 8.09 9.18 10.31 11.48 76 78 80 82 135.7 140.5...

  • Page 58: Servicing

    Servicing 56 s-111 capillary tubes/restrictor orifices the capillary tubes/restrictor orifices used in conjunction with the indoor and outdoor coil, are a predetermined length and bore (i.D.). They are designed to control the rate of liquid refrigerant flow into an evaporator coil. The amount of ref...

  • Page 59: Servicing

    Servicing 57 notice violation of epa regulations may result in fines or other penalties. Now determine if a burn out has actually occurred. Confirm by analyzing an oil sample using a sporlan acid test kit, ak- 3 or its equivalent. Remove the compressor and obtain an oil sample from the suction stub....

  • Page 60: Servicing

    Servicing 58 • the distance between the condenser and evaporator in a completely horizontal installation in which the indoor and outdoor unit do not differ more than 10 feet in vertical distance from each other can approach 150 feet, as long as the equivalent length does not exceed 150 feet. 4. Two-...

  • Page 61: Servicing

    Servicing 59 3. An oil trap is required at the evaporator only if the condenser is above the evaporator. Preformed oil traps are available at most hvac supply houses, or oil traps may be created by brazing tubing elbows together (see diagram below). Remember to add the equivalent length from oil tra...

  • Page 62: Servicing

    Servicing 60 s-203 air handler external static to determine proper air movement, proceed as follows: 1. Using a draft gauge (inclined manometer), measure the static pressure of the return duct at the inlet of the unit, (negative pressure). 2. Measure the static pressure of the supply duct, (positive...

  • Page 63: Accessories Wiring Diagrams

    Accessories wiring diagrams 61 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. +5vdc 24 vac g power supply input power supply common out to hp control p3-1 6.8k p...

  • Page 64: Accessories Wiring Diagrams

    62 accessories wiring diagrams high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Emergency heat relay 13 42 blue white black brown thermostat ot/ehr18-60 2 1 from a...

  • Page 65: Accessories Wiring Diagrams

    Accessories wiring diagrams 63 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Emergency heat relay 13 42 blue white black brown thermostat ot/ehr18-60 #2 2 1 fro...

  • Page 66: Accessories Wiring Diagrams

    64 accessories wiring diagrams high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Bk bl bk l1 l2 bk bk htr1 tl htr2 rd 9 8 7 r wh bl pu tl bk 5 6 3 4 bk rd 1 2 wh bk...

  • Page 67: Accessories Wiring Diagrams

    Accessories wiring diagrams 65 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Com xfmr-c xfmr-r speedup c nc m1 k1 r g no k1 use copper or aluminum wire equipmen...

  • Page 68: Accessories Wiring Diagrams

    66 accessories wiring diagrams high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. No mark indicates no heat kit installed after installing optional heat kit, mark an...

  • Page 69: Accessories Wiring Diagrams

    Accessories wiring diagrams 67 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Blower section bk vstb ds 1 pn. B1368270 rev. A j1 thermostats w2 heater w c r j3 j...

  • Page 70: Accessories Wiring Diagrams

    68 accessories wiring diagrams high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Typical wiring schematic aspf****16a* with electric heat. This wiring diagram is fo...

  • Page 71: Accessories Wiring Diagrams

    Accessories wiring diagrams 69 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Typical wiring schematic aspf****16b* with electric heat. This wiring diagram is fo...

  • Page 72: Gsh 10 Seer

    1 • refer to service manual rs6100004 for installation, operation, and troubleshooting information. • all safety information must be followed as provided in the service manual. • refer to the appropriate parts catalog for part number information. • models listed on page 3. Gsh 10 seer split system h...

  • Page 73: Product Identification

    Product identification 2 the model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. Warning warning high voltage! Disconnect all power before servicing or installing this unit. Multiple power sou...

  • Page 74: Product Identification

    Product identification 3 the united states environmental protection agency (“epa”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substa...

  • Page 75: Product Design

    Product design 4 the gsh101203 units are shipped with a nitrogen holding charge only and are available in 208/230v 3-phase. The starting charge for the 10 ton unit should be 15 lbs. Of r- 22. The length of line set, indoor unit airflow, condensing unit location and number of tubing fittings will hav...

  • Page 76: Product Dimensions

    5 w d h product dimensions model dimensions - w x d x h gsh101203ac 35½ x 35½ x 41½.

  • Page 77: Gsh101203Ac

    6 gsh101203ac heat pump specifications (1) wire size should be determined in accordance with national electrical codes. Extensive wire runs will require larger wire sizes. (2) maximum overcurrent protection: must use fuses or hacr-type circuit breakers of the same size as noted. Notes: * always chec...

  • Page 78: Cooling Performance Data

    7 cooling performance data gsh101203ac e x p a nd ed pe rf o r m a nc e d a ta c ool in g op er a t ion m o d e l: g s h 1 0 1203 a c / a r 1 20* ou td o o r a m b ien t t e m p erat u re 6 5 75 85 9 5 105 11 5 e n te ri ng i n door w e t b u lb t e m p e ra tu re id b * a ir fl o w 5 96 36 77 15 9 ...

  • Page 79: Cooling Performance Data

    8 cooling performance data gsh101203ac e x p a nd ed pe rf o r m a nc e d a ta c ool in g op er a t ion m o d e l: g s h 1 0 1203 a c / a r 1 20* ou td o o r a m b ien t t e m p erat u re 6 5 75 85 9 5 105 11 5 e n te ri ng i n door w e t b u lb t e m p e ra tu re id b * a ir fl o w 5 96 36 77 15 9 ...

  • Page 80: Heating Performance Data

    9 high pressure is measured at the suction service valve ( the larger valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. Heating performance data *note: shaded ar...

  • Page 81: Wiring Diagrams

    Wiring diagrams 10 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Gsh101203ac wiring is subject to change. Always refer to the wiring diagram on the unit for the...

  • Page 82: Gsh/vsh 13 Seer

    1 • refer to service manual rs6100004 for installation, operation, and troubleshooting information. • all safety information must be followed as provided in the service manual. • refer to the appropriate parts catalog for part number information. • models listed on page 3. Gsh/vsh 13 seer split syst...

  • Page 83: Product Identification

    Product identification 2 the model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. Warning warning high voltage! Disconnect all power before servicing or installing this unit. Multiple power sou...

  • Page 84: Product Identification

    Product identification 3 the united states environmental protection agency (“epa”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substa...

  • Page 85: Product Design

    Product design 4 condensing unit gsh/vsh13 seer heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications. Gsh13 3, 4 and 5 ton models are also available for 208/230v 3 phase. Additionally, gsh13 4 and 5 ton units are available for 460v...

  • Page 86: Product Dimensions

    5 w d h product dimensions model dimensions - w x d x h gsh130363a* 29 x 29 x 38¼ gsh130483a* 29 x 29 x 34¼ gsh130603a* 35½ x 35½ x 34¼ gsh130484a* 29 x 29 x 34¼ gsh130604a* 35½ x 35½ x 34¼ model dimensions - w x d x h gsh130181a* 29 x 29 x 32¼ gsh130191a* 29 x 29 x 32¼ gsh130241a* 29 x 29 x 34¾ gsh...

  • Page 87: Heat Pump Specifications

    6 heat pump specifications gsh130[18-60]1a* g s h 1 3 0 18 1a * g s h 1 3 0 19 1a * g s h 1 3 0 24 1a * g s h 1 30 2 5 1a * g s h 1 30 3 0 1a * g s h 1 3 0 311 a * cooling capacity, btuh 18,000 18,000 23,000 23,000 28,000 28,000 compressor r.L. Amps 6.2 9.0 10.1 10.9 10.8 12.2 l.R. Amps 34 41 51 54 ...

  • Page 88: Heat Pump Specifications

    7 g s h1 301 81b * g s h1 302 41b * gs h 1 3 0 3 0 1 b * gs h 1 3 0 3 6 1 b * cooling capacity, btuh 18,000 23,000 28,000 35,000 compressor r.L. Amps 6.2 9.2 10.8 12.2 l.R. Amps 35 43 60 73 loss of charge pressure switch open / close 7 psig/25 psig 7 psig/25 psig 7 psig/25 psig 7 psig/25 psig conden...

