Goodman CPG0360451D***B Series Specifications

Manual is about: CPG Commercial 3- to 6-Ton Packaged Gas/Electric Units 13 SEER / up to 11.3 EER 80% AFUE

Summary of CPG0360451D***B Series

  • Page 1

    Ss-cpg36-72 www.Goodmanmfg.Com 3/12 supersedes 11/11 standard features • r-410a chlorine-free refrigerant • tufftube™ tubular heat exchanger • high-efficiency scroll compressor • high- and low-pressure switches • copper tube / aluminum fin coils • contactor with lugs • high-capacity, steel-cased fil...

  • Page 2

    P roduct s pecifications p roduct s pecifications 2 www.Goodmanmfg.Com ss-cpg36-72 n omenclature c p g 060 045 3 b * * * a * 1 2 3 4,5,6 7,8,9 10 11 12 13 14 15 16 revision levels major & minor brand factory-­‐installed op7ons c commercial x no opcons a non-­‐powered convenience outlet configura7on b...

  • Page 3: — Cpg036

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 3 p roduct s pecifications — cpg036 cpg036 0451d***b* cpg036 0453d***b* cpg036 0453b***b* cpg036 0454b***b* cooling capacity total btu/h 34,600 34,600 34,600 34,600 sensible btu/h 25,600 25,600 25,600 25,600 seer / eer ...

  • Page 4: — Cpg036 (

    P roduct s pecifications p roduct s pecifications 4 www.Goodmanmfg.Com ss-cpg36-72 p roduct s pecifications — cpg036 ( cont .) cpg036 0901d***b* cpg036 0903d***b* cpg036 0903b***b* cpg036 0904b***b* cpg036 0907b***b* cooling capacity total btu/h 34,600 34,600 34,600 34,600 34,600 sensible btu/h 25,6...

  • Page 5: — Cpg048

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 5 p roduct s pecifications — cpg048 cpg048 0901d***b* cpg048 0903d***b* cpg048 0903b***b* cpg048 0904b***b* cooling capacity total btu/h 45,500 45,500 45,500 45,500 sensible btu/h 35,000 35,000 35,000 35,000 seer / eer ...

  • Page 6: — Cpg048 (

    P roduct s pecifications p roduct s pecifications 6 www.Goodmanmfg.Com ss-cpg36-72 p roduct s pecifications — cpg048 ( cont .) cpg048 1151d***b* cpg048 1153d***b* cpg048 1153b***b* cpg048 1154b***b* cpg048 1157b***b* cooling capacity total btu/h 45,500 45,500 45,500 45,500 45,500 sensible btu/h 35,0...

  • Page 7: — Cpg060

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 7 p roduct s pecifications — cpg060 cpg060 0901d***b* cpg060 0903d***b* cpg060 0903b***b* cpg060 0904b***b* cooling capacity total btu/h 59,500 59,500 59,500 59,500 sensible btu/h 43,200 43,200 43,200 43,200 seer / eer ...

  • Page 8: — Cpg060 (

    P roduct s pecifications p roduct s pecifications 8 www.Goodmanmfg.Com ss-cpg36-72 p roduct s pecifications — cpg060 ( cont .) cpg060 1401d***b* cpg060 1403d***b* cpg060 1403b***b* cpg060 1404b***b* cpg060 1407b***b* cooling capacity total btu/h 59,500 59,500 59,500 59,500 59,500 sensible btu/h 43,2...

  • Page 9: — Cpg072

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 9 p roduct s pecifications — cpg072 cpg072 1403b***b* cpg072 1404b***b* cpg072 1407b***b* cooling capacity total btu/h 71,000 71,000 71,000 sensible btu/h 48,280 48,280 48,280 eer / ieer 11.1 / 11.2 11.1 / 11.2 11.1 / 1...

  • Page 10: — Cpg036B

    P roduct s pecifications p roduct s pecifications 10 www.Goodmanmfg.Com ss-cpg36-72 a irflow d ata — cpg036b s tandard d irect d rive — h orizontal s tandard d irect d rive — d own s hot cfm static amps watts rpm speed tap cfm static amps watts rpm speed tap 1293 0.1 1.72 364 715 low 1313 0.10 1.68 ...

