Goodman GPC 13 SEER H Series Installation Instructions Manual

Manual is about: AIR CONDITIONERS AND HEAT PUMP UNITS

Summary of GPC 13 SEER H Series

  • Page 1

    Goodman manufacturing company, l.P. Io-390a 5151 san felipe, suite 500, houston, tx 77056 6/2011 www.Goodmanmfg.Com www.Amana-hac.Com © 2010 - 2011 goodman manufacturing company, l.P. I nstallation i nstructions f or s elf -c ontained p ackage a ir c onditioners and h eat p ump u nits gpc/gph 13 see...

  • Page 2

    2 introduction ........................................................... 2 checking product received ......................................... 2 message to the homeowner ........................................ 2 before beginning installation ...................................... 2 replacement pa...

  • Page 3

    3 consumer affairs goodman manufacturing company, l.P. 7401 security way houston, texas 77040 877-254-4729 important safety instructions recognize safety symbols, words, and labels the following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the ...

  • Page 4

    4 36" 36" 10" unit wall 36" figure 1 rooftop installation (figure 2) 1. Before locating the unit on the roof, make sure that the strength of the roof and beams is adequate to support the weight involved. (see specification sheet for weight of units.) this is very important and the installer’s respon...

  • Page 5

    5 ducting work should be fabricated by the installing contractor in accordance with local codes. Industry manuals may be used as a guide when sizing and designing the duct system- such as nesca (national environmental systems contractors association, 1501 wilson blvd., arlington, virginia 22209). Th...

  • Page 6

    6 install condensate drain trap as shown. Use ¾ “ drain connection size or larger. Do not operate without trap. Unit must be level or slightly inclined toward drain. Wiring all wiring should be made in accordance with the national electrical code. The local power company should be consulted to deter...

  • Page 7

    7 1. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of the run can be determined from table 4 using the circuit ampacity found on the unit rating plate. From the unit disconnect to unit, the smallest wire size allowable in table 4 may be used f...

  • Page 8

    8 15. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely. Final system checks 16. Check to see if all supply and return air grilles are adjusted and the air distribu...

  • Page 9

    9 4. Compressor - this item is activated by the contactor for heating and cooling, except during emergency heat. It is protected byan internal overload. 5. Contactor relay - this control is activated by the thermostat (24v coil) and supplies power to the contactor. 6. Defrost control - the defrost c...

  • Page 10

    10 calls for heat. At the end of the timing period, the unit’s defrost cycle will be initiated provided the sensor remains closed. When the sensor opens (approximately 75° f), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor tem...

  • Page 11

    11 after unit is set and ducted, verify esp with a 1" inclined manometer with pitot tubes or a magnahelic gauge and confirm cfm to blower curves in the specification sheets. All units have three speed blower motors. If low speed is not utilized, the speed tap can be changed to medium or high speed. ...

  • Page 12

    12 electric heat installation & adjustment this series of electric cooling and heat pump package equipment is designed to accept a field installed electric heat kit. The unit is equipped to easily install the hkr series electric heat kit. Full installation instructions are included in this kit. Plea...

  • Page 13

    13 troubleshooting chart warning high voltage! D isconect all power before servicing or installing this unit . M ultiple power sources may be present . F ailure to do so may cause property damage , personal injury or death . Symptom high head - low suction a. Restriction in liquid line or flowrator ...

  • Page 14

    14 wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. W a rni n g h igh vo l t a ge ! D is co n e ct al l po w e r be f o re ser vic in g or in s t al l ing th is un it . M ul t ip l e po w e r s o ur ce s ma y be pr e sen t . F ai l u r e to ...

  • Page 15

    15 gpc13(60)h21** wiring diagram wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. W a rni n g h igh vo l t a ge ! D is co n e ct al l po w e r be f o re ser vic in g or in s t al l ing th is un it . M ul t ip l e po w e r s o ur ce s ma y be...

  • Page 16

    16 wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. W a rni n g h igh vo l t a ge ! D is co n e ct al l po w e r be f o re ser vic in g or in s t al l ing th is un it . M ul t ip l e po w e r s o ur ce s ma y be pr e sen t . F ai l u r e to ...

  • Page 17

    17 wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. W a rni n g h igh vo l t a ge ! D is co n e ct al l po w e r be f o re ser vic in g or in s t al l ing th is un it . M ul t ip l e po w e r s o ur ce s ma y be pr e sen t . F ai l u r e to ...

  • Page 18

    18 this page left blank intentionally.

  • Page 19

    19 this page left blank intentionally.

  • Page 20

    20 note: specifications and performance data listed herein are subject to change without notice quality makes the difference! All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency. We have designed these units to significantly reduce t...