  • Page 89: Gsh130[36-60]3*

    8 g s h 1 30 363 a* g s h 1 3 048 3a* g s h 1 306 03a * g s h 1 30 484 a* g s h 1 3 060 4a* cooling capacity, btuh 35,000 45,000 55,500 45,000 55,500 compressor r.L. Amps 8.3 12.4 17.3 5.8 6.7 l.R. Amps 48.0 88.0 123.0 44.0 49.5 loss of charge pressure switch open / close 7 psig/25 psig 7 psig/25 ps...

  • Page 90: Heat Pump Specifications

    9 heat pump specifications vsh130[18-60]1a* (1) wire size should be determined in accordance with national electrical codes. Extensive wire runs will re- quire larger wire sizes. (2) maximum overcurrent protection: must use fuses or hacr-type cir- cuit breakers of the same size as noted. Notes: * al...

  • Page 91: Cooling Performance Data

    10 cooling performance data gsh130181a* expa nded per f o rm a nce da t a c ooli n g ope r a t io n m o del : g s h 1 3 018 1a * / a r u f 3 2 -0 0* -1 * / a ruf 1 824 1a * o u td o o r a m b ie n t t e m p e ra tu re 6 5 75 85 95 10 5 115 e n te ri ng i ndo or w e t b u lb t e mpe ra tu re id b a i...

  • Page 92: Cooling Performance Data

    11 cooling performance data gsh130181a* e x p a nd e d p e rf o r m a n c e da t a c o o l in g op e r a t io n m o de l : g s h1 3 0 1 8 1 a * / ar u f 3 2 -0 0 *- 1 * / a r u f 1 8 2 4 1 a * o u td oor a m b ie n t te mpe ra tu re 6 5 75 85 95 105 1 1 5 e n te ri ng i n d oor w e t b u lb te m p e...

  • Page 93: Cooling Performance Data

    12 cooling performance data gsh130181b* e x p and e d p e rf o r m a n c e da t a c o ol in g op e r a t io n mo d e l : g s h 1 3 0 1 8 1 b * / a r *f 1 8 2 4 1 6 ** d e s ig n su b c o o lin g 9 ± 3 ° f @ th e liq u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u td oo r a m bi...

  • Page 94: Cooling Performance Data

    13 cooling performance data gsh130181b* ex pa n d e d p e r f o r m a n c e d a t a c o ol in g op e r a t io n mo d e l : g s h 1 3 0 1 8 1 b * / a r *f 1 8 2 4 1 6 ** d e s ig n su b c o o lin g 9 ± 3 ° f @ t h e liq u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u td oo r a m...

  • Page 95: Cooling Performance Data

    14 cooling performance data gsh130191a* e x p a nd e d p e rf o r m a n c e da t a c ool in g op e r a t io n m o d e l : g s h 1 3 0 1 9 1 a * / a w u f 1 8 xx 1 a * d e s ig n su b c o o li n g 9 ± 3 ° f @ t h e li q u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u td oo r am ...

  • Page 96: Cooling Performance Data

    15 cooling performance data gsh130191a* e x p a nd e d p e rf o r m a n c e da t a c ool in g op e r a t io n mo d e l : g s h 1 3 0 1 9 1 a * / a w u f 1 8 xx 1 a * d e s ig n su b c o o li n g 9 ± 3 ° f @ t h e li q u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u td oo r am b...

  • Page 97: Cooling Performance Data

    16 cooling performance data gsh130241a* e x p a nd e d p e rf o r m a n c e da t a c o o l in g op e r a t io n m o d e l : g s h 1 3 0 24 -1 a * / a r u f 3 2 -0 0* -1 * / a r u f 1 8 2 41a * o u td oor a m b ie n t te m p e ra tu re 6 5 75 85 95 105 1 1 5 e n te ri ng i n d oor w e t b u lb te m p...

  • Page 98: Cooling Performance Data

    17 cooling performance data gsh130241a* e x p a nd e d p e rf o r m a n c e da t a c o o l in g op e r a t io n m o de l : g s h1 3 0 2 4 1 a * / ar u f 3 2 -0 0 *- 1 * / a r u f 1 8 2 4 1 a * o u td oor a m b ie n t te m p e ra tu re 6 5 75 85 95 105 1 1 5 e n te ri ng i n d oor w e t b u lb te m p...

  • Page 99: Cooling Performance Data

    18 cooling performance data gsh130241b* e x pan d e d p e r f o r m a nc e d a t a c ool in g op e r a t io n m o d e l : g s h 1 30 2 4 1 b * / a r *f 1 8 2 4 16 ** d esi g n s u b c o o li n g 9 ± 3 °f @ th e l iq u id s e rv ic e val ve , a h r i 9 5 t e st co n d it io n s o u td o o r a m b ie ...

  • Page 100: Cooling Performance Data

    19 cooling performance data gsh130241b* e x pan d e d p e r f o r m a nc e d a t a c ool in g op e r a t io n m o d e l : g s h 1 30 2 4 1 b * / a r *f 1 8 2 4 16 ** d esi g n s u b c o o li n g 9 ± 3 °f @ th e l iq u id s e rv ic e val ve , a h r i 9 5 t e st co n d it io n s o u td o o r a m b ie ...

  • Page 101: Cooling Performance Data

    20 cooling performance data gsh130251a* e x p a nd e d p e rf o r m a n c e da t a c ool in g op e r a t io n m o d e l : g s h 1 3 0 2 5 1 a * / a w b 3 6 -x x / a w u f 3 6 x x 1 a * d e s ig n s u bc o o lin g 9 ± 3 ° f @ t h e li q u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n ...

  • Page 102: Cooling Performance Data

    21 cooling performance data gsh130251a* e x p a nd e d p e rf o r m a n c e da t a c ool in g op e r a t io n m o d e l : g s h 1 3 0 2 5 1 a * / a w b 3 6 -x x / a w u f 3 6 x x 1 a * d e s ign s u b c oo lin g 9 ± 3 ° f @ t h e li q u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o nd it io ns o...

  • Page 103: Cooling Performance Data

    22 cooling performance data gsh130301a* ex pan d e d p e r f o r m anc e d a t a co o l in g o p e rat io n m o d e l : g s h 130 3 0 1 a * / a r u f 42 -00* -0 1* / a r uf 30 301 a * o u tdoor am bi e n t te m p e ra tur e 6 5 7 5 85 9 5 10 5 1 15 e n te ri ng i n do or w e t b u lb te m p e ra tur...

  • Page 104: Cooling Performance Data

    23 cooling performance data gsh130301a* ex pan d e d p e r f o r m anc e d a t a co o l in g o p e rat io n m o d e l : g s h 130 3 0 1 a * / a r u f 42 -00* -0 1* / a r uf 30 301 a * o u tdoor am bi e n t te m p e ra tur e 6 5 7 5 85 9 5 10 5 1 15 e n te ri ng i n do or w e t b u lb te m p e ra tur...

  • Page 105: Cooling Performance Data

    24 cooling performance data gsh130301b* e xpa n d e d pe r f o r m a n c e d a t a co o l in g o p e rat io n m o d e l : g s h 1 30 301 ba / ar *f 303 01 6* * d e s ig n s u b c o o li n g 9 ± 3 ° f @ t h e l iq u id s e rv ic e val ve , a hri 95 t e s t c o n d it io n s o u tdoor a m bi e n t te ...

  • Page 106: Cooling Performance Data

    25 cooling performance data gsh130301b* e xpa n d ed pe r f o r m a n c e d a t a co o l in g o p e rat io n m o d e l : g s h 130 30 1 b a / a r *f 303 01 6* * d e s ig n s u b c o o li n g 9 ± 3 ° f @ t h e l iq u id s e rv ic e v a lv e , a h r i 95 t e s t c o n d it io n s o u tdoor a m bi e n ...