  • Page 11: — Cpg036B (

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 11 a irflow d ata — cpg036b ( cont .) s tandard b elt d rive — h orizontal esp (“ h 2 o) turns open 0 1 2 3 4 5 cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp 0.2 --- --- --- --- --- --- --- --- 1524 0.32 1340 0.25 0.4...

  • Page 12: — Cpg048B

    P roduct s pecifications p roduct s pecifications 12 www.Goodmanmfg.Com ss-cpg36-72 a irflow d ata — cpg048b s tandard d irect d rive — h orizontal s tandard d irect d rive — d own s hot cfm static amps watts rpm speed tap cfm static amps watts rpm speed tap 1592 0.1 2.54 543 815 low 1612 0.1 2.60 5...

  • Page 13: — Cpg048B (

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 13 a irflow d ata — cpg048b ( cont .) s tandard b elt d rive — h orizontal esp (“ h 2 o) turns open 0 1 2 3 4 5 cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp 0.2 --- --- --- --- --- --- --- --- 1800 0.47 1556 0.35 0.4...

  • Page 14: — Cpg060B

    P roduct s pecifications p roduct s pecifications 14 www.Goodmanmfg.Com ss-cpg36-72 a irflow d ata — cpg060b s tandard d irect -d rive — h orizontal s tandard d irect -d rive — d own s hot cfm static amps watts rpm speed tap cfm static amps watts rpm speed tap 1416 0.1 1.63 176 588 t1 1237 0.1 1.64 ...

  • Page 15: — Cpg060B (

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 15 a irflow d ata — cpg060b ( cont .) s tandard b elt d rive — h orizontal esp (“ h 2 o) turns open 0 1 2 3 4 5 cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp 0.2 --- --- --- --- 2460 0.96 2251 0.80 2073 0.65 1862 0.51...

  • Page 16: — Cpg072B

    P roduct s pecifications p roduct s pecifications 16 www.Goodmanmfg.Com ss-cpg36-72 a irflow d ata — cpg072b s tandard b elt d rive — h orizontal esp (in w.C.) 0 turns 1 turn 2 turns 3 turns 4 turns 5 turns cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp cfm bhp 0.2 --- --- --- --- --- --- 2749 1.18 2573 0....

  • Page 17: — Cpg036B

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 17 e xpanded c ooling d ata — cpg036b outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 13...

  • Page 18: — Cpg036B (

    P roduct s pecifications p roduct s pecifications 18 www.Goodmanmfg.Com ss-cpg36-72 e xpanded c ooling d ata — cpg036b ( cont .) outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6...

  • Page 19: — Cpg048B

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 19 e xpanded c ooling d ata — cpg048b outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 18...

  • Page 20: — Cpg048B (

    P roduct s pecifications p roduct s pecifications 20 www.Goodmanmfg.Com ss-cpg36-72 e xpanded c ooling d ata — cpg048b ( cont .) outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6...

  • Page 21: — Cpg060B

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 21 e xpanded c ooling d ata — cpg060b outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 22...

  • Page 22: — Cpg060B (

    P roduct s pecifications p roduct s pecifications 22 www.Goodmanmfg.Com ss-cpg36-72 e xpanded c ooling d ata — cpg060b ( cont .) outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6...

  • Page 23: — Cpg072B

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 23 e xpanded c ooling d ata — cpg072b outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 24...

  • Page 24: — Cpg072B (

    P roduct s pecifications p roduct s pecifications 24 www.Goodmanmfg.Com ss-cpg36-72 e xpanded c ooling d ata — cpg072b ( cont .) outdoor ambient t emper ature 65 75 85 95 105 115 entering indoor w et bulb t emper ature idb airfl o w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6...

  • Page 25: Appendix C Unit Dimensions

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 25 d imensions 30 appendix c unit dimensions horizontasl discharge vertical discharge note for horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply ...

  • Page 26

    P roduct s pecifications p roduct s pecifications 26 www.Goodmanmfg.Com ss-cpg36-72 u nit c learances maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible rem...

  • Page 27: — R

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 27 r oof c urb i nstallation — r igging provisions for forks have been included in the unit base frame. No other fork locations are approved. • unit must be lifted by the four lifting holes located at the base frame cor...

