Goodman GPH 13 M Series Technical manual

Other manuals for GPH 13 M Series: Installation & operating instructions manual
Manual is about: Multi Position Package Heat Pump Units with R410A

Summary of GPH 13 M Series

  • Page 1

    • refer to service manual rs6300008 for installation, operation, and troubleshooting information. • all safety information must be followed as provided in the service manual. • refer to the appropriate parts catalog for part number information. • models listed on page 3. Gph 13 m series multi positi...

  • Page 2: Product Identification

    Product identification 2 the model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. Warning warning high voltage! Disconnect all power before servicing or installing this uni...

  • Page 3: Product Identification

    Product identification 3 the model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. Gph1324m41ab gph1330m41ab gph1336m41ab gph1342m41ab gph1348m41ab gph1360m41ab the united s...

  • Page 4: Product Design

    4 product design gph13 (m series) package units are designed for outdoor installations only in either residential or light commercial ap- plications and are available in 2, 2.5, 3, 3.5, 4 & 5 ton sizes. They are designed for 208/230 volt single phase applications. The connecting ductwork (supply and...

  • Page 5: Product Design

    Product design 5 outside slab installation -multi-positional (m) note: roof overhang should be no more than 36" and provi- sions made to deflect the warm discharge air out from the overhang. Minimum clearances are required to avoid air recirculation and keep the unit operating at peak efficiency. Ro...

  • Page 6: Product Design

    6 product design hkr electrical data all wires and overcurrent protection devices are sized for use with electric heaters only and without refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See package unit specifications section for minimum circuit a...

  • Page 7: Product Dimensions

    Product dimensions 7 gph13[24-60]m41* medium chassis gph1324m41* gph1330m41* gph1336m41* gph1342m41* large chassis gph1348m41* gph1360m41* blower access panel ? ? 2 34 51 47 supply 1 3/8 a return power wire entrance 4 1/8 2 1/8 6 ½ 16 16 5 ½ b b control wire entrance condensate drain connection 3/4”...

  • Page 8: Gph13[24-36]M41Ab

    Package heat pump specifications 8 gph13[24-36]m41ab (1) maximum overcurrent protection device: must use time delay fuse or hacr type circuit breaker of the same size as noted. * calculated external filter size based on air velocity of 300 ft/min. Wire size should be determined in accordance with na...

  • Page 9: Gph13[42-60]M41Ab

    Package heat pump specifications 9 gph13[42-60]m41ab (1) maximum overcurrent protection device: must use time delay fuse or hacr type circuit breaker of the same size as noted. * calculated external filter size based on air velocity of 300 ft/min. Wire size should be determined in accordance with na...

  • Page 10: Accessories

    Accessories 10 gph13[24-60]m41* part number description ot18-60a outdoor thermostat kit w/lockout stat ot/ehr18-60 emergency heat relay kit hkr electric heat kit pgc101/102/103 roof curb pehh101/102 horizontal economizer for heat pump, small and medium chassis pehh103 horizontal economizer for heat ...

  • Page 11: Blower Performance Data

    Blower performance data 11 notes: • data shown is dry coil. Wet coil pressure drop is approximate. 0.1" h 2 o, for 2 row indoor coil; 0.2” h 2 o, for 3 row indoor coil; and 0.3” h 2 o, for 4 row indoor coil. • data shown does not include filter pressure drop, approx. 0.08” h 2 o. • all models should...

  • Page 12: Blower Performance Data

    12 blower performance data 30 40 50 6 0 70 80 90 11 0 1 2 0 10 0 13 0 1 4 0 15 0 10 0 90 80 70 60 50 40 30 20 10 ou t p u t b t u /h r x 10 0 0 bt u o u t p u t v s t e mper at u r e r is e ch art temperat ur e ri se 60 0 c f m 70 0 90 0 10 0 0 11 0 0 12 0 0 14 0 0 16 0 0 18 0 0 20 0 0 22 0 0 24 0 0...

  • Page 13: Cooling Performance Data

    13 cooling performance data gph1324m41* mo d e l: g p h 1 32 4m41 * e x p a nd e d p e rf o r m a n c e da t a c ool in g op e r a t io n d esi g n s u b c o o li n g , 10 + /- 2 ° f @ t h e li q u id a cce ss fi tt in g co n n e c ti o n a h r i 95 t est co n d it io n s . D e si g n s u p e rh eat...

  • Page 14: Cooling Performance Data

    14 cooling performance data gph1324m41* m o de l : g p h1 3 2 4 m 4 1 * e x p a nd e d p e rf o r m a n c e da t a c ool in g op e r a t io n d e s ign s u b c ool in g, 1 0 + /- 2 ° f @ t h e l iqui d a c c e s s f it ti ng c onne c ti on a h ri 9 5 t e s t c ondi ti ons . D e s ign s upe rh e a t ...

  • Page 15: Cooling Performance Data

    15 cooling performance data gph1330m41* m o d e l : g p h 1330m41* e x p a nd e d p e rf o r m a n c e da t a c ool in g op e r a t io n d e s ign s u bc o o li n g, 1 0 + /- 2 °f @ t h e l iq u id a c c e s s f it ti ng c o nn e c ti on a h r i 9 5 t e s t c o nd it ions . D e s ign s upe rh e a t ...