  • Page 107: Cooling Performance Data

    26 cooling performance data gsh130311a* expa nded pe rforma nce da ta coo ling o p e r a t ion m o d e l : g s h 1303 11a * / a w b 36- x x / a w u f 36x x1 a * ou td oo r a m bi ent tem p er atu re 65 75 85 95 105 115 e n te ri ng i ndo or w e t b u lb t e mpe ra tur e id b * a ir fl o w 5 9 6 36 7...

  • Page 108: Cooling Performance Data

    27 cooling performance data gsh130311a* ex pa n d e d p e r f o r m a n c e d a t a c o o l in g op e r a t ion m o de l : g s h1 3 0 3 1 1 a * / aw b3 6 -x x / aw u f 3 6 x x 1 a * o u tdoo r a m bi e n t te m p e ra tur e 65 75 8 5 9 5 105 1 1 5 e n te ri ng i ndo or w e t b u lb te m p e ra tu re...

  • Page 109: Cooling Performance Data

    28 cooling performance data gsh130361a*/b* e x p a nd e d p e rf orm a nc e d a t a c o ol in g o p e r a t io n m o d e l : g s h 1 30 3 61* * / a r u f 4 9 -00* -1 * / a r u f 3 6 4 21a * o u tdoor a m bi e n t t e m p er a tu re 6 5 75 8 5 95 10 5 1 1 5 e n te ri n g i ndoo r w e t b u lb te m p ...

  • Page 110

    29 cooling performance da t a gsh130361a*/b* expanded performance data cooling operation model: gsh130361** / aruf49-00*-1* / aruf36421a* outdoor ambient temperature 65 75 85 95 105 115 entering indoor wet bulb temperature idb* airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 6...

  • Page 111: Cooling Performance Data

    30 cooling performance data gsh130421a* expa nded perform a n ce da ta c o ol in g o p e r a t io n m o d e l: g s h 1 3 0421a * / a r u f 49 -00 *- 1 * / a r u f 3 6421a * o u td o o r a m b ien t t e m p erat u re 65 75 85 95 105 115 e n te ri n g in do or w e t b u lb t e mpe ra tur e id b * a ir...

  • Page 112: Cooling Performance Data

    31 cooling performance data gsh130421a* ex pa n d e d p e r f o r m a n c e d a t a c o o l in g op e r a t ion m o de l : g s h1 3 0 4 2 1 a * / ar u f 4 9 -0 0 *- 1 * / a r u f 3 6 4 2 1 a * o u tdoor am bi e n t te m p e ra tur e 65 75 8 5 95 105 1 1 5 e n te ri ng i n do or w e t b u lb te m p e...

  • Page 113: Cooling Performance Data

    32 cooling performance data gsh130481a* exp a n d e d p e rf o r m a n c e da t a c o o l in g opera t io n m o d e l : g s h 130481a * / a r u f 61-00* -1* / a r u f 48601a * o u td o o r a m bien t t e m p erat ure 65 7 5 85 9 5 1 0 5 115 e n ter ing in doo r w e t bul b temp er atur e id b * a ir...

  • Page 114: Cooling Performance Data

    33 cooling performance data gsh130481a* e x p a nd e d pe rf orm a n c e da t a c o ol in g op e r a t io n m o d e l : g s h 130 48 1 a * / a r u f 6 1 -00* -1 * / a r u f 4 8 6 01a * o u tdoor a m b ie n t te m p e ra tur e 6 5 7 5 85 95 10 5 1 15 e n te ri ng i ndo or w e t b u lb te m p e ra tur...

  • Page 115: Cooling Performance Data

    34 cooling performance data gsh130601a* expa nded perfor m a n c e da ta coo l ing opera t ion m o d e l: g s h 1 30601a * / a r u f 61-00* -1* / a r u f 48601a * o u td oo r a m bien t temp er a tu re 6 5 75 85 95 10 5 115 e n ter ing i ndo or w e t bu lb t e m p e ratur e id b * a ir fl o w 5 96 3...

  • Page 116: Cooling Performance Data

    35 cooling performance data gsh130601a* ex p a n d e d p e r f o r m a n c e d a t a c o ol in g op e r a t io n m o d e l : g s h 130 6 0 1 a * / a r u f 61 -00* -1 * / a r u f 486 01a * o u tdoo r a m b ie n t te m p e ra tur e 6 5 7 5 8 5 95 10 5 1 15 e n te ri ng i n d o or w e t b u lb te m p e...

  • Page 117: Cooling Performance Data

    36 cooling performance data gsh130363a* expa nded pe rfo r ma nce da ta c ool in g op er a t io n m o d e l : g s h 1 3 036 3a * / a r u f 49- 00 *- 1* / a r u f 364 21a * o u td oo r a m b ie n t tem p er at u re 65 75 85 95 105 115 e n te ri ng i ndo or w e t b u lb t e mpe ra tur e id b * a ir fl...

  • Page 118: Cooling Performance Data

    37 cooling performance data gsh130363a* ex pa n d e d p e r f o r m a nc e d a t a c ool in g o p e r a t io n m o d e l : g s h 130 363 a * / a r u f 49 -00* -1 * / a r u f 364 21a * o u td o o r a m b ien t t e m p er at u re 65 75 8 5 95 10 5 1 1 5 e n te ri ng i n do or w e t b u lb te m p e ra ...

  • Page 119: Cooling Performance Data

    38 cooling performance data gsh130483a* expa nded performa n c e da ta co oli ng oper a t io n m o del: g s h13 0 4 8 3 a * / a ruf61 -0 0* -1 * / a r u f 4 8 6 0 1 a * o u td o o r a m b ient tem p erat ure 65 75 85 95 1 0 5 115 e n te ri ng ind oor w e t b u lb t e mpe ra tu re id b * a ir fl o w ...

  • Page 120: Cooling Performance Data

    39 cooling performance data gsh130483a* e x p a n d ed pe rf o r m a n c e da t a co o l in g o p e rat io n m o d e l : g s h 1 30 483 a * / a r u f 61 -0 0 *- 1 * / a r u f 486 01a * o u td oo r a m bi e n t te m p e ra ture 65 75 8 5 9 5 105 1 1 5 e n te ri n g i n do or w e t b u lb te m p e ra ...

  • Page 121: Cooling Performance Data

    40 cooling performance data gsh130603a* expa nded performa n ce da ta coo l ing ope r a t io n m o d e l: g s h 130 603 a * / a r u f 61 -00* -1* / a r u f 4 860 1a * o u tdoor a m bi ent t e m p e ra tur e 6 5 75 85 95 105 115 e n te ri ng i ndoor w e t bul b t e m p er a tur e id b * a ir fl o w 5...

  • Page 122: Cooling Performance Data

    41 cooling performance data gsh130603a* ex pa n d e d p e r f o r m a n c e d a t a c ool in g op e r a t io n m o d e l : g s h 1 30 603 a * / a r u f 61 -00* -1 * / a r u f 486 0 1 a * o u td oo r am bi e n t te m p e ra tur e 6 5 75 8 5 95 1 0 5 115 e n te ri n g in d o o r w e t b u lb t e m p e...

  • Page 123: Cooling Performance Data

    42 cooling performance data gsh130484a* e x p a n d e d p e rf or m a nce da t a c o o l in g o p e r a t ion m o d e l : g s h 130 48- 4 a * / a r u f 61 -0 0 *- 1 * / a r u f 4 8 6 0 1a * d es ig n s u b c o o li n g 9 ± 3 ° f @ t h e l iq u id ser v ice va lv e, a h r i 95 t e st co n d it io n s...

  • Page 124: Cooling Performance Data

    43 cooling performance data gsh130484a* e x p a n d e d p e rf or m a nce da t a c o o l in g o p e r a t ion m o d e l : g s h 130 48- 4 a * / a r u f 61 -0 0 *- 1 * / a r u f 4 8 6 0 1a * d es ig n s u b c o o li n g 9 ± 3 ° f @ t h e l iq u id ser v ice va lv e, a h r i 95 t e st co n d it io n s...