  • Page 28

    P roduct s pecifications p roduct s pecifications 28 www.Goodmanmfg.Com ss-cpg36-72 r oof c urb i nstallation ( cont .) curb installations must comply with local codes and should follow the established guidelines of the national roofing contractors association. Proper unit installation requires that...

  • Page 29: —

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 29 w iring d iagram — cpg0360451d (s ingle -p hase , d irect d rive ) 2. For 208 volt transformer operation move black wire from terminal 3 to terminal 2 on transformer. 1. Replacement wire must be the same size and typ...

  • Page 30: —

    P roduct s pecifications p roduct s pecifications 30 www.Goodmanmfg.Com ss-cpg36-72 w iring d iagram — cpg036/480901d (s ingle -p hase d irect d rive ) 2. For 208 volt transformer operation move black wire from terminal 3 to terminal 2 on transformer. 1. Replacement wire must be the same size and ty...

  • Page 31: —

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 31 w iring d iagram — cpg060*1d (s ingle -p hase d irect d rive ) auxillary limit switch female plug/connector integrated ignition control vmr ls 4 installer/serviceman troubleshooting this appliance. Status light codes...

  • Page 32: —

    P roduct s pecifications p roduct s pecifications 32 www.Goodmanmfg.Com ss-cpg36-72 w iring d iagram — cpg060*3d (t hree -p hase , d irect d rive ) wiring is subject to change. Al wa ys refer to the wiring diag ram or the unit for the most up-to-da te wiring . ⚠ w arnin g high voltage: disconnect al...

  • Page 33: —

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 33 w iring d iagram — cpg036.48*3d (t hree -p hase d irect d rive ) wiring is subject to change. Al wa ys refer to the wiring diag ram or the unit for the most up-to-da te wiring . ⚠ w arnin g high voltage: disconnect a...

  • Page 34: —

    P roduct s pecifications p roduct s pecifications 34 www.Goodmanmfg.Com ss-cpg36-72 w iring d iagram — cpg036/48*3d (t hree -p hase , d irect d rive ) wiring is subject t o chang e. Alw ay s re fer to the wiring diagr am or the unit for the mos t up-t o-da te wiring. ⚠ w arning high volt ag e: disc ...

  • Page 35: , B

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 35 w iring d iagram — cpg036-600904b/7b — cpg036*4b/7b — cpg072*4b/7b (460v/575 v , b elt d rive ) wiring is subject to change. Al wa ys refer to the wiring diag ram or the unit for the most up-to-da te wiring . ⚠ w arn...

  • Page 36: —

    P roduct s pecifications p roduct s pecifications 36 www.Goodmanmfg.Com ss-cpg36-72 w iring d iagram — cpg036/48/600903b — cpg072*3b (t hree -p hase , b elt d rive ) wiring is subject to change. Al wa ys refer to the wiring diag ram or the unit for the most up-to-da te wiring . ⚠ w arnin g high volt...

  • Page 37: —

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 37 w iring d iagram — cpg036/480454b — cpg072*4b/7b (460v/ 575v b elt d rive ) wiring is subject to change. Al wa ys refer to the wiring diag ram or the unit for the most up-to-da te wiring . ⚠ w arnin g high voltage: d...

  • Page 38: —

    P roduct s pecifications p roduct s pecifications 38 www.Goodmanmfg.Com ss-cpg36-72 w iring d iagram — cpg036/480453b (t hree -p hase , b elt d rive ) wiring is subject to change. Al wa ys refer to the wiring diag ram or the unit for the most up-to-da te wiring . ⚠ w arnin g high voltage: disconnect...

  • Page 39

    P roduct s pecifications p roduct s pecifications ss-cpg36-72 www.Goodmanmfg.Com 39 a ccessories item # description fits model sizes field- installed factory- installed 14curb3672b 14" roof curb 3-6 tons √ 25fd3672 25% manual fresh air damper 3-6 tons √ 25mfd3672 25% motorized fresh air damper 3-6 t...

  • Page 40

    P roduct s pecifications p roduct s pecifications 40 www.Goodmanmfg.Com ss-cpg36-72 goodman manufacturing company, l.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2012 • goodman manufacturing company, l.P. •...