  • Page 16: Cooling Performance Data

    16 cooling performance data gph1330m41* mo d e l : g p h 133 0m41 * ex pa n d e d p e r f o r m a n c e d a t a c o o l in g op e r a t io n d esi g n s u b c o o li n g , 10 + /- 2 ° f @ t h e l iq u id a cce ss fi tt in g co n n ec ti o n a h r i 95 t est co n d it io n s . D e si g n s u p e rh e...

  • Page 17: Cooling Performance Data

    17 cooling performance data gph1336m41* mo d e l : g p h 1 3 36m41* ex pan d e d p e r f o r m a n c e d a t a c ool in g op e r a t io n d esi g n su b c o o li n g , 9 + /- 2 ° f @ t h e l iq u id ac c e s s f it ti n g c o n n ect io n a h r i 9 5 t e st co n d it io n s . D e s ig n s u p e rh e...

  • Page 18: Cooling Performance Data

    18 cooling performance data gph1336m41* m o de l : g p h1 3 3 6 m 4 1 * e x p a nd e d pe rf o r m a n c e da t a c o o l in g o p e r a t io n d e s ign s ubc ool in g, 9 + /- 2 ° f @ t h e l iqui d a c c e s s f it ti ng c onne c ti on a h ri 9 5 t e s t c o ndi ti o n s . D e s ig n s u pe rh e a...

  • Page 19: Cooling Performance Data

    19 cooling performance data gph1342m41* mod e l : g p h 1 342 m 4 1 * ex pa n d e d p e r f o r m a n c e d a ta co o l in g o p e r a t io n d esi g n s u b c o o li n g , 10 + /- 2 ° f @ t h e l iq u id a cce ss f it ti n g co n n ec ti o n a h r i 95 t e st co n d it io n s . D e si g n s u p e r...

  • Page 20: Cooling Performance Data

    20 cooling performance data gph1342m41* mo d e l : g p h 1342m41* e x p a n d ed pe rf o r m a n c e d a t a c o o l in g op e r a t io n d e s ig n s u b c o o li n g , 1 0 + /- 2 ° f @ t h e l iq u id a cce ss f it ti n g co n n ec ti o n a h r i 95 t est co n d it io n s. D e si g n s u p e rh ea...

  • Page 21: Cooling Performance Data

    21 cooling performance data gph1348m41* m o d e l : gp h 1348m 41* e x p a nd ed p e rf orm a n c e da t a c o o l in g o p e r a t io n d esi g n s u b c o o li n g , 1 2 + /- 2 ° f @ t h e l iq u id a cce ss f it ti n g co n n e c ti o n a h r i 95 t e s t co n d it io n s . D e si g n s u p e rh ...

  • Page 22: Cooling Performance Data

    22 cooling performance data gph1348m41* m o d e l : g p h 1 3 48m 41* ex pan d e d p e r f o r m a nc e d a t a c ool in g op e r a t io n d e s ign s ubc ool in g, 1 2 + /- 2 °f @ t h e l iqui d a c c e s s f it ti ng c onne c ti on a h r i 9 5 t e s t c ondi ti ons . D e s ign s upe rh e a t 9 + /...

  • Page 23: Cooling Performance Data

    23 cooling performance data gph1360m41* mod e l : gp h 1 360m41* ex pa n d e d p e r f o r m a n c e d a t a c o o l in g op e r a t io n d e s ig n s u b c o o li n g , 9 + /- 2 ° f @ t h e l iq u id ac ces s fi tt in g c o n n e c ti o n a h r i 95 t e st c o n d it io n s . D e s ig n s u p e rh ...

  • Page 24: Cooling Performance Data

    24 cooling performance data gph1360m41* m o d e l : gp h 1 360m 41* ex pan d e d p e r f o r m a nc e d a t a c o ol in g op e r a t io n d esi g n su b c o o li n g , 9 + /- 2 ° f @ t h e l iq u id ac ces s f it ti n g c o n n ect io n a h r i 95 t e st co n d it io n s . D e s ig n s u p e rh e a ...

  • Page 25: Heating Performance Data

    25 heating performance data gph13[24-42]m41* performance test all data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (cfm) as listed in the performance data sheets: if conditions vary from this, results...

  • Page 26: Heating Performance Data

    26 heating performance data performance test all data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (cfm) as listed in the performance data sheets: if conditions vary from this, results will change as f...

  • Page 27: Wiring Diagrams

    Wiring diagrams wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. 27 wa rn in g hi gh v o l t age ! Di s c onne ct al l p o we r be f o re s e r v ici ng or i n s t al l ing t h is u n it . M u lti ple po w e r s o u r c es m a y b e pr esen ...

  • Page 28: Wiring Diagrams

    28 wiring diagrams wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. Wa rn in g hi gh v o l t age ! Di s c onne ct al l p o we r be f o re s e r v ici ng or i n s t al l ing t h is u n it . M u lti ple po w e r s o u r c es m a y b e pr esen ...