  • Page 125: Cooling Performance Data

    44 cooling performance data gsh130604a* ex pa n d e d p e r f o r m a n c e d a t a c ool in g op e r a t io n m o d e l : g s h 1 30 60- 4 a * / a r u f 61 -00* -1 * / a r u f 486 01 a * d e s ig n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id se rv ic e va lv e, a h r i 9 5 t est co n d it io n s ...

  • Page 126: Cooling Performance Data

    45 cooling performance data gsh130604a* ex pa n d e d p e r f o r m a n c e d a t a c ool in g op e r a t io n m o d e l : g s h 1 30 60- 4 a * / a r uf 61 -00* -1 * / ar u f 486 01 a * des ig n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id se rvi c e va lv e, a h r i 9 5 t est co n d it io n s o u ...

  • Page 127: Cooling Performance Data

    46 cooling performance data vsh130181a* e x p and e d p e rf o r m a n c e dat a c o o l in g op e r a t io n m o d e l : v s h 13 018 1a * / a r *f 182 416 b * d e si g n s u b c o o li n g 9 ± 3 ° f @ t h e li q u id s e rv ic e val ve , a h r i 95 te s t c o n d it io n s o u tdoor a m bi e n t t...

  • Page 128: Cooling Performance Data

    47 cooling performance data vsh130181a* e x p and e d p e rf o r m a n c e dat a c o o l in g op e r a t io n m o d e l : v s h 13 018 1a * / a r *f 182 416 b * d e si g n s u b c o o li n g 9 ± 3 ° f @ t h e li q u id s e rv ic e val ve , a h ri 95 te s t c o n d it io n s o u tdoor a m bi e n t t ...

  • Page 129: Cooling Performance Data

    48 cooling performance data vsh130191a* e x p a nd ed p e rf o r m a n c e dat a co o l in g o p e rat io n m o d e l : v s h 1 3 0 1 9 1 a * / a w u f 1 8 x x 1 6 a * d e s ig n s u bc o o ling 9 ± 3 ° f @ t h e l iq u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o ndi tion s o u tdoor a m bi e ...

  • Page 130: Cooling Performance Data

    49 cooling performance data vsh130191a* e x p a nd e d p e rf o r m a n c e dat a co o l in g o p e rat io n m o d e l : v s h 1 3 019 1a * / a w u f 18x x 16a * d e s ig n s u b c o o li n g 9 ± 3 ° f @ t h e l iq u id s e rv ic e v a lv e , a hri 95 te s t c o n d it io n s o u tdoor a m bi e n t ...

  • Page 131: Cooling Performance Data

    50 cooling performance data vsh130241a* ex pa n d e d p e r f o r m a nc e d a t a co o l in g o p e rat io n mo d e l : v s h 1 3 0 2 4 1 a * / a r *f 1 8 2 4 1 6 b * d e s ign s u bc o o lin g 9 ± 3 ° f @ t h e liq u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u td o o r a m ...

  • Page 132: Cooling Performance Data

    51 cooling performance data vsh130241a* ex pa n d e d p e r f o r m a n c e d a t a co o l in g o p e rat io n m o d e l : vs h 1 3 0 2 4 1 a * / a r *f 1 8 2 4 1 6 b * d e s ig n s u b c o o lin g 9 ± 3 ° f @ t h e liq u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u td o o r a...

  • Page 133: Cooling Performance Data

    52 cooling performance data vsh130251a* e x p a nd e d p e rf o r m a n c e d a t a co ol in g op e rat io n m o d e l : v s h 13 025 1a * / a w u f 24x x 16a * d e s ig n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id s e rv ic e val ve , a h r i 95 t e st co n d it io n s o u tdoor a m b ie n t te ...

  • Page 134: Cooling Performance Data

    53 cooling performance data vsh130251a* e x p a nd e d p e rf o r m a n c e d a t a co ol in g op e rat io n m o d e l : v s h 13 025 1a * / a w u f 24x x 16a * d e s ig n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id s e rv ic e val ve , a h ri 95 t e st co n d it io n s o u tdoor a m b ie n t te m...

  • Page 135: Cooling Performance Data

    54 cooling performance data vsh130301a* e x p a nd ed p e rf o r m a n c e dat a co o l in g o p e rat io n m o d e l : v s h 1 3 0 3 0 1 a * / a r *f 3 0 3 0 1 6 b * d e s ig n s u bc o o ling 9 ± 3 ° f @ t h e l iq u id s e rv ic e v a lv e , a h r i 9 5 t e s t c o ndi tion s o u tdoor a m bi e n...

  • Page 136: Cooling Performance Data

    55 cooling performance data vsh130301a* e x p a nd e d p e rf o r m a n c e dat a co o l in g o p e rat io n m o d e l : v s h 1 3 030 1a * / a r *f 3 0 3 0 1 6 b * de si g n s u b c o o li n g 9 ± 3 ° f @ t h e l iq u id s e rv ic e v a lv e , a hri 95 te s t c o n d it io n s o u tdoor a m bi e n ...

  • Page 137: Cooling Performance Data

    56 cooling performance data vsh130311a* e xpa n d ed pe r f o r m a n c e d a t a c o ol in g op e r a t io n m o d e l : v s h 13 031 1a * / a w uf 36x x 1 a * d esi g n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id ser vi ce va lv e , a h r i 95 t e st co n d it io n s o u tdoor a m bi e n t te m ...

  • Page 138: Cooling Performance Data

    57 cooling performance data vsh130311a* e xpa n d ed pe r f o r m a n c e d a t a c o ol in g op e r a t io n m o d e l : v s h 13 031 1a * / a w uf 36x x 1 a * d esi g n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id ser vi ce va lv e , a h r i 95 t e st co n d it io n s o u tdoor a m bi e n t te m ...

  • Page 139: Cooling Performance Data

    58 cooling performance data vsh130361a* e x p a nd e d p e rf o r m a n c e d a t a co ol in g op e rat io n m o d e l : v s h 13 036 1a * / a r *f 364 216 b * d e si g n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id s e rv ic e val ve , a h r i 95 t e st co n d it io n s o u tdoor a m b ie n t te m...

  • Page 140: Cooling Performance Data

    59 cooling performance data vsh130361a* e x p a nd e d p e rf o r m a n c e d a t a co ol in g op e rat io n m o d e l : v s h 13 036 1a * / a r *f 364 216 b* d e si g n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id s e rv ic e val ve , a h ri 95 t e st co n d it io n s o u tdoor a m b ie n t te m p...

  • Page 141: Cooling Performance Data

    60 cooling performance data vsh130421a* e x p a nd e d p e rf o r m a n c e da t a c o o l in g op e r a t ion m o d e l : v s h 1 3 0 4 2 1 a * / a r *f 3 6 4 2 1 6 b * d e s ig n s u b c o o li ng 9 ± 3 ° f @ t h e l iqu id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u tdoor a m...

  • Page 142: Cooling Performance Data

    61 cooling performance data vsh130421a* e x p a nd e d p e rf o r m a n c e da t a c o o l in g op e r a t io n m o d e l : v s h 1 3 0 4 2 1a * / a r *f 364 2 1 6 b * d e s ig n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id s e rv ic e va lv e , a h ri 95 t e st c o n d it io n s o u tdoor a m b ie...

  • Page 143: Cooling Performance Data

    62 cooling performance data e xpa n d ed pe rf o r m a n c e d a t a c o ol in g op e r a t io n m o d e l : v s h 13 048 1a * / a r *f 486 016 b * d esi g n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id ser vi ce va lv e , a h r i 95 t e st co n d it io n s o u tdoor a m bi e n t te m p e ra tu re ...

  • Page 144: Cooling Performance Data

    63 cooling performance data vsh130481a* e xpa n d ed pe r f o r m a n c e d a t a c o ol in g op e r a t io n m o d e l : v s h 13 048 1a * / a r *f 486 016 b* d esi g n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id ser vi ce va lv e , a h r i 95 t e st co n d it io n s o u tdoor a m bi e n t te m p...

  • Page 145: Cooling Performance Data

    64 cooling performance data vsh130601a* e x p a nd e d p e rf o r m a n c e da t a c o o l in g op e r a t ion m o d e l : v s h 1 3 0 6 0 1 a * / a r *f 4 8 6 0 1 6 b * d e s ig n s u b c o o li ng 9 ± 3 ° f @ t h e l iqu id s e rv ic e v a lv e , a h r i 9 5 t e s t c o n d it io n s o u tdoor a m...

  • Page 146: Cooling Performance Data

    65 cooling performance data vsh130601a* e x p a nd e d p e rf o r m a n c e da t a c o o l in g op e r a t io n m o d e l : v s h 1 3 0 6 0 1a * / a r *f 486 0 1 6 b * d e s ig n s u b c o o li n g 9 ± 3 °f @ t h e l iq u id s e rv ic e va lv e , a h ri 95 t e st c o n d it io n s o u tdoor a m b ie...

  • Page 147: Heating Performance Data

    66 heating performance data high pressure is measured at the suction service valve ( the larger valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. Expanded perfor...

  • Page 148: Heating Performance Data

    67 heating performance data high pressure is measured at the suction service valve ( the larger valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. *note: shaded a...

  • Page 149: Heating Performance Data

    68 heating performance data expanded performance data model: gsh130421a* / aruf49-00*-1* / aruf36421a* heating operation outdoor ambient temperature 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 mbh 49.0 46.4 43.7 40.8 39.0 37.8 35.1 32.4 28.7 26.5 24.4 23.0 22.1 19.9 17.6 15.4 13.1 10.7 delt...

  • Page 150: Heating Performance Data

    69 expanded performance data model: gsh130601a* / aruf61-00*-1* / aruf48601a* heating operation outdoor ambient temperature 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 mbh 69.8 66.0 62.2 58.1 55.5 53.8 50.0 46.1 43.6 40.3 37.1 35.0 33.7 30.2 26.8 23.4 20.0 16.3 delta t 35.9 34.0 32.0 29.9 2...

  • Page 151: Heating Performance Data

    70 high pressure is measured at the suction service valve ( the larger valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. Heating performance data expanded perfor...

  • Page 152: Heating Performance Data

    71 heating performance data performance test all data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (cfm) as listed in the performance data sheets: if conditions vary from this, results will change as f...

  • Page 153: Heating Performance Data

    72 heating performance data high pressure is measured at the suction service valve ( the larger valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. *note: shaded a...

  • Page 154: Heating Performance Data

    73 heating performance data high pressure is measured at the suction service valve ( the larger valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. *note: shaded a...

  • Page 155: Heating Performance Data

    74 heating performance data performance test all data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (cfm) as listed in the performance data sheets: if conditions vary from this, results will change as f...

  • Page 156: Wiring Diagrams

    Wiring diagrams 75 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Gsh/vsh130[18-60]1a*/1b* u se n .E .C . C l as s 2 wi r e no t e s : 1 ) t o i n d o o r u n it...

  • Page 157: Wiring Diagrams

    Wiring diagrams 76 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Gsh130[36-60]3a* & gsh130[48-60]4a* us e n. E .C . Cl a s s 2 wi r e no t e s : 1 ) t o in d o ...

  • Page 158

    1 • refer to service manual rs6100004 for installation, op- eration, and troubleshooting information. • all safety information must be followed as provided in the service manual. • refer to the appropriate parts catalog for part number information. Models listed on page 3. Ash 13 seer split system h...

  • Page 159: Product Identification

    Product identification 2 the model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. Warning warning only individuals meeting the requirements of an "entry level technician" as specified by the ai...

  • Page 160: Product Identification

    Product identification 3 warning warning warning warning to prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design c...

  • Page 161: Product Design

    Product design 4 ash13 seer heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the...

  • Page 162: Heat Pump Specifications

    5 heat pump specifications ash130[18-60]*a* (1) wire size should be determined in accordance with national electrical codes. Extensive wire runs will require larger wire sizes. (2) maximum overcurrent protection device: must use time delay fuse or hacr type circuit breaker of the same size as noted....

  • Page 163: Cooling Performance Data

    6 cooling performance data ash130181a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13018 1a * & a r u f 032- 00* -1* / a r u f 18 241a * c o ol ing op e r a t io n o u tdoor a m bi e n t t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b a ir fl...

  • Page 164: Cooling Performance Data

    7 cooling performance data ash130181a* expa nd e d perf o rm a nce da ta c ool ing op e ra t ion mo d e l : g s h 130181 a * / a r u f 32- 00* -1 * / a r u f 1 8241a * o utdoor a m bi e nt t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b * a ir fl o ...

  • Page 165: Cooling Performance Data

    8 cooling performance data ash130241a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13024 1a * & a r u f 032- 00* -1* / a r u f 18 241a * c o ol ing op e r a t io n o u tdoor a m bi e n t t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b a ir fl...

  • Page 166: Cooling Performance Data

    9 cooling performance data ash130241a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13024 1a * & a r u f 032- 00* -1* / a r u f 18 241a * coo l in g o p era t io n o utdoor a m bi e nt t e m p e ra tur e 65 75 85 95 1 05 1 15 e nt e ri n g i n door w e t b ul b t e m p e ra tur e id b * ai rf ...

  • Page 167: Cooling Performance Data

    10 cooling performance data ash130301a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13030 1a * & a r u f 042- 00* -1* / a r u f 30 301a * c o ol ing op e r a t io n o u tdoor a m bi e n t t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b a ir f...

  • Page 168: Cooling Performance Data

    11 cooling performance data ash130301a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13030 1a * & a r u f 042- 00* -1* / a r u f 30 301a * c o ol ing op e r a t io n o utdoor a m bi e nt t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b * a ir f...

  • Page 169: Cooling Performance Data

    12 cooling performance data ash130361a* expa n d e d perf o rm a nce da t a mo d e l : a s h 13036 1a * & a r u f 049- 00* -1* / a r u f 36 421a * c o ol in g op e r a t io n o utdoor a m bi e nt t e m p e ra tur e 65 75 85 95 1 05 1 15 e nt e ri n g i n door w e t b ul b t e m p e ra tur e id b a i...

  • Page 170: Cooling Performance Data

    13 cooling performance data ash130361a* expa nd e d perf o rm a n ce da ta m o del : a s h13036 1a * & a ruf 049- 00*- 1* / a ruf36 421a * c o ol ing op e r a t io n o u tdoor a m bi e n t t e m p erat ure 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p erat ure idb* a ir fl o w 59...

  • Page 171: Cooling Performance Data

    14 cooling performance data ash130421a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13042 1a * & a r u f 049- 00* -1* / a r u f 36 421a * c o ol ing op e r a t io n o u tdoor a m bi e n t t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b a ir f...

  • Page 172: Cooling Performance Data

    15 cooling performance data ash130421a* expa nd e d perf o rm a nce da t a mo d e l : a s h 13042 1a * & a r u f 049- 00* -1* / a r u f 36 421a * c o oli n g op e r a t io n o utdoor a m bi e nt t e m p e ra tur e 65 75 85 95 1 05 1 15 e nt e ri n g i n door w e t b ul b t e m p e ra tur e id b * ai...

  • Page 173: Cooling Performance Data

    16 cooling performance data ash130481a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13048 1a * & a r u f 061- 00* -1* / a r u f 48 601a * c o ol ing op e r a t io n o u tdoor a m bi e n t t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b a ir f...

  • Page 174: Cooling Performance Data

    17 cooling performance data ash130481a* expa nd e d perf o rm a nce da ta mo d e l : a s h 13048 1a * & a r u f 061- 00* -1* / a r u f 48 601a * c o ol ing op e r a t io n o utdoor a m bi e nt t e m p er atur e 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p er atur e id b * a ir f...

  • Page 175: Cooling Performance Data

    18 cooling performance data ash130601a* expa n d e d perf o rm a nce da t a mo d e l : a s h 13060 1a * & a r u f 061- 00* -1* / a r u f 48 601a * c o ol in g op e r a t io n o utdoor a m bi e nt t e m p e ra tur e 65 75 85 95 1 05 1 15 e nt e ri n g i n door w e t b ul b t e m p e ra tur e id b a i...

  • Page 176: Cooling Performance Data

    19 cooling performance data ash130601a* expa nd e d perf o rm a nce da ta m o del : a s h13060 1a * & a ruf 061- 00*- 1 * / a ruf48 601a * c o ol ing op e r a t io n o u tdoor a m bi e n t t e m p erat ure 65 75 85 95 1 05 1 15 e n te ri n g i n door w e t b u lb t e m p erat ure id b * a ir fl o w ...

  • Page 177: Heating Performance Data

    20 heating performance data high pressure is measured at the liquid service valve (the smaller valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. Expanded perform...

  • Page 178: Heating Performance Data

    21 heating performance data high pressure is measured at the liquid service valve (the smaller valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. Expanded perform...

  • Page 179: Heating Performance Data

    22 high pressure is measured at the liquid service valve (the smaller valve). Amps = outdoor unit amps (comp.+fan) low pressure is measured at the gauge port connection. Kw = total system power calculations are based on nominal cfm and 70 °f indoor dry bulb. Heating performance data expanded perform...

  • Page 180: Performance Data

    23 performance data performance test all data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (cfm) as listed in the performance data sheets: if conditions vary from this, results will change as follows: ...

  • Page 181: Wiring Diagrams

    Wiring diagrams 24 wa rn in g hi gh v o l t age ! Di s c onne ct al l p o we r be f o re s e r v ici ng or i n s t al l ing t h is u n it . M u lti ple po w e r s o u r c es m a y b e pr esen t . F a ilu r e to do s o m a y caus e p r op e r t y dam age , p e rs onal i n j ury or de at h. Ash130[18-...

  • Page 182

    • refer to service manual rs6100004 for installation, op- eration, and troubleshooting information. • all safety information must be followed as provided in the service manual. Models listed on page 3. Gsh 14 seer remote heat pump rt6213004 rev. 1 june 2008 this manual is to be used by qualified hva...

  • Page 183: Product Identification

    Product identification 2 the model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. Warning warning warning warning high voltage! Disconnect all power before servicing or installing this unit. Mu...

  • Page 184: Product Identification

    Product identification 3 the model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. Warning warning warning warning to prevent the risk of property damage, personal injury, or death, do not store...

  • Page 185: Product Design

    Product design 4 gsh14 seer split system heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications. Air is drawn through the outdoor coil by a propeller fan, and is discharged vertically out the top of the unit. No additional restrictio...

  • Page 186: Heat Pump Specifications

    5 heat pump specifications gsh14[018-060]1a* (1) wire size should be determined in accordance with national electrical codes. Extensive wire runs will require larger wire sizes. (2) must use fuses or hacr-type circuit breakers of the same size as noted. Notes: * always check the s&r plate for electr...

  • Page 187: Cooling Performance Data

    6 cooling performance data gsh140181a* expa nded performa n ce da ta c o ol in g o p er a t io n m o d e l: g s h 140 181 a * / c a *f 31 31b6a *+ t xv / m b r 800 ** -1 d es ign subcoo li ng, 9 ± 3 ° f @ t h e l iqu id s e rv ic e v a lv e, a r i 9 5 t est con d it io ns o u tdoor a m bi ent t e m ...

  • Page 188: Cooling Performance Data

    7 cooling performance data gsh140181a* expa nded performa n ce da ta c o ol in g o p er a t io n m o d e l: gsh 140 181 a * / c a *f 31 31b 6a *+ t xv / m b r 800 **-1 d es ign subcoo li ng, 9 ± 3 ° f @ the l iqu id s e rvic e v a lv e, a r i 9 5 test con d it io ns o u td o o r a m b ie n t te m p ...

  • Page 189: Cooling Performance Data

    8 cooling performance data gsh140241a* e xpa nded pe rf o r m a nce da t a co oli n g oper a t ion m o d e l: gsh 1 4 0 2 4 1 a * / c a *f 36 36 b 6 a *+ t xv / m b r 8 00 ** 1 d e s ign subc ool ing 9 ±3 ° f @ the l iqui d se rvi c e val ve, a r i 95 tes t c ondi ti ons out doo r a m b ie n t t e m...

  • Page 190: Cooling Performance Data

    9 cooling performance data gsh140241a* e xpa nded pe rf o r m a nce da t a co oli n g oper a t ion m o d e l: gsh 1 4 0 2 4 1 a * / c a *f 36 36 b 6 a *+ t xv / m b r 8 00 ** 1 d e s ign subc ooli ng 9 ±3 ° f @ the li qui d se rvi c e val ve, a r i 95 tes t c ondit ions o u td o o r a m b ien t t e ...

  • Page 191: Cooling Performance Data

    10 cooling performance data gsh140301a* expa nded perf o rma n ce da t a c o ol in g o p er a t io n m o de l: gs h140 301 a * / ca *f 36 36b 6a * +t x v / m b r 1 200 **-1 d es ign s ubco o li ng 9 ± 3 °f @ th e l iquid ser v ice v a lv e , a r i 95 tes t cond it ion s o u tdoor a m bi e n t t e m ...

  • Page 192: Cooling Performance Data

    11 cooling performance data gsh140301a* expa nded perf o rma n ce da t a c o ol in g o p er a t io n m o de l: gs h140 301 a * / ca *f 36 36b 6a * +t x v / m b r 1200 **-1 d es ign s ubco o li ng 9 ± 3 °f @ th e l iquid ser v ice v a lv e , a r i 95 tes t cond it ion s o u tdoor a m bi e n t t e m p...

  • Page 193: Cooling Performance Data

    12 cooling performance data gsh140361a* expa nded perf o rma n ce da t a c o ol in g o p er a t io n m o d e l: gs h 140 361 a * / c a *f 48 60c 6a * +t x v / m b r 1600 **-1 d e si g n s ubcoo li n g 9 ± 3 °f @ th e l iq ui d ser v ice v a lve, a r i 95 tes t c o ndi ti o n s o u tdoor a m bi e n t...

  • Page 194: Cooling Performance Data

    13 cooling performance data gsh140361a* expa nded perf o rma n ce da t a c o ol in g o p er a t io n m o d e l: gs h 140 361 a * / c a *f 48 60c 6a * +t x v / m b r 1600 **-1 d e si g n s ubcoo li n g 9 ± 3 °f @ th e l iq ui d ser v ice v a lve, a r i 95 tes t c o ndi ti o n s o u tdoor a m bi e n t...

  • Page 195: Cooling Performance Data

    14 cooling performance data gsh140421a* e xpa nded performa n ce da ta c o ol in g op e r a t ion m o d e l: gsh 1404 21a * / c a *f4860d 6a *+ t xv / m b r 2000**-1 d es ig n su bco o lin g, 9 ± 3 °f @ th e liquid serv ice v a lv e, a r i 95 t e st con d it ions o u td o o r a m b ien t t e m p era...

  • Page 196: Cooling Performance Data

    15 cooling performance data gsh140421a* e xpa nded perf o rm a n ce da ta c ooling oper a t ion m o de l: gs h1404 21a * / ca *f4860d6a *+ t x v / m b r2000**-1 d es ig n s u bco o lin g, 9 ± 3 °f @ th e liquid serv ice v a lv e, a r i 95 t e st con d it ions outd oor a m b ie n t te m p e ra tur e ...

  • Page 197: Cooling Performance Data

    16 cooling performance data gsh140481a* e xpa nded perf o rm a n ce da ta c ooling oper a t ion m o de l: gs h1404 81a * / ca *f4860d6a *+ t x v / m b r2000**-1 d es ig n s u bco o lin g 9 ± 3 °f @ th e liqu id serv ice v a lv e, a r i 95 t e st con d it io ns outd oor a m b ie n t te m p e ra tur e...

  • Page 198: Cooling Performance Data

    17 cooling performance data gsh140481a* e xpa nded perf o rm a n ce da ta c ooling oper a t ion m o de l: gs h1404 81a * / ca *f4860d6a *+ t x v / m b r2000**-1 d es ig n s u bco o lin g 9 ± 3 °f @ th e liqu id serv ice v a lv e, a r i 95 t e st con d it io ns outd oor a m b ie n t te m p e ra tur e...

  • Page 199: Cooling Performance Data

    18 cooling performance data gsh140601a* e xpa nded performa n ce da ta c o oli n g oper a t io n m o d e l: gsh 1406 01a * / c a *f 4860d 6a * + t xv / m b r 2000* *- 1 d es ig n su bco o lin g 9 ± 3 °f @ th e liqu id ser v ice v a lv e, a r i 95 t e st con d it ion s outd oor a m b ie n t te m p e ...

  • Page 200: Cooling Performance Data

    19 cooling performance data gsh140601a* e xpa nded performa n ce da ta c o oli n g oper a t io n m o d e l: gsh 1406 01a * / c a *f 4860d 6a * + t xv / m b r 2000* *- 1 d es ig n su bco o lin g 9 ± 3 °f @ th e liqu id ser v ice v a lv e, a r i 95 t e st con d it ion s outd oor a m b ie n t te m p e ...

  • Page 201: Performance Data

    20 performance data outdoor temp. ° f. Total btuh sensible btuh latent btuh total watts 75° 18,900 13,282 5,618 1,367 80° 18,675 13,290 5,385 1,410 85° 18,450 13,295 5,155 1,452 90° 18,225 13,344 4,881 1,489 95° 18,000 13,389 4,611 1,526 100° 17,550 13,301 4,249 1,558 105° 17,100 13,201 3,899 1,589 ...

  • Page 202: Expanded Performance Data

    21 expanded performance data model: gsh140181a* / ca*f3131b6a*+txv / mbr800**-1 heating operation outdoor ambient temperature 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 mbh 22.6 21.4 20.2 18.8 18.0 17.4 16.2 14.9 13.6 12.5 11.5 10.9 10.5 9.4 8.3 7.3 6.2 5.1 delta t 34.9 33.1 31.1 29.1 27.8...

  • Page 203: Expanded Performance Data

    22 split system heating performance expanded performance data model: gsh140421a* / ca*f4860d6a*+txv / mbr2000**-1 heating operation outdoor ambient temperature 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10 mbh 49.8 47.1 44.4 41.5 39.6 38.4 35.6 32.9 31.2 28.8 26.6 25.1 24.1 21.7 19.2 16.8 14.3 ...

  • Page 204: Heating Specifications

    23 heating specifications capacity btuh c.O.P. 4.8 9.6 14.4 19.2 65 22.63 4.23 39.008 55.391 71.7732 88.156 60 21.42 4.09 37.802 54.185 70.5672 86.950 55 20.16 3.93 36.542 52.925 69.3072 85.690 50 18.85 3.75 35.228 51.611 67.9932 84.376 45 17.44 3.54 33.824 50.207 66.5892 82.972 40 16.20 3.36 32.582...

  • Page 205: Performance Data

    24 performance data performance test all data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (cfm) as listed in the performance data sheets: if conditions vary from this, results will change as follows: ...

  • Page 206: Wiring Diagrams

    Wiring diagrams 25 high voltage! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Gsh140[18-60]1a* u se n .E .C . C l as s 2 wi r e no te s : 1) t o i n d o o r u n it l o w v o...

  • Page 207: Gsh 10 Seer

    Gsh 10 seer remote heat pumps repair parts rp-364a this manual is to be used by qualified technicians only. Www.Goodmanmfg.Com www.Amana-hac.Com this manual replaces rp-364. © 2009 goodman manufacturing company, l.P. ◊ 5151 san felipe, suite 500 ◊ houston, tx 77056 october 2006 gsh100903aa gsh100903...

  • Page 208

    Important information for assistance within the u.S.A. Contact: international division goodman company, l.P. 7401 security way houston, texas 77040 713-861-2500-telephone 713-863-2382-facsimile for assistance outside the u.S.A. Contact: index functional parts list rev. A: added "ab" models. Illustra...

  • Page 209

    Functional parts part no: description: 0130m00025s 24v relay cap200000440rps capacitor 20/370v zr108kctf5950 compressor 10900, 200/230/60/3 (m5, m6) zr108kctfd950 compressor 10900, 460/60/3 (m7, m8) zr84kctf5950 compressor 85500, 200/230/60/3 (m1, m2) zr84kctfd950 compressor 85500, 460/60/3 (m3, m4)...

  • Page 210

    Control cover/control box 4 rp-364a www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 211

    Control cover/control box ref. No: part no: description: ref. No: part no: description: image 1: lower access panel (m5, m6, m7, m8) 4400211pdg 11 lower access panel (m1, m2, m3, m4) 4400212pdg 11 control cover 0121r00053pdg 21 contactor cont3p040024vs 71 capacitor 20/370v cap200000440rps 81 capacit...

  • Page 212

    Compressor/tubing assembly 6 rp-364a www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 213

    Compressor/tubing assembly ref. No: part no: description: ref. No: part no: description: image 1: filter drier (bi-flow) b1219227 21 solenoid coil cord w/1/4"terminal b1225020 31 valve core b1787000 41 cut-out switch, low pressure b1360719 61 cut-out switch, high pressure b1360721 71 accumulator b12...

  • Page 214

    Coil/cabinet top/side panels 8 rp-364a www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 215

    Coil/cabinet top/side panels ref. No: part no: description: ref. No: part no: description: image 1: venturi top panel 35" 0121r00013pdg 11 wire grill 35" 0152r00003 21 fan blade 26" b1086768 31 motor mount bracket 0121r00003 41 cond motor 1 hp, 1 sp, 230v (m1, m2, m5, m6) 0131m00040s 51 cond motor 1...

  • Page 216: Gsh13

    Gsh13 remote heat pumps repair parts rp-436g this manual is to be used by qualified technicians only. Www.Goodmanmfg.Com www.Amana-hac.Com this manual replaces rp-436f. © 2008 goodman manufacturing company, l.P. ◊ 5151 san felipe, suite 500 ◊ houston, tx 77056 october 2008 gsh130181ac gsh130181ba gs...

  • Page 217

    Important information for assistance within the u.S.A. Contact: international division goodman company, l.P. 7401 security way houston, texas 77040 713-861-2500-telephone 713-863-2382-facsimile for assistance outside the u.S.A. Contact: index functional parts list rev. G: added model gsh130421ae. Il...

  • Page 218

    Functional parts part no: description: cap050300370rss capacitor 5/30/370v (m3, m4, m5) cap050350370rss capacitor 5/35/370v (m1, m2, m6, m7, m10, m11) cap050000370vas capacitor 5/370v (m16, m17, m23, m24) cap050400370rss capacitor 5/40/370v (m8, m9) cap050550370rts capacitor 5/50/370v (m18, m19, m20...

  • Page 219

    Control cover/control box 4 rp-436g www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 220

    Control cover/control box ref. No: part no: description: ref. No: part no: description: image 1: lower access panel (m1, m2, m3, m5, m6, m7, m18, m19, m20) 4400201pdg 11 lower access panel (m8, m9, m10, m11, m21, m22, m23, m24) 4400202pdg 11 lower access panel (m4) 4400203pdg 11 lower access panel (...

  • Page 221

    Basepan/compressor/coil assembly 6 rp-436g www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 222

    Basepan/compressor/coil assembly ref. No: part no: description: ref. No: part no: description: image 1: tubing assy, cond coil (m6, m7) 0201r00058s 11 tubing assy, cond coil (m10, m11) 0201r00066s 11 tubing assy, cond coil (m21, m22, m23, m24) 0201r00068s 11 tubing assy, cond coil (m18, m19, m20) 02...

  • Page 223

    Tubing assembly 8 rp-436g www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 224

    Tubing assembly ref. No: part no: description: ref. No: part no: description: image 1: reversing valve (m1, m2, m3, m4, m5, m6, m7) b1227315s 21 reversing valve (m8, m9, m10, m11) b1227316s 21 reversing valve (m12, m13, m14, m15, m16, m17, m18, m19, m21, m22, m23, m24) b1227317s 21 reversing valve (...

  • Page 225

    Cabinet top/side panels 10 rp-436g www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 226

    Cabinet top/side panels ref. No: part no: description: ref. No: part no: description: image 1: top panel 26" (m2, m5, m9) 0121r00008pdg 11 top panel 29" (m1, m3, m4, m6, m7, m8, m10, m11, m12, m13, m14, m15, m16, m17, m18, m19, m20, m21, m22, m23, m24) 0121r00010pdg 11 cond motor 1/4 hp, 1 sp, 8 pl ...

  • Page 227: Gsh 14 Seer

    Copyright © 2008 goodman manufacturing company, l.P gsh 14 seer remote heat pumps this manual is to be used by qualified technicians only. Rp-356d may 2008 repair parts www.Goodmanmfg.Com goodman manufacturing company, l.P. 5151 san felipe, suite 500 houston, tx 77056 www.Amana-hac.Com this manual r...

  • Page 228

    Copyright © 2008 goodman manufacturing company, l.P. Important information for assistance within the u.S.A. Contact: international division goodman company, l.P. 7401 security way houston, texas 77040 713-861-2500-telephone 713-863-2382-facsimile for assistance outside the u.S.A. Contact: index func...

  • Page 229

    Functional parts part no: description: zr16k4pfv930 compressor 16500, 208/230/60/1 (m1, m2) zr22k4pfv930 compressor 22000, 208/230/60/1 (m3, m4, m5) zr24k4pfv930 compressor 24000, 208/230/60/1 (m6, m7, m8) zr30k3pfv930 compressor 31100, 208/230/60/1 (m9, m10, m11, m12, m13, m14) zr34k3pfv930 compres...

  • Page 230

    Control cover / control box 4 rp-356d.

  • Page 231

    Control cover / control box ref. No: part no: description: ref. No: part no: description: image 1: lower access panel (m1, m2) 4400202pdg 11 lower access panel (m3, m4, m5, m6, m7, m8, m9, m10, m11, m12, m13, m14, m15, m16, m17, m18, m19, m20, m21, m22, m23, m24, m25, m26) 4400205pdg 11 control cove...

  • Page 232

    Tubing assembly 6 rp-356d.

  • Page 233

    Tubing assembly ref. No: part no: description: ref. No: part no: description: image 1: reversing valve (m1, m2, m3, m4, m5, m6, m7, m8) b1227316s 21 reversing valve (m9, m10, m11, m12, m13, m14, m15, m16, m17, m18, m19, m20, m21, m22, m23, m24, m25, m26) b1227318s 21 txv valve 3 r22 (m9, m10, m11, m...

  • Page 234

    Cabinet top / side panels / cond coil 8 rp-356d.

  • Page 235

    Cabinet top / side panels / cond coil ref. No: part no: description: ref. No: part no: description: image 1: top panel 29" (m1, m2, m3, m4, m5, m6, m7, m8) 0121r00010pdg 11 top panel 35" (m9, m10, m11, m12, m13, m14, m15, m16, m17, m18, m19, m20, m21, m22, m23, m24, m25, m26) 0121r00012pdg 11 cond m...

  • Page 236: Repair Parts

    Repair parts rp-392e this manual is to be used by qualified technicians only. This manual replaces rp-392d. Www.Amana-hac.Com amana is a trademark of maytag corporation and used under license to goodman company, l.P. All rights reserved. © 2006-2008 goodman company, l.P. ◊ 5151 san felipe, suite 500...

  • Page 237

    Important information for assistance within the u.S.A. Contact: consumer affairs department goodman company, l.P. 7401 security way houston, texas 77040 877-254-4729-telephone 713-863-2382-facsimile international division goodman company, l.P. 7401 security way houston, texas 77040 713-861-2500-tele...

  • Page 238

    Functional parts part no: description: b1226207 accumulator (m12, m13, m14, m15, m16, m17, m18, m19, m20, m21, m22, m23) b1226206 accumulator (m1, m2, m3, m4, m5, m6, m7, m8, m9, m10, m11) cap050300370rss capacitor 5/30/370v (m1, m2, m3) cap050350370rss capacitor 5/35/370v (m4, m5, m6, m7, m8, m9, m...

  • Page 239

    Control cover/control box 4 rp-392e www.Amana-hac.Com.

  • Page 240

    Control cover/control box ref. No: part no: description: ref. No: part no: description: image 1: lower access panel (m1, m2, m3, m4, m5, m6, m7, m16, m17, m18) 4400201pdg 11 lower access panel (m8, m9, m10, m11, m19, m20, m21, m22, m23) 4400202pdg 11 lower access panel (m12, m13, m14, m15) 4400205pd...

  • Page 241

    Coil/compressor/tubing 6 rp-392e www.Amana-hac.Com.

  • Page 242

    Coil/compressor/tubing ref. No: part no: description: ref. No: part no: description: image 1: muffler 1/2 x 1/2 (m7, m11, m15) b1219301 11 reversing valve (m1, m2, m3, m4, m5, m6, m7) b1227315s 21 reversing valve (m8, m9, m10, m11) b1227316s 21 reversing valve (m12, m13, m14, m15, m16, m17, m18, m19...

  • Page 243

    Cabinet top/side panels 8 rp-392e www.Amana-hac.Com.

  • Page 244

    Cabinet top/side panels ref. No: part no: description: ref. No: part no: description: image 1: venturi top panel 29" (m1, m2, m3, m4, m5, m6, m7, m8, m9, m10, m11, m12, m13, m14, m15, m16, m17, m18, m19, m20, m21) 0121r00011pdg 11 venturi top panel 35" (m22, m23) 0121r00013pdg 11 wire grill 29" (m1,...

  • Page 245: Repair Parts

    Repair parts rp-569a this manual is to be used by qualified technicians only. This manual replaces rp-569 www.Goodmanmfg.Com © 2009 goodman manufacturing company, l.P. ◊ 5151 san felipe, suite 500 ◊ houston, tx 77056 may 2009 vsh13 remote heat pumps vsh130181aa vsh130191aa vsh130241aa vsh130251aa vs...

  • Page 246

    Important information for assistance within the u.S.A. Contact: international division goodman company, l.P. 7401 security way houston, texas 77040 713-861-2500-telephone 713-863-2382-facsimile for assistance outside the u.S.A. Contact: index functional parts list rev. A: added models vsh130181aa, v...

  • Page 247

    Functional parts part no: description: cap050300440rss capacitor 5/30/370v [control box] (m2, m3) cap050350440rss capacitor 5/35/440v [control box] (m1, m4, m6, m7) cap050400370rss capacitor 5/40/370v [control box] (m5) cap050500440rts capacitor 5/50/440v [control box] (m8) cap050550440rts capacitor...

  • Page 248

    Control cover/control box 4 rp-569a www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 249

    Control cover/control box ref. No: part no: description: ref. No: part no: description: image 1: lower access panel (m1, m2, m3, m4, m8) 4400201pbb 11 lower access panel (m5, m6, m9, m10) 4400202pbb 11 lower access panel (m7) 4400205pbb 11 control cover 0121r00053pbb 21 contactor 25 amp, 2p, 24v (m1...

  • Page 250

    Cabinet top/side panels/cond coil 6 rp-569a www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 251

    Cabinet top/side panels/cond coil ref. No: part no: description: ref. No: part no: description: image 1: top panel 26" (m1, m3, m5) 0121r00008pbb 11 top panel 29" (m2, m4, m6, m7, m8, m9) 0121r00010pbb 11 top panel 35" (m10) 0121r00012pbb 11 cond motor 1/4 hp, 1 sp, 8 pl (m7, m8, m9) 0131m00014ps 21...

  • Page 252

    Tubing assembly 8 rp-569a www.Goodmanmfg.Com www.Amana-hac.Com.

  • Page 253

    Tubing assembly ref. No: part no: description: ref. No: part no: description: image 1: accumulator (m1, m2, m3, m4, m5, m6) b1226206 11 accumulator .875 (m7, m8, m9, m10) b1226207 11 base pan 26" (m1, m3, m5) 0121r00005pbb 21 base pan 29" (m2, m4, m6, m7, m8, m9) 0121r00006pbb 21 base pan 35" (m10